Professional Documents
Culture Documents
S I 32-251-3
S I 32-251-3
om
For
AIR CIRCUIT BR E AKE R TYP E S
75DH250E/500E AND 150DH1SOE/250E/500E
1200-2000 AMPERE RATINGS
.c
ls
ua
an
•
tM
These supplementary instructions are to be used in conjunction
NOVEMBER, 1959
ww
U
.
W E S TI N G H O S E E L E C T R 1,- C C 0 R P 0 R A TI 0 N
ASSEMBLED SWITCHGEAR DEVICES
om
DESCRIPTIOH
The Type 75 DHE and 150 DHE Air Circuit Breakers are 3-pole, electrically operated, hor
.c
izontal drawout units for metal-clad switchgear. The rating of the br�akers are as follows:
Interrupting Rating 250 MVA 500 �t'/A 150 �WA 250 MVA 500 MVA
ls
Continuous 60 Cycle
Rating 1200-2000 A. 1200-2000 A. 1200 A. 1200-2000 A. 1200-2000 A.
ua
Rated Voltage 7200 v. 7200 v. 13800 v. 13800 v. 13800 v.
an
•
Minimum Voltage For
Interrupting Capacity 4600 v. 6600 v. 6600 v. 6600 v. 11500 ·v.
Interrupting Current
At Rated Voltage
��ximum Interrupting
Current
20000 A.
32000 A�
40000 A.
44000 A.
tM 6300 A.
13000 A.
10600 A.
22000 A.
21000 A.
25000 A.
ar
Figure 1 shows a typical breaker completely assembled as it is placed into the cell.
lP
ca
tri
lec
.E
w
.·
ww
om
Figure 2 shows the barrier removed, the arrangement of the center coil arc chutes, the
contacts,and the solenoid operating mechanism.
.c
-----
• \ · ARC OiUTE
LIFTING
PIN
n � ARCOiUTE
ni ,lLL-
ls
.
I
. I'
I , I
BLOWOUT
WAGNET
I ! i
ua
,,_
I HINGE BRACKET
4 [
HINGE PIN
an
ARC OiUTE
tM
SUPPORT
SECONDARY
CONTACT ROLLER ARM
SLIDE AND ROLLER
ar
MANU.>.L
CLC51SG
SOCKET
lP
ca
These components are supported on a welded steel frame �bich is mounted on flanged
lec
wheels for driving it into the metal clad cell. In t!:e l011er part of the fra:r.e is also lo
cated the levering-in device for moving the breaker into final contact engage�ent. This de
vice is interlocked with the mechanism to prevent inserting or withdrawing the breaker with
the contacts closed. Also located in the lower part of the frame are the secondary contact-s
for automatically disconnecting the control wiring when the breaker is withdrawn, the a uxil
.E
The arc chutes on this breaker are of the center coil design. In this type of construc
tion, the magnetic circuit is H-shaped with the cross member of the H passing through the
center of the arc chute. The blowout coils are wound around the cross member of the H and
w
3
AIR .CIRC.UIT BREAKE R TYPES 75 DHE.·lSO DHE
om
With this type of construction, the magnetic core passes through the center of the arc
chute, and is an integral part of the arc chute assembly. To provide easy accessibility for
contact maintenance and inspection, the arc chutes are h inged at the rear, and a simple tilt
ing device is provided. Figure 3 shows the breaker with the arc chutes til ted back. The
.c
levering-in device is used-to supply the mechanical advantage for tilt � ng the arc chutes.
ls
ua
an
---
tM
ar
lP
ca
J1
tri
lli!£J:i����;.;...�..._. �����'�;.::�:£�.:d .
lec
. FIG. 3. CIRCUIT BREAKER \tiTH MAIN BARRIER REI�OVED AND ARC CHUTES RAISED
A barrier assembly is placed on the breaker before it is rolled into its cell. The
front sheet is 1/8 inch steel to form a grounded barrier between personnel and live parts
.E
when the unit is in the cell. �he barrier assembly is in four parts for convenience in han
dling. There are three separate insulating barrier compartments - a left, center, and
right unit placed side by side. The front steel barrier is supported by two hangers which
engage the barriers at the top. The bottom of the barrier is secured with two hexagon head
·bolts which attach to the frame structure.
w
ww
AIR CIRCUIT BREAKER TYPES 75 DH E•lSO DHE
om
RECEIVING, HANDLING AND STORING
The receiving, handling and storing of the breakers should be done in the manner set
forth in the instruction book I. B. 32-25 1·3. The approximate weight of the breakers and the
.c
various parts are as follows.
ls
and barriers 950 pounds 1230 pounds
ua
Barrier assembly 200 pounds 200 pounds
an
•
INSTALLATION
tM
With the exception o f the arcing chambers and the barriers, these breakers are shipped
completely assembled and adjusted. No adjustment should be required and none should be made
unless obviously needed.
CAUTION: Severe in j ury may be sustained if any part of the body is str:�ck by the con
ar
tact arms since they move very rapidly in the opening stroke. Personnel working about the
breaker should stay clear of the space in which the contact arms move while the breaker is
closed or being closed. If breaker has b�el) closedby hand, always remove the hand closingl ever
lP
before tripping.
The following sequence of operation stould be performed in preparing th� brea�er for
ca
use:
1. Breakers are usually shipped with the contacts closed and with a tie on the t:::-ip lever
to prevent tripping. After the breake� is unpacked and the shipping ties and braces re
moved, take off the tie on the trip lever and trip the breaker. Then close t�e breaker
tri
carefulls by hand using the removable hand closing lever. �lake certain that all parts
are functioning properls in that there is no binding or excessive friction. As the con
tacts touch near the end o f the closing stroke, the force necessary to close the breaker
lec
increases rapidly.
2. �ith the breaker in the closed position, check the contacts to make certain that the ad
justments have not been disturbed. For Proper settings, refer to Figure 24 o f
I. B. 32-25 1-3. If adjustments are required, they may be made as described on Page 23.
.E
A light film o f grease is applied to both the arcing and main contacts before the breaker
is operated at the factory. This film is normally removed be fore shipment. Be fore the
breaker is placed in service, inspect all contacts to see that they are free o f oil or
grease.
w
3. The breaker is more easily handled with the arc chutes and barriers removed. Mount these
�
parts after the breaker has been moved near the metal clad cell · tructure. Before in
�
stalling the arc chutes, play a stream of dry compressed air throu h them from each end
ww
to remove any dust or foreign matter. Then examine the chutes to make certain that the
vents and slots are free o f any foreign material.
5
A I,R: CIR C U I T B R E A K ER TYPES 75 DHE•lSO DHE
om
4. ��unt the arc chutes one at a time in the following manner:
a. Place a rope sling through the 5/8 dia. stud located at the top center of each arc chute.
.c
b. �
Lift the arc chut s and lower them carefully over each phase making certain that they
center over the contact structure without striking the ceramic pieces.
ls
d. Lower arc chute into place so that back end is between hinge bracket on uPPer bush �ng
flange. Use care in lining up the arc chute so that rear arc horn clip makes good con
ua
tact with upper contact foot.
an
•
g. Tighten lower connection of arc horn connector since it may have come loose during ship
ment.
tM
h. �ake final check by operating breaker slowly by hand, and see that there is no interfer
ence with the movement of the contacts.
is at the top left side, and the other at the top right side. Interchanging the t\\O end
compartments will place the.supporting pins at the incorrect location for the steel front
barrier. After the compartments are slid into place, the steel barrier is placed flatly
ca
against the compartments at a slightly higher elevation and slowly lowered until the hooks
engage the pins at both sides. The lower end of the steel barrier is then secured to the
frame structure with two hex head bolts, making certain that the barrier is vertically
straight in position to enter the cell opening.
tri
6. The breaker is now reads to be operated electrically. Each breaker should' be closed and
tripped electrically several times before being connected to high voltage. These o p e r a
tions may be made at the test position in the cell or by means of other test facilities
lec
prov fded. See Pages 17, 18, 19, and 20 of I. B. 32-251-3 for information concerning plac
ing the breaker in the cell. The _hand closing lever must be always removed from the socket
in the mechanism before making electrical operations. If electrical operation is quick
and positive on both the close and trip, the breaker is now ready to be levered _into the
.E
operating position.
C AUTION: Do not attempt to c lose the breaker by hand against an e nergized circuit. To
insure suf trc i ent closing force and speed, the breaker should be closed el ectrically from an
·adequate power source. See HEMA standard SG-6-213.
w
When the breaker is put into the celi and moved in beyond the tes t yosition, the high
voltage parts will be �nergized. If the barrier is comp letel y assembled on the breaker, per
._ ,
sonnel w i ll f
be pro tec ed from contact with the live parts. If however, the barrier assembly
ww
is left off and the breaker roll ed into the c�IJ, live parts are expo sed. The breaker never
should be rolled into an e nergized cel l st ructure beyQnd the test position without having the
arc chutes and comple te barrier assembl y in pl ace. �
6
om
OPERATION AND ADJUSTMENT
The operation and adjustments of the breaker is the same as that for the breakers de
scribed in I. B. 32-251·3. Reference should be made to Pages 9 through 12 of the I. B. for in
formation covering the Mechanism, Mechanism Panel with its associated tripping device and
.c
auxiliaries, and Mechanism Adjustments.
CONTACT ADJUSTMENT
ls
The contacts on this breaker are the same as those described on Pages 23 and 26,in the
instruction book. AnY adjustments that are necessary should be made as outlined in that sec
ua
tion.
ARC CHUTES
an
The· arc chute, Fig. 15 of I. B. 32-25�3. consists of an H-shaped blowout magnet, blowout
coils, transfer arc horns, transfer s�acks, main interrupter stacks, a front arc horn, and a
rear arc horn, all assembled in and about a fabricated rectangular chute jacket. The arc
chute is hinged to the breaker a nd when it is in the normal position, its lower end completely
surrounds the contact structure.
tM
The blowout magnet is located so that the magnetic core passes through the center of the
arc chute. The blowout coils are wound about the core and lie in windows cut in the chute
ar
side sheets. One terminal of each coil connects to a transfer arc horn and the other terminals
are joined together with the shading coil. Two transfer stacks are placed in the space be
tween the transfer arc horns and the shading coil. To either side of the transfer arc horns
lP
are the main interrupter stacks which are made up of a series of insulating refractory plates.
These plates have inverted V-shaped slots. The slots are off set so that as the plates are
stacked with the slots alternating from one side to the other, the arc must take a serpentine
path as it moves up into the arc chute, thus increasing the length of the arc.
ca
To either side of the main interrupter stacks are two metallic arc horns to which the
arc transfers from the arcing contacts. The front arc horn is connected electrically to the
moving contact hinge, and the rear arc horns automatically connects to the stationary contact
tri
The action of the breaker in interrupting an arc is as follows: Referring to Figllre 15,
lec
when the arcing contacts part and an arc is drawn, it loops up and impinges on the lower ends
of the two transfer arc horns and the shading coil. The two short segments of arc from the
transfer arc horns to the shading coil then move up into the transfer stacks and are quickly
interrupted placing the blowout coil in series with the arc.
.E
When the current starts to flow in the blowout coils, a magnetic field is established
and the arc, which by this time is two separate arcs, extending from the two end arc horns to
the transfer horns,. ts driven very rapidly up into the slots of the refractory plates. As the
arc moves to the closed end of the slots, it is restricted, lengthened, cooled, and subject to
to a strong magnetically induced blast of gas. All of these forces r�sult in rapid "de-ioni
zation" of the arc space, and for the arc to maintain itself it must continually ionize fresh
w
gas. At current zero the formation ot·new ionization momentarily cea�es, but the de-ionization
continues so that dielectric strength is established in the arc space ana the circuit is in
..
ww
terrupted.
7
AIR CIR CUIT B RE AKER TYPES 75 DHE•lSO DHE
---·�---
om
ARC CHUTE LIFTER
In order to raise the arc chutes for contact inspection and maintenance, an arc chute
lifter is provided. This attachment which uses the mechanical advantage of the levering-in
.c
device to provide the lifting·force, consists of a 1" diameter steel bar, and two channel
·
shaped arms. The steel bar is inserted through the arc chute openings, and the arms are se
cured in place as shown in Fig. 3.
ls
1. Remove barrier assembly.
ua
2. Place 1" diameter steel bar through large 1-1/8 diameter holes in front of arc chutes.
3. Fasten the channel arms to the ends of the 1" diameter bar.
Place crank on levering-in devi.ce operating shaft and rotate clo.ckwise so that the rollers
an
4.
at each side of the breaker advance forward e�ough to insert the opposite end of the chan
nel arms. Clamp the arms over the roller$.
6.
tM
Place crank on levering-in operating shaft and continue to rotate clockwise to raise the
arc chute to position shown in Figure 3.
ar
It i s important that the arc chutes be raised until the indicator on the front of the
breaker shows that the full travel of the levering-in device has been used. This releases
the mechanism interlock and permits the breaker to be closed and tripped either electrically
lP
To lower the arc chutes acd prepare the breaker for return to service, repe a t �te stEps
1 to 6 in reverse order.
ca
CAUTION: After inspecting the contacts and arc chutes ana before returning the breaker
to service, make certain that the shunt connection to the front arc horns is bolted tight.
tri
H O RIZONTAL D R A WO U T A RR A N G EM ENT
lec
The breaker is arranged for use in horizontal drawout metal clad equipment and any qu.::::;
tions pertaining to this arrangement, which includes operation of the breaker levericg-in de
vice, should be referred to I.B. 32-251-3 Pages 8 through 22.
.E
MAINTENANCE
Maintenance procedure for the air circuit breaker, refer to I.B. 32-251-3, Pages 26
through 30.
w
PARTS IDENTIFICATION
Instruction Book 32-251-3 illustrates similar parts used on these breakers. Parts for
ww
8
....
.
· � AIR CIRCUIT BRE AKER TYPES 75 DHE•lSO DHE
om
type and rating bf the breaker for which the parts are required. The breaker nameplate will
identify the breaker type and rating.
.c
MOTOR OPERATED BREAKERS
ls
ua
an
•
tM
ar
lP
ca
tri
lec
.E
w
ww
9
'
'
· '
-
ww
w
.E
lec
tri
ca •
MEMORANDUM
lP
-
ar
-.
tM
an
ua
ls
.c
om
� . ••of'f';.;:..,
< •
,; .... '1
..
MEMORANDUM
om
.c
ls
ua
an
•
tM
ar
lP
ca
tri
lec
.E
w
ww
ww
w
.E
lec
tri
ca
lP
ar
tM
an
ua
ls
.c
om
SUPPLEMENT NO. 2 1.8. 32-251-3
om
SUPPLEMENTARYINS TRUCTIONS
.c
ls
-
ua
c CJ!'-
an
#ttck fff�e
tM
ar
These supplementary instructions are to be used in conjunction
APRIL, 1963
ww
DESCRIPT ION
(
.c
The Type 1 50·DH·750E Air Circuit Breaker is a 3-pole, electrically operated, horizontal
drawout unit for metal-clad switchgear. The rating of the breaker is as follows:
ls
2. Continuous current at 60 cycles 1 200 and 2000 amperes
ua
4. Maximum design voltage 1 5. 0 KV
'
l
I
5. Minimum voltage for rated interrupting capacity 1 1. 5 KV
an
f 6. Interrupting current at rated voltage 3 1 . 500 amperes
!
tM
Figure 1 shows a typical breaker completely assembled as it is placed into the cell.
ar
c
lP
ca
tri
lec
i!
ll
I
.E
w
0
ww
2
om
AIR CIRCUIT BREAKER TYPE 150-DH·750E
Figure 2 shows the arrangement of the center coil arc chutes, the contacts, and the
solenoid operating mechanism.
.c
l
�
ls
I
l ARC CHUTE
;�
ua
i BLOWOu o
!
---- MAGNET
t HINGE BRACKET
t' HINGE PIN
•
an
I SECONDARY
CONTACT tM
SLIDE
ar
MANUAL
CLOSING
SOCKET
lP
ca
f
lec
These components are supported on a welded steel frame which is mounted on flanged wheels
for driving it into the metal clad cell. In the lower part of the frame is also located the
levering-in device for moving the breaker into final contact engagement. This device is in
terlocked with the mechanism to prevent inserting or withdrawing the breaker with the contacts
closed. Also located in the lower part of the frame are the secondary contacts for automati
.E
cally disconnecting the control wiring when the breaker is withdrawn, the auxiliary switch,
,
and other auxiliary devices.
The arc chutes on this breaker are of the center coil design. In this type of construc
tion, the magnetic circuit is H-shaped with the cross member of the H passing through the
center of the arc chute. The blowout coils are wound around the cross member of the H and
w
With this type of construction, the magnetic core passes through the center of the arc
ww
chute, and is an integral part of the arc chute assembly. To provide easy accessibility
3
AIR CIRCLIT BREAKER TYPE 1S0-DH·750E
om
.c
ILt
ls
lrT
ua
INTERRUPTER PLATES
v
- ,..... I
I
I
I
an
I
I
1.-/
---. 1 I
,----
1
I
I
I
I
tM - -- -,
I
I
I
I
I
a
1\
ar
I I
I I
I I
I I
I I
�:-:::.
I
-:::. ==='\.--- -r----
I 1
I
1 I
lP
I I I
a:
ca
--- �
: a:
tri
I
I
_.._ ___ _
lec
-::- �
.E
/ I TRANSFER STACKS
w
.c
ls
ua
an
tM
ar
lP
ca
FIG. � CIRCUIT BREAKER WITH MAIN BARRIER REMOVED AN D ARC CHUTES RAISED
tri
lec
l
for contact maintenance and inspection, the arc chutes are hinged at the rear, and a simple
.E
tilting device is provided. Figure 4 shows the breaker with the arc chutes tilted back. The
levering-in device is used to supply the mechanical advantage for tilting the arc chutes.
A barrier assembly is placed on the breaker before it is rolled into its cell. The front
sheet is 1 /8 inch steel to form a grounded barrier between personnel and live parts when the
unit is in the cell. On the 150-DH-750E breakers, the barrier assembly is in three parts for
w
convenience in handling.
ww
s
A�R CI�'IT BREAKER TYPE ISO·DH·750E
om
RECEIVING, HANDLING AND STORING
f
.c
The receiving, handling and storing of the 150-DH-750E breaker should be done in the man
ner set f orth in the instruction book I. B. 32-251-3. The approximate weight of the breaker
and the various breaker parts is as follows.
ls
Breaker Parts 1200 Amperes 2000 Amperes
ua
Breaker without arc chute
and barriers 950 pounds 1230 pounds
an
Barrier assembly 200 pounds 200 pounds
tM
INSTALLATION
ar
With the exception of the arcing chambers and the barriers, these breakers are shipped
completely assembled and adjusted. No adjustment should be required and none should be made
unless obviously needed.
lP
CAUT ION : Severe injury may be substained if any part of the body is struck by the con
tact an1s since they move very rapidly in the opening stroke. Personnel working about the
breaker should stay clear of the space in which the contact arms move while the breaker is
ca
closed or being closed. If breaker has been closed by hand, always remove hand closing lever
before tripping.
tri
The following sequence of operation should be performed in preparing the breaker for use:
1. Breakers are usually shipped with the contacts closed and with a tie on the trip
lec
lever to prevent tripping. After the breaker is unpacked and the shipping ties and
braces removed, take off the tie on the trip lever and trip the breaker. Then close
the breaker carefully by hand using the removable hand closing lever. Make certain
that all parts are functioning properly in that there is no binding or excessive
friction. As the contacts touch near the end of the closing stroke, the force nec
.E
2. With the breaker in the closed position, check the contacts to make certain that the
adjustments have not been d isturbed. For proper settings, refer to Figure 24 of
I.B. 32-251-3. If adjustments are required, they may be made as described on Page
23. A light film of grease is applied to both the arcing and main contacts before
w
the breaker is operated at the factory. This film is normally removed before ship
ment. Before the breaker is placed in service,
are free of oil or grease .
inspect all contacts to see that they
•
ww
AIR CIRCUIT BREAKER TYPE JSO-DH-750E
om
• 3. The breaker is more easily handled with the arc chutes and barriers removed.
these parts after the breaker has been moved near the metal clad cell structure.
Mount
Before installing the arc chutes, play a stream of dry compressed air through them
.c
from each end to remove any dust or foreign matter. Then examine the chutes to make
certa]n that the vents and slots are free of foreign material.
a. Place a rope sling through the 5/8 dia. stud located at the top center of each
ls
arc chute.
b.
ua
Lift the arc chutes and lower them carefully over each phase making certain that
they center over the contact structure without striking the ceramic pieces.
an
d. Lower arc chute into place so that back end is between hinge bracket on upper
bushing flange. Use care in lining up the arc chute so that rear arc horn clip
makes good contact with upper contact foot.
tM
e. Insert hinge pin and put cotter pins in place.
g. Tighten lower connection of arc horn connector since it may have come loose dur
ar
••
ing shipment.
h. Make final check by operating breaker slowly by hand. and see that there is no
lP
5. The interphase barrier should now be put in place. Because of the size and weight,
the barrier assembly is divided into four parts. The center part goes on first and
ca
I
is aligned by the two locating pins on the breaker frame. Asingle bolt in the center
holds it in place. The two outside sections mount next. Make sure the lower rear
corner of the Micarta plate goes to the inside of the steel gussets on the breaker
I
frame. These two parts are aligned by locating pins in the lower front corners and
tri
bolts to the center barrier. Two bolts at the lower front corners hold these assem-
blies in place.
lec
6. The breaker is now ready to be operated electrically. Each breaker should be closed
and tripped electrically several times before being connected to high voltage. These
operations may be made at the test position in the cell or by means of other test
facilities provided. See Pages 17, 18. 19, and 20 of I.B. 32-251-3 for information
concerning placing the breaker in the cell. The hand closing lever must be always
removed from the socket in the mechanism before making electrical operations. If
.E
electrical operation is quick and positive on both the close and trip, the breaker
is now ready to be levered into the operating position.
w
•
ww
- -
---..--------.-- �-�· -·-·-------·-- ·-· __,_ __,_._.._--------.- -
om
AIR CIRCUIT BRE AKER TYPE l50·DH-750E
CAUTION: Do not attempt to close the 150-DH-750E breaker by hand against an energized
circuit. To insure sufficient closing force and speed, the breaker should be closed elec
trically from an adequate power source. See NEMA standard SG-6-213 .
.c
When this breaker i s put into the cell and moved in beyond the test position, the high
voltage parts will be energized. If the barrier is completely assembled on the breaker, per
sonnel will be protected from contact with the 1 ive parts. If however, the barrier assembly
is left off and the breaker rolled into the cell, 1 ive parts are exposed. The breaker never
ls
f
should be rolled into an energized cell structure beyond the test position without having the
complete barrier assembly in place. '
ua
OPERATION AND ADJUSTMENT
The operation and adjustments of the breaker is the same as that for the breakers de
an
scribed in I . B. 32-2 5 1 -3. Reference should be made to Pages 9 through 12 of the I . B. for
information covering the Mechanism, Mechanism Panel with its associated tripping device and
auxiliaries, and Mechanism Adjustments.
tM
CONTACT ADJUSTMENT
The contacts on this breaker are the same as those described on Pages 23 and 26 in the
instruction book. Any adjustments that are necessary should be made as outlined in that sec
ar
tion.
ARC CHUTES
0
lP
The arc chute consists of an H-shaped blowout magnet, blowout coils, transfer arc
horns, transfer stacks, main interrupter stacks, a front arc horn, and a rear arc horn.
ca
all assembled in and about a fabricated rectangular chute jacket. The arc chute is hinged
to the breaker and when it is in the normal position, its lower end completely surrounds
the contact structure. Figure 3 is a schematic cross section of the arc chute showing the
component parts.
tri
The blowout magnet is located so that the magnetic core passes through the center of the
arc chute. The blowout coils are wound about the core and lie in windows cut in the chute
jackets side sheets. One terminal of each coil connects to a transfer arc horn and the other
lec
terminals are joined together with the shading coil. TWo transfer stacks are placed in the
space between the transfer arc horns and the shading coil. To either side of the transfer arc
horns are the main interrupters stacks which are made up of a series of insulating refractory
plates. These plates have inverted V·shaped slots. The slots are off set so that when the
plates are stacked with the slots alternating from one side to the other, the arc must take
.E
a serpentine path as it moves up into the arc chute, thus increasing the length of the arc.
To either side of the main interrupter stacks are two metallic arc horns to which the
arc transfers from the arcing contacts. The front arc horn is connected electrically to the
moving contact, and the rear arc horns is connected to the stationary contact when the arc
chute is lowered to its normal position.
w
0
ww
I, 8
l
AIR CIRCUIT BREAKER TYPE 150-DH-7SOE
om
The action of the breaker in interrupting an arc is as follows: Referring to Figure 3.
when the arcing contacts part and an arc is drawn. it loops up and impinges on the lower ends
of the two transfer arc horns and the shading coil. The two short segments of arc from the
.c
transfer arc horns to the shading coil then move up into the transfer stacks and are quickly
interrupted placing the blowout coil in series with the arc.
I When the current starts to flow in the blowout coils. a magnetic field is established and
the arc, which by this time is two separate arcs, extending from the two end arc horns to the
.I
r
ls
transfer horns, is driven very rapidly up into the slots of the refractory plates. As the arc
moves to the closed end of the slots, it is restricted, lengthened, cooled, and subject to a
1
strong magnetically induced blast of gas. All of these forces result in rapid "de-ionization"
ua
of the arc space. and for the arc to maintain itself it must continually ionize fresh gas. At
current zero the formation of new ionization momentarily ceases. but the de-ionization contin
ues so that dielectric strength is established in the arc space and the circuit is interrupted.
an
ARC CHUTE LIFTER
In order to raise the arc chutes for contact inspection and maintenance, an arc chute
lifter is provided. This attachment which use� the mechanical advantage of the levering-in
tM
device to provide the lifting force, consists of a 1 " diameter steel bar, and two channel
shaped arms. The steel bar is inserted through the arc chute openings, and the arms are se
cured in place as shown in Figure 4.
2. Place 1" diameter steel bar through large 1 -1 /8 diameter holes in front of arc chutes.
3. Fasten the channel arms to the ends of the 1 " diameter bar.
ca
4. Place crank on levering-in device operating shaft and rotate clockwise so that the rollers
at each side of the breaker advance forward enough to insert the opposite end of the chan
nel arms. Clamp the arms over the rollers.
tri
6. Place crank on levering-in operating shaft and continue to rotate clockwise to raise the
lec
It is important that the arc chutes be raised until the indicator on the front of the
breaker shows that the full travel of the levering-in device has been used. This releases
the mechanism interlock and permits the breaker to be closed and tripped either electrically
or manually with the arc chutes in the raised position.
.E
To lower the arc chutes and prepare the breaker for return to service, repeat the steps
1 to 6 in reverse order.
CAUTION: After inspecting the contacts and arc chutes and before returning the breaker
to service, make certain that the shunt connection to the front arc horns is bolted tight.
w
ww
9
om
AIR CIRCl"IT BREAKER TYPE 150-DH·750E
.c
The 15 0-DH-75 0E is arranged for use in horizontal drawout metal clad equipment and any
questions pertaining to this arrangement, which includes operation of the breaker levering-in
device. should be referred to I. B. 32-25 1 -3 Pages 8 through 22.
ls
MAINTENANCE
For maintenance procedure on the 1 5 0-DH-75 0E air circuit breaker, refer to I. B. 32-2 5 1 -3 ,
ua
Pages 26 through 30.
PARTS IDENTIFICATION
an
Instruction Book 3 2 -2 5 1 -3 illustrates similar parts used on these breakers. Parts for a
Particular breaker can be identified by these illustrations, specifically mentioning the type
and rat ing of the breaker for which the parts are required. The breaker nameplate will iden
tify the breaker type and rating.
tM
MOTOR OPERATED BREAKERS
A separate instruction book is supplied for breakers having a motor-spring type of clos
ar
ing mechanism, and are supplied with the order involving this type of equipment.
0
lP
ca
tri
lec
.E
w
0
ww
10
om
MEMORANDUM
.c
ls
j,:;-o D !-1 7tJO t=
ua
an
tM
ar
lP
ca
tri
lec
I
.E
w
c
ww
/�Y�-s-
om
)-�
17 )� {·
.c
ls
ua
an
tM
ar
lP
ca
tri
lec
.E
' .
: .
.. . �
.: .
-c .. ; . .._
,' ... j' ...
• )'
I'
.
I
w
0
ww
I
..
I
I
f
om
.c
ls
ua
INSTRUCTION BOOK
an
tM
De-ion®
ar
'·· - ,. .
, ,,· -
.. ..
...
.
.
•,
·�: .,_>'�
lP
...
..
ca
�· . ��- '
·. . ,. .
tri
.. .
lec
:r -
--�--
.
----- • y ; .�_
.E
. ·.. ·
.:· E I e c t r ic C o r p o r a t i on-
:
.
. · .
.
��.
'
• • 'o. , f. ' f ' • '
• " . �·· .
< ,·', • I
.if I ·,
ww
.
.
_ : ·,: �- / ·. ' ... LB. 32-251-3
1.8. 32-251-3
om
RECEIVING • OPERATION • MAINTENANCE
INSTRUCTIONS
.c
ls
ua
De-ion@
AIR CIRCUIT BREAKER
an
Type DH
tM
Horizontal Drawout
ar
Indoor and Outdoor Service
lP
INTERRUPTING
VOLTAGE RATINGS
ca
3-PHASE RATINGS-AMPERES
AIR AMPERES
INTER-
CIRCUIT CONTIN·
RUPTING Min. KV.
BREAKER Max. uous At
RATING Rated for Rated Max.
TYPE Design 60 CYCLES Rated
MVA. KV. INT. Amperes
KV. Voltage
MVA.
tri
SWITCHGEAR DIVISION
Printed in U.S.A.
om
TABLE OF CONTENTS
\ DESCRIPTION Pages 5-7
I
Part One
Description. 5
.c
Part Two RECEIVING, HANDLING AND STORING Page 8
Receiving. 8
Handling. 8
Storing. 8
ls
Weights. 8
ua
Part Three
Operation .. 8
Mechanism..... 8
Mechanism Panel ... 9
Shunt Trip Magnet................. . 9
an
Cut-Off Switch.. .... . ... . . . . . . . . . . . . . . . . . . II
Contact Position Indicator. . .. . . . . . . . . . . . . . . . 11
Interlock Position Indicator .................... 11
Operation Counter ...................... . I2
tM
Auxiliary Switch.. . . . .. . .. . . . . . . . . . . . . . . I2
Latch Check Switch ......... I2
Undervoltage Trip Attachment ......... ...... . I2
Three-Coil Trip Attachment................... . I2
Contacts...... . . .. . . ... . I3
ar
. . . . . . . . . . . . . . . . . .
Arc Chutes...................................... I6
Levering-In Device.................................. . I7
Test Position....................................... I9
lP
Operating Position.. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Interlock.... . . .
. . . . .. . . . . . . . . . . . . . . . . . . . . . . . . 20
Secondary Contacts................................. 20
Ground Contact................................... . 2I
ca
Puffer Assembly..................................... 2I
Mechanism Operated Control Switch.................. . 22
Secondary Control Wiring........................ . 22
tri
Arc Chutes. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . ... .... 27
Broken or Cracked Ceramic Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ... . .. 28
3
Part Six MAINTENANCE (Continued) Pages 26-30
om
Erosion of Ceramics...... . . . . . ..... . . . ..... . ... . . . .................. . 28
Dirt in Arc Chute.... . . . . ... . .... . . . . ..................... . ....... . ....... . 28
Cleaning Arc Shields.. . ....... . .............................. . ........... . 28
Operating Mechanism..... . .... . ............ . ........... . .................... 28
Lubrication.... . ....... . ....................................... . ..... . .... 28
Clearances............... . ....... . .. . ....... . . ........... . .... . .........
.c
. 29
Puffer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Puffer Nozzle. . . . . . . ... . . ............ . ........... . ... . . ......... . ........ . . . . 30
Auxiliary Switch...................................... . ........ . ...... . .... . 30
Insulation............................................................. . ... . 30
ls
Part Seven PARTS IDENTIFICATION Pages 30-34
Parts Identification...... . ......... .... . . ....... . ..... . ....... . . . ............ . 30
Identification Photographs . . . . . . . . . . . . . . . .... . . ..... . ... ..... . ................ 31
ua
Fig. 25 Moving Contact Assembly...................... . ....... . . ....... 31
Fig. 26 Stationary Contact Assembly. . . . ........................... . .. ....... 32
Fig. 27 Mechanism Assembly. . .......... . . . ........ . .......... . . .... . ... . .. 33
Fig. 28 Puffer Assembly . . . .. . ..... . ...... ...... . . . ......... ...... . .. .. . ... . 34
an
Fig. 29 Auxiliary Switch.... . ................ . . . ............... . . . .......... 34
Renewal Parts. . .............................. . ................. . ... ... . ..... 30
LIST OF ILLUSTRATIONS
Figul'e
1
2
3
Type 50-DH- 250-E, 1200 Amp. Breaker, Completely Assembled..............
Type 50-DH- 250-E, 1200 Amp. Breaker, Completely Assembled, Rear View.. . .
Type 50-DH- 250-E, 1200 Amp. Breaker with Barrier Removed, Front View.....
tM .
.
Page
2
5
ar
. 6
'
4 Type 50-DH- 250-E, 1200 Amp. Breaker, with Barrier Removed and Arc Chutes
5
Tilted Back for Inspection.... . . .
'
6 Solenoid Operating Mechanism. Diagram of Tripping Positions... . . 10
7 Mechanism Front Panel. . ........... . .......... . . . .... . . . . ..... 11
8 Undervoltage Trip Unit..................... . . ...................... 12
9 Type 50-DH-150-E, 1200 Amp. Breaker Contacts Viewed from Rear...... . 13
ca
10 Type 50-DH-250-E, 1200 Amp. Breaker Contacts Viewed from Rear.. . ... . . 14
11 Type 50-DH-150-E /250-E, 2000 Amp. Breaker Contacts Viewed from Rear . . . . . 14
12 Type 50-DH-150-E, 1200 Amp. Breaker Contacts Viewed from Front . ...... . . . . . 15
13 Type 50-DH- 250-E, 1200 Amp. Breaker Contacts Viewed from Front....... . .. . 15
tri
14 Type 50-DH-150-E /250-E, 2000 Amp. Breaker Contacts Viewed from Front.. . . . 16
15 Arc Chute Arrangement................................................. 17
16 Partially Assembled Arc Chutes... . .. .. .. ... . . .. . ..... . . . . . . . . . . . . . . . . . . . 18
lec
4
om
.c
ls
ua
an
tM
ar
lP
ca
2
PART ONE
om
DESCRIPTION
-
The type 50-DH-150-E and 50-DH- 250-E air cir
.c
cuit breakers are three-pole, electrically operated,
horizontal drawout units for use in metal-clad switch
gear. The ratings of the breakers are tabulated on
page l.
Figure 1 shows the front and right side of a type
50-DH-250-E breaker completely assembled, while
ls
Fig. 2 shows the breaker from the left rear ready
to be placed in the cell. Figure 3 is the same breaker
ua
with the main barrier removed, and shows the
center-coil arc chutes in their operating positions.
Part of the separating contacts, primary disconnect
ing contacts, insulated operating rods, auxiliary
switch and part of the solenoid operating mecha
an
nism are visible. These components are supported
on a welded steel frame which is mounted on
flanged wheels for rolling into the metal-clad cell.
In the lower part of the frame is located the levering
tM
in device for moving the breaker into final contact
engagement. This is interlocked with the mecha
nism to prevent inserting or withdrawing the breaker
with the contacts closed, and also prevents closing
the contacts unless the breaker is completely in or
ar
completely out of the cell. Also located in the lower
part of the frame are the auxiliary switch, shunt trip,
cut-off switch, latch check switch, operation counter,
lP
tilted back. In this position, the contacts are readily ings, to facilitate moving the breaker. The wheel
available for inspection and maintenance. flanges engage with rails to align the breaker in the
A one piece barrier assembly is placed on the metal-clad cell.
breaker before it is rolled into the cell. The front The six main primary conductors project hori
sheet is of one-eighth inch steel and forms a ground zontally from the rear of the breaker, and are sup
ed barrier between personnel and live parts when ported and insulated by Redarta bushings. At the
w
the unit is in the cell. rear of these main conductors are the primary dis
The Type 50-DH-150-E and 50-DH-250-E air cir
,
connects which are clusters of contact fingers ar
cuit breakers are arranged for use in metal-clad ranged to engage the primary conductors in the
ww
5
DESCRIPTION ------
om
.c
ARC CHU T E
ls
B L OWOUT MAGN ET
ua
A RC CH U T E H IN G E
an
SHUNT CON N ECTION
P RIMARY
D I SCON N E CTS
D EV I C E A R M
O P E RATING SH A FT
M ECHAN I SM PANEL
tri
lec
FIG. 3 . Type 50-DH-250-E, 1 200 Ampere Breaker with Barrier removed, Front View
.E
w
f)):
ww
6
DESCRIPTION __________________________________ ������----------� 1 -=
B�-�
32�
-2
�5�
1-
� 3
om
50-DH-150 & -250 A I R C I RC U I T BREAKERS
.c
ls
ua
an
tM
ar
lP
ca
tri
7
om
PART TWO
.c
All Type DH breakers are assembled and given After the breaker is unpacked, the best way to move
operating tests at the factory, after which they are it is by rolling on its own wheels.
carefully inspected and prepared for shipment by If it is necessary to lift the breaker after it is un
workmen experienced in the proper handling and crated, lift it without the barrier or arc chutes in
packing of electrical equipment. The complete place. Slings may be placed under the breaker
ls
breaker is shipped in a single crate. The breaker frame or hooks used in the holes provided near the
frame is located at the front of the crate, with the top of the frame.
interphase barrier installed. The three arc chutes STORING
ua
are individually packaged and are located at the The arcing chambers are shipped in separate
rear of the crate. containers located at the rear of the crate to guard
After the equipment has been unpacked, make against damage from rough handling and for better
a careful inspection for any damage which may have protection from dust and water or liquids. Store
occurred in transit. If the apparatus has been dam them in their shipping containers until ready for use.
an
aged, file a claim immediately with the carrier and Store all components of these breakers in a clean
notify the nearest Westinghouse Sales Office. dry place. During the storage period, keep them
sufficiently warm to prevent moisture condensation.
HANDLING
Table of Approximate Weights (In Pounds)
tM
Remove the crating and packing carefully. To
avoid damage from improper handling of crow-bars BREAKER
or other tools, use a nail puller for the uncrating. BREAKER AMPERE WITHOUT SINGLE BA RRIER COM·
TYPE RATING CHUTE ARC ASSEM· PLETE
Care must be used in handling the arc chutes since & CHUTE BLY BREAKER
!,
..
PART TH REE
ca
OPERATION
tri
Before placing the circuit breaker in service, it This insures that the main contact surfaces will re
is advantageous to become familiar with the con main free of burning and pitting for good current
struction and function of the various parts which carrying capacities. Above the arcing contacts are
lec
are described in the following paragraphs. This located the center-coil arc chutes for extinguishing
material should be studied carefully. the arc while the breaker contacts are separating.
The general arrangement of the breaker com The breaker is tripped by lifting the primary latch
ponents is shown in Fig. 3. The solenoid coil is built either manually or electrically by means of the trip
to exert a horizontal force on the mechanically trip coil.
free linkage of the mechanism. This linkage, in tum,
.E
MECHANISM
exerts an upward force on the three insulated oper The solenoid operating mechanism with its trip
ating rods which act on the moving contact arms free linkage is shown in Fig. 5, with the operation
to close the contacts. The breaker . has two sets of of the linkage diagrammed in Fig. 6. In this mecha
contacts: the main contacts for carrying the con nism, the horizontal pull of the solenoid coil is trans
tinuous load current, and the arcing contacts for mitted to the contact operating rods through a sys
w
carrying the current during interruption. As the tem of links which rotate counterclockwise about
contacts close, the arcing contacts touch first to the operating center. This linkage system consists
establish the circuit, and then the main contacts of four major links: the non-trip free lever, trip free
ww
follow closed. On opening, the main contacts lever, upper trip free link, and lower trip free link.
separate first and then the arcing contacts follow. These members are arranged as shown and are held
8
OPERATION ------------------------------------ 2-���1�
��B -�3� -3
������� ���B· ;
50-DH-150 &-250 AIR CIRCUIT REAKERS
om
C O N TA C T
P OS I T I O N
I N D IC A T O R
.c
ls
N O N· T R I P
F RE E L E V E R
ua
TRIP FREE
�---
L OW E R T R I P L EVER
F REE LINKS
an
SOL ENOID
COIL
tM
C LO S I N G
L A T CH
ar
lP
to form a rigid member by the cam link and tripping under the force of the contact springs, and the
cam. The tripping cam is prevented from rotating accelerating springs on the puffer rods. The j unction
by the tripping latch. of these links moves to the right, and the trip free
tri
When the solenoid is energized, the movable core lever rotates clockwise opening the breaker contacts.
pulls on the j unction of the non-trip free lever and The position of the linkage is then as shown in the
the lower trip free link through the closing link. This TRIP FREE POSITION, Fig. 6B .
causes the system to rotate about the operating In moving to this position, the lower trip free link
lec
center as the parts move from the RESET POSITION, presses the closing latch downward, and disen
Fig. 6C, to the CLOSED POSITION, Fig. 6A. The gages the pin in the non-trip free lever. The re
trip free lever then exerts an upward force on the trieving spring now pulls on the solenoid core which
three operating rods to close the breaker contacts. moves the linkage and the tripping cam to the reset
The mechanism linkage is held in this position by position as shown in Fig. 6C. In this position the
.E
the closing latch which locks on a pin at the bottom tripping latch is reset, and the breaker may be
of the non-trip free lever. reclosed.
The breaker is tripped either electrically or manu MECHANISM PANEL
ally by lifting the primary latch which disengages The mechanism panel is mounted on the front of
the tripping latch. This allows the tripping latch to the closing mechanism as shown in Fig. 7. On it are
rotate counterclockwise and release the tripping mounted the following auxiliary devices included as
w
9
om
OPERATION-----
� i)
C O N TA C T
. , , / .')
A DJUSTING STUD
I N S U L AT E D
.c
/
OPERAT I N G R O D ------J / O P E R AT I N G
CENTER
LOCK I N G NUTS --�,.-----J
UPPER TRIP
TRIP FREE LEVER FREE LINK STAT I O N A RY
l
LOW E R T R I P CORE
MAGNET
ls
FREE LINK
TRIPPING L ATCH M O VA B L E BACK
CLOSI N G LINK CORE P L AT E
ua
P R I M ARY
LATCH
an
tM -------
ar
-
A
.
C LO S E D POSITION
ca
tri
lec
.E
B c
10
OPERATION------------------------------------------�--�������� 2-�2�
- B�-�3� -3
5 1�
om
50-DH-150 &-250 A I R C I R C U I T BREAKERS
M ECHAN I SM CONTROL
B A RR I E R MOUNTING
.c
B RACK ET
L EV E R I N G- I N D EVICE
O P E RA T IN G SH AFT
ls
ua
L A TCH CHECK
an
SWI TCH CONTACT POSITION
I N D ICATOR
T R IP L EV E R
MAIN TENANCE
tM
CLOSING L E V E R
SOCK E T
S E CONDARY
CONTACT S L I D E
SHU N T T R I P
ar
MAGN ET
lP
ca
breaker electrically from an external source. It may breaker control relays to cut off the closing coil cur·
be equipped with a coil for direct current, alter rent after the breaker is closed. The switch is oper
nating current, or capacitor tripping. When the ated by an arm attached to the trip-free lever in the
lec
shunt trip magnet is energized, the moving core is mechanism and the contact remains closed as long
drawn up into the magnet yoke toward the station as the breaker is closed.
ary core. An extension of the moving core protrudes Contact Position Indicator. The contact posi
through the top of the magnet assembly. As the core tion indicator gives a positive indication that the
moves up, this extension moves against the trip breaker contacts are either open or closed. It oper
.E
lever directly above it. The force of the solenoid is ates directly on the trip-free lever in the mechanism .
sufficient to raise the trip lever which disengages Interlock Position Indicator. The interlock
the primary latch tripping the breaker. A bracket position indicator gives a positive indication of the
at the bottom of the assembly retains the moving position of the breaker interlock. It operates from
core, and limits its travel to about 3f4 inch. A thin the levering-in device shaft. When the indicator
brass washer prevents the moving core from being points to the word OPERATE, the interlock is free
w
retained by residual magnetism in the raised posi and the breaker may be closed or tripped. When
tion after the coil is de-energized. the indicator points to the word INTERLOCKED, the
Cut-Gff Switch. The cut-off switch is a single interlock is functioning and the breaker cannot be
ww
pole normally open contact which acts with the closed. Since the interlock is operative only when
11
om
OPERATION�------
.c
ating Position and the main disconnecting contacts BASE
fully engaged, or that it is in the Test Position with
the contacts separated.
Operation Counter. The operation counter
records each operation of the breaker. It advances
..
.
one count for each tripping operation. A spring type
ls
link from the trip free lever operates the counter.
Auxiliary Switch. The auxiliary switch is a LATCH
PLATE
nine pole rotary type, and is operated by a link from
ua
the trip free lever in the mechanism. There are five
"a" contacts (closed when the breaker is closed),
and four "b" contacts (closed when the breaker is
open). These are arranged alternately, starting with
an
an "a" contact nearest the operating lever. TRI PPI N G
The first and third segments of the rotor are longer SPRING
than the others, and are connected on each side of
the shunt trip coil. When the breaker closes, these
tM
complete the trip coil circuit j ust as the main con TRIPPING LATCH
LINK
tacts touch. The rotor turns approximately 90°, and
is adjusted by the serrated operating lever.
Each contact is able to carry 20 amperes con FIG. 8. Undervoltage Trip Unit
250 a-e 25. 1 5. the device is held magnetically against the station
600 a-e 5. 3. ary core to hold the rod and consequenUy the reset
lever in the reset position. When the coil voltage is
Latch Check Switch. The latch check switch reduced sullicienUy, the reset lever spring over
tri
is a small, light force, snap action switch which is comes the magnetic attraction of the cores and
operated by the primary latch of the mechanism. rotates the reset lever clockwise. As the reset lever
When a breaker is to be automatically reclosed after rotates, the pin pushes against the latch to release
it from its latch plate. When the latch releases, the
lec
position. and is supplied with about 300 volts d-e from a trans
•.
In addition to the above items which are standard former, Redox, and capacitor device mounted in
on all breakers, the following special devices may the cell. The capacitor is connected across the coil,
also be mounted on the mechanism panel when and provides a slowly decaying holding current.
required. The time delay is adjusted by varying the charging
·'
voltage to the capacitor by a four step resistor, giving
w
when its control voltage drops below a predeter trip attachment, when supplied, mounts on the
mined value. This device uses the energy stored in mechanism panel and is used in addition to the
12
OPERATION------------------------------------������-------2�� - B�-�32�-� -3
25�1�
om
50-DH-150 &-250 A I R C I RC U I T BREAKERS
M O VI N G A RC I N G
, CON TACT
.c
STATION A R Y
M A I N CON TACT
FINGER
MOVING MAIN
�----- CON TACT
ls
F I N G E R STOP
ua
---- M OV I N G
CON TACT ARM
P U F F E R NOZZLE
an
tM
FIG. 9. Type 50-DH - 1 50-E, 1 200 Ampere Breaker Contacts Viewed from Rear
ar
shunt trip magnet. It is designed to accommodate the higher interrupting current and is shown in
three instantaneous current transformer trip assam· Fig. 10.
blies. The calibration of each current trip coil is For both the 50-DH-150-E and 50-DH-250-E rat
lP
engraved with the values of current required to trip ings, the 2000 ampere breakers use the same moving
the breaker. contact as the 1200 ampere Type 50-DH-250-E
CONTACTS
breaker. However, four moving blades are employed
Each pole of the type 50-DH-150-E and 50-DH-
instead of two, and five contact bolts instead of
ca
tween two formed copper blades which hinge on employs four movable fingers for the main con
the lower bushing foot and form the moving contact tact, each backed by a separate finger spring. Each
arm. See Fig. 9. These are moved between the has a silver inlay that mates with the moving main
closed and open positions by the mechanism through contact. The stationary arcing contact is located
the Redarta operating rods. The load current is con directly above. See Fig. 12.
.E
ducted across the hinge through silver electro The 1200 ampere Type 50-DH-250-E breaker
plated surfaces, with pressure being supplied by stationary contact is shown in Fig. 13 and is
spring washers on either side. similar with the exception that the arcing contact
The moving arcing contact is hinged to the top is wider.
of the main contact and the arcing current is carried The 2000 ampere rating employs six fingers on
by means of a flexible shunt inside the assembly. each stationary contact, and is shown in Fig. 14.
w
For the type 50-DH-150-E breaker the moving arcing Cooling fins are located on each side of the contact.
contact consists of a single casting with a silver With this contact design, all current breaking
tungsten inlay. See Fig. 9. On the Type 50-DH� and interrupting parts are completely enclosed by
ww
250-E breaker, this contact is divided for carrying the arc chutes.
13
om
OPERATION'-----
UPPER S TA T I O N A R Y
C O NTACT F O O T A RC I N G C O N TACT 1'1
t ' ' :,
.c
S TA T I O N A RY
M A I N C O N TA C T
·
F IN G E R
------- MOVING
A RCING
C O N TACTS
ls
ua
MOVING
MAIN
C O N TACT
an
~
P UF F E R
N OZ Z L E
tM �------
MOVING
CONTACT
ar
ARM
FIG. 1 0 . Type 50-DH-250-E, 1 200 Ampere Breaker Contacts, Viewed from Rear
lP
PUFFER M O V I N G A RC IN G
S T A T I O NARY
A RC I N G CONTACT N OZ Z L E C O N TACTS
ca
UPPER
C O N TACT F O O T
tri
------ MOV I N G. MA I N
C O N TACT
lec
.E
M OV I N G C O N TACT
A RMS: I N N E R & O U T E R
w
ww
FIG. 1 1 . Type 50-DH- 1 50-E/250-E, 2000 Ampere Breaker Contacts, Viewed from Rear
14 �
..
'
OPERATION------���-B�-�3�2-�25�1�-3
om
50-DH-150 &-250 A I R C I RC U I T BREAKERS
STATIONARY
A RCING CONTACT
M OVIN G ARCING
.c
CONTACT . ..
·�' i.: � .�
,, . �.. :. .
.,.., ,. ., .;.' . .
· . 1iiJ: :·. ;::! .
' .• A RCING CONTACT
ls
EYE BOLT
! .,.·
• '
ua
M OVIN G ·
CONTACT ARM
an
.·�
,· · :.
-'l ,:
tM
FIG. 1 2 . Type 50-DH - 1 50-E, 1 200 Ampere Breaker Contacts, Viewed from Front
S TA TI O N A RY
ar
A R C I N G C O N TA CT
lP
S TA T I O N A R Y
M A I N C ON TA C T
F I N G E RS (4)
ca
M O V I N G A RC I N G -.:::;;;;;,.._-
C O N TA C TS
tri
A R C I N G CON TA C T
E Y E BOLT
lec
M OV IN G .
.E
A RC I N G CONTACT
S P R I N GS
w
ww
FIG. 13. Type 50-DH-250-E, 1200 Ampere Breaker Contacts, Viewed from Front
15
om
OPERATION
U PP E R S T ATIONA RY I'
CONTACT FOOT A R C I N G CONTACT II .,
.c
S TA T I O N A R Y
SPRING M A IN C O N TACT
I N SU LA TI O N F I N G E R S (6)
ls
MOVING A RC I N G
C ON TACTS
ua
A R C I N G C ON TACT
PUFFER E Y E BOLT
N OZ Z L E
an
A R C I N G C ON TACT
S P R I N GS
tM
M O V I N G CONTACT
A R MS:
INNER & OUTER
L OW E R
CONTACT F O O T
ar
FIG. 1 4 . Type 50-DH- 1 50-E/250-E, 2000 Ampere Breaker Contacts, Viewed from Front
magnet, blow-out coils, transfer arc horns, transfer from the arcing contacts. The front arc horn is con
s�acks, main interrupter stacks, a front arc horn, and nected electrically to the moving contact, and the
a rear arc horn all assembled in and about a fabri rear arc horn is connected to the stationary contact.
ca
cated rectangular Redarta chute jacket. The arc The action of a breaker in interrupting an arc is
chute is hinged to the breaker; and when it is in the as follows. Referring to Fig. 15, when the arcing
normal position, its lower end completely surrounds contacts part and an arc is drawn, it loops up and
the contact structure. Fig. 15 is a schematic cross impinges on the lower ends of the two transfer arc
tri
section of the arc chute showing the component horns and the shading coil. The two short segments
parts. of the arc, from the transfer arc horns to the shading
The blow-out magnet is located so that the core coil, then move up into the transfer stacks and are
passes through the center of the arc chute. A blow quickly interrupted placing the blow-out coils in
lec
out coil is wound near each end of the core and lays series with the arc.
in a window cut in the side sheet of the chute jacket. When the current starts to flow in the blow-out
One terminal of each coil connects to a transfer, coils, a magnetic field is established and the arc,
or center arc horn, and the other terminals are which by this time is two separate arcs extending
joined at the top of the shading coil. Two transfer from the front and rear arc horns to the transfer
.E
stacks are placed in the space between the transfer horns, is driven very rapidly into the slots of the
arc horns and the shading coil. To either side of the refractory plates of the main interrupter stacks under
transfer arc horns are the main interrupter stacks the influence of the powerful magnetic force. As the
which are made up of a series of insulating refractory arc moves to the closed end of the slots, it is restric
plates. These plates have inverted V-shaped slots ted, lengthened, and cooled. All of these forces re
molded into them. The slots are offset so that when sult in rapid de-ionization of the arc space; and for
w
the plates are stacked with the slots alternating from the arc to maintain itself, it must continuously ionize
one side to the other, the arc must take a serpentine fresh gas. At current zero the formation of new ioni
path as it moves up into the arc chute increasing the zation momentarily ceases, but the de-ionization con
ww
length of the arc and at the same time restricting tinues so that dielectric strength is established in the
the diameter of the arc. arc space and the circuit is interrupted.
16
om
OPERATION------------------------------------��������--��� - B - 32�-=
251-3
�� ��
50-DH-150 &-250 AIR CIRCUIT BREAKERS
TRANSFER STACK
.c
DEFLECTOR
CHANNEL
D E F L ECTOR
ls
ua
an
tM
ar
lP
ca
tri
S HUN T
STRAP
STATIONARY
lec
CONTACT
MOVING
A S S E M B LY
C O N TACT
A S SE M B LY
been removed to show the front center arc horn . provided on each breaker. There is an arm on each
Similar parts have been removed from the right side side mounted on a common shaft across the back
of the Type 50-DH-150-E arc chute shown on the of the breaker. On each arm is a roller which en
ww
right of Fig. 16. gages a groove in the sidewall of the cell. A remov-
17 ,I
om
OPERATION -------
.c
ls
ua
T Y P E SO.DH-2SOE TYPE 50-DH-lSOE
an
FIG . 1 6. Partially Assembled Arc Chutes
18
OPERATION ____________ ________ ________
· B - 32- 25 � 3
__ __ ____ ����������·� �����--
50-DH-150 &-250 AIR CIRCUIT B REAKERS
om
With the arms to the rear and down as shown in shaft, push in and rotate to engage the coupling,
.c
operated at this position, remove the crank and en
TEST POSITION
gage the secondary contacts in the manner de
The breaker may be rolled into the metal clad
scribed in the section under Secondary Contacts.
cell until the rollers on the levering-in device stop
To move the breaker from the test position to the
against a pair of vertical angles welded into the cell.
fully engaged operating position, put the crank on
ls
The levering-in device is not operated. This is the
the shaft, push in and rotate to engage the levering
test position in which the breaker primary contacts
in coupling, and crank clockwise. The torque re
are separated from the energized contacts in the
quired will increase when the primary contact
ua
cell, and a metal shutter is closed completely isolat
fingers engage the stationary contact studs in the
ing all high voltage parts from the breaker. The
cell. Continue cranking to the end of the travel
secondary contacts may be engaged and the breaker
where the interlock will again fall free, pushing the
operated safely for test purposes without the arc
crank back out. Remove the crank. The indicator
chutes or barrier.
an
on the panel will again point to the word "OPERATE" .
To remove the breaker from the operating posi Caution: THE BREAKER SHOULD NEVER
tion, first check that the breaker is open. The lever BE MOVED BEYOND THE TEST POSITION
ing-in device cannot be engaged unless the breaker WITHOUT THE ARC CHUTES AND BARRIER
contacts are open. Put the crank on the operating IN PLACE.
L EVERING-IN DEVICE
I N TERLOCK CAM
tM PUFFER
D I A PHRAGM
CLAMPING R I N G
ar
L EVERIN G-IN DEVICE •
G EAR HOUSING P U F FE R
D IAPHRAGM
lP
FRON T PLATE
ca
I N TERLOCK -----
.
PIN
G R OU N D
CONTACT
SOLENOID
tri
S E CONDARY
CONTACT
PLUG
.E
w
ww
19
om
OPERATION----
.c
Caution: WHEN THE BREAKER IS IN THE
�
OPERATING POSITION IT SHOULD NEVER
BE CLOSED BY THE MAINTENANCE CLOS
ING HANDLE.
INTERLOCK
ls
The interlock on the DH breakers has two func
tions to perform. First, it prevents the breaker from
being moved from the test to the operate position
ua
or vice versa with the contacts closed. Second, if
the breaker is in some intermediate position between
the test and operate positions, it prevents the con
tacts from being closed.
This interlocking action is accomplished by hav
an
ing a rod, operated by the breaker mechanism, and
a pin operated by the levering-in device, move at
right angles to each other.
The puffer diaphragm is operated by two puffer
tM
rods extending through the puffer casting and con
FIG. 20. Operating Secondary Contacts
nected to the trip-free lever of the mechanism. The
right hand rod also extends beyond the rear of the
diaphragm support plate and is directly above the
ar
levering-in gear housing, and at right angles to
the interlock pin. See Fig. 19. When the breaker
is closed, this puffer rod moves over the interlock
pin and prevents the latter from moving upwards.
lP
vice and rotating the levering-in crank clockwise. bracket on the lower left hand side of the breaker
As the breaker travels beyond the Test Position, the frame. This permits it to be extended to the rear while
metal shutter covering the high voltage primary con the breaker is in the test position, and to make con
ww
tacts will be automatically opened by the shutter tact with the stationary receptacle so that the control
rollers which are located on each side of the breaker circuits are completed. Sufficient clearance is pro
frame at the rear. See Fig. 17. At the end of the vided in the mounting of both plug and receptacle,
20
om
OPERATION------���.8�·�32�-�25�1�-3
50-DH-150 &-250 AIR C I RCUIT B REAKERS
and two large tapered pins on the plug provide posi GROUND CONTACT
) tive alignment. The secondary contacts of the plug
are made from high conductivity copper alloy and
A ground contact is located at the left rear of the
breaker frame directly above the 18-point secondary
.c
are slotted to provide a spring action which insures plug, Fig. 19. Six spring loaded floating contact
a good electrical contact. The flexible control wires fingers engage the ground contact at the rear of the
are soldered to each plug and are arranged in a cell and insure a low impedance path to the ground.
loop to allow free movement of the contact slide.
To engage the secondary contacts while the PUFFER ASSEMBLY
breaker is in the test position, place the breaker Directly above the solenoid coil of the mechanism
ls
maintenance closing handle in the socket on the is a puffer arrangement that supplies a jet of air
secondary contact slide at the lower left hand side through an insulating tube and nozzle to each of the
of the breaker, Fig. 20. Push forward slightly to contacts. The diaphragm and clamping ring of the
ua
release the latch, then raise up on the handle to puffer are visible in Fig. 19. On low current inter
the end of travel. See Fig. 21. To disengage the ruptions the blow-out force of the small arcs is very
secondary contacts, the maintenance closing handle light, so a jet of air is released at the instant the
is inserted into the socket and lowered. If the breaker is tripped. This facilitates the movement of
an
breaker is levered into the operating position, the the arc upward into the arc chute where it is quickly
secondary plug and slide will automatically return interrupted. The nozzle location is shown in Figs.
to the normal position; and the latch will hold it in 9 and 11. The diaphragm is connected to the trip
place when the breaker is later moved to the test free lever of the operating mechanism by means of
tM
position. two operating rods which also carry the accelerating
COUP L I N G
ar
)
lP
ca
tri
lec
.E
w
ww
21
om
OPERATION-------
springs. As the breaker trips open, the diaphragm One lead from each of the three current trip coils
is drawn into the cavity expelling the air which is is connected to secondary contacts 13, 14 and 15
directed to the contacts by the three puffer nozzles. with the common connection from the three coils
.c
The diaphragm is made of a longlasting wide tem going to contact 16 when this type of tripping is used.
perature range material and should never require This eliminates the connection to the last "a" and
replacement unless through accidental puncturing. "b" contact of the auxiliary switch.
MECHANISM OPERATED
ls
CONTROL SWITCH
Some installations require more auxiliary switch
ua
contacts than are available on the nine pole auxiliary
switch on the breaker. For this purpose additional A .C. B.
an
An operating arm, shown in Fig. 22, on the right
GRD. BUS
hand side of the breaker frame is connected to the
trip free lever and moves with the mechanism. The - -, '
tM
9-P
may be arranged for operation of the switches when AUX.
the breaker is in the operating position only, or both SEC. SW.
S EC.
testing and operating positions. RECEPT. PLUG
3 9 17 II 13 15
I 2 3 I 2 3
0 0 0 0 0 0
�
ar
SECONDARY CONTROL WIRING 1 6
4 5 6 4 5 6
0 0 0 0 0 0 L.C.
The low voltage control wiring from the 18-point SW. CUT-OFF
secondary plug to the various components consists 7 8 9 7 8 9
0 0 0 0 0 0 sw.
lP
r]!!Y •
I
breaker intemal wiring is shown on Connection 13 1 4 1 5 1 3 14 15
J
Diagram, Fig. 23. 0 0 0 0 0 0
ca
16 1 7 1 8 1 6 1 7 18
When an undervoltage trip device is used on the 0 0 0 0 0 0
# 10
breaker, its coil is connected between secondary F. V. M E �H .
_
contacts 15 and 16; and the "a" contact at the end
tri
of the auxiliary switch is not wired. FIG. 23. Diagram o f Breaker Internal Wiring
PART FOU R
lec
INSTALLATION
With the exception of installing the arcing cham After the breaker has been removed from
•.
bers these breakers are shipped completely assem the shipping crate, place it in a convenient
.E
bled and adjusted. No change in adjustments should position adj acent to the test cabinet or in
be required and none should be made unless it is front of the metal clad cell in which it will go.
·
obvious they have been disturbed. Then perform the following sequence of oper
·.
ing stroke. Personnel working about the are shipped with the contacts closed and a tie on the
breiiker should stay clear of the space in which hand-trip lever to prevent tripping. Take off the tie
on the trip lever being careful not to trip the mech
ww
22 ..
INSTALLATION ______________________________
�����������I. �
B�
- 3�
2-��
�1�
-3
50-DH-150 & 250 AIR C I RCUIT BREAKERS
om
M OV I N G A R C I N G CO N TACT STATI ONARY UPPER
ARC I N G CON TACT
SPR I N G GUIDE CONTACT FOOT
.c
ARC I N G CONTACT FLEXIBLE S H U N T STAT I ON A R Y
A R C I N G CONTACT S P R I N G S CO NTACT
FI NGER
�
� ·v F I N G E R STOP
ls
C A ST I N G
/�·�
ua
'
an
CONTACT UPPER STUD a
STOP NUT BU SH I N G A S SY
M OV I N G
CONTACT ARM -'-.1
tM '----
STAT I O N AR Y M A I N CONTACT
M OVIN G M A I N C O N TACT
ar
lP
LOCK N U T
( l.H. THREAD )
ca
Z. Wipe off breaker main and arcing con travel at the bottom of the outside stationary cont&Q.t
tacts. A light film of grease is applied to the con fingers is between lfa and 5.6.inch, with the breaker
tacts before the breaker is operated at the factory closed and latched. See Fig. 24. This may be meas
and is normally removed before shipment. Be sure ured through the rectangular opening on each
contacts are free of grease or any foreign material side of the finger stop casting. If adjustment is
.E
main
23
om
INSTALLATION-------
this position, adjust the contact stop nut located ing as the seal to the ceramic plate will be
�low t he moving arcing contact springs until the
moving and stationary arcing contacts just touch.
broken.
(c) Carefully lower the arc chute to the hori
1) �1
�·
,
Current is conducted across the hinge through
.c
zontal position while checking the' alignment with
silver contact rings on the inside of the moving con the moving and stationary contacts. The rear arc
tact arms and the outside of the lower contact foot, horn clip must make good contact with the rear pro
with the correct pressure being maintained by means jection of the upper contact foot .
of spring cup washers. There should be no need for (d) Bolt front arc horn to shunt strap of moving
changing this adjustment unless the moving contact contact bushing.
ls
arms have been removed. With the operating rod (e) Make final check by operating breaker
disconnect�d from the moving contact arms, open
slowly by hand to see that there is no interference
the arms to approximately 45 degrees from the "con
ua
with movement of the contacts at any point in the
tact closed" position. Tighten the castle nut on the travel.
hinge bolt sufficiently to barely hold the 45° position.
(£) Check the nine pole auxiliary switch con
Replace the cotter pin, and reconnect the operating
tacts to see that the fingers are approximately center
rod.
ed on the rotor segments for both open and closed
an
S. Trip the breaker. The breaker is tripped positions of the breaker.
both manually and electrically by lifting up on the
(g) The plunger of the single pole cutoff
hand trip assembly on the front of the breaker
switch, located to the right of the nine pole switch,
mechanism panel. Refer to Fig. 7.
should be fully depressed when the breaker is
6. Close and trip the breaker. Close and trip
tM
latched closed.
the breaker manually several times to be certain
1 0. Mount the barrier. When mounting the
that all parts are functioning properly.
barrier, the lower rear corners of the outside plates
7. Connect test jumper. Connect the test
go to the inside of the breaker frame. Two bolts in
ar
j umper from the test cabinet to the breaker second
the lower front corners hold the assembly in place.
ary contact block and operate the breaker electrical
1 1 . Prepare levering-in device to move
ly several times. With some installation, a Test Jump
er is furnished instead of a Test Cabinet. This j umper
breaker into cell. Breakers are shipped with
lP
(a) Remove the hinge pin from the hinge 13. Engage secondary contacts. Place the
bracket on the bushing support. maintenance closing handle in the secondary con
(b) Lift the arc chute into place so that the tact socket and lift up to engage the secondary con
two parts of the hinge bracket are aligned with the tacts, Figs. 20, and 21.
arc chute in the tilted back position. See Fig. 4. 14. Operate breaker electrically. Close and
Slip the hinge pin into place, and secure with a trip the breaker several times electrically from the
w
cotter pin on each end. The arc chutes are balanced control switch on the front of the cell to check the
so that they will remain in this position. control wiring in the cell. If the operation is satis
DO NOT use the molded deflec factory, the breaker may now be levered into the
ww
Caution:
tor angles at the top of the arc chutes for lift- operating position.
24
INSTALLATION ________________________________
� -B�-�32�-=
25�1�
-3
om
� ����
50-DH-150 �AIR
&-250 �� ����
CIRCUIT B REAKERS
1 5. Caution: When this breaker is put mechanism panel will point to "Operate". The
into the cell and moved in beyond the test breaker must be all the way in for the interlock to
position, the high voltage parts will be ener release to permit the contacts to close. Remove the
gized. If the barrier is completely assembled levering-in crank.
.c
on the breaker, personnel will be protected 17. Caution: Do not attempt to close this breaker
from contact with the live parts. If however,
by hand against an energized circuit. To insure suf
the barrier assembly is left of£ and the breaker
ficient force and speed, the breaker must be closed
rolled into the cell, live parts are exposed . The
electrically, from an adequate power source. (See
breaker should NEVER be rolled in to an ener
NEMA Standard SG-6-213) .
ls
gized cell structure beyond the test position �
ua
control switch on the cell door.
16. Lever breaker into cell. To move the
breaker to the operating position, the contacts must If a test cabinet is not available for checking the
be open. Place the crank on the levering-in device breaker electrically before placing it in the cell, it
operating shaft, press in to engage the levering-in can be checked electrically in the test position in the
cell. Observe the caution of Step 15 above and do
an
device, and rotate the crank clockwise to the end of
the travel. At the end of the travel, the handle will not go beyond the test position unless the arc chutes
come back out and the indicator on the breaker and barrier are in place.
PART FIVE
ADJUSTMENT tM
ar
MECHANISM cam is in its normal position. The stop bolt is acces
The mechanism of the breaker is adjusted at the sible through the cut-out in the mechanism panel
factory and is designed to give long, trouble free next to the shunt trip. See Fig. 7. The hand closing
lP
performance. Do not make any adjustment unless lever should be out of the socket during this adjust
faulty operation is observed. ment.
Tripping Latch. If a breaker fails to close con Cut-Off Switch. Operation of this switch must
tacts although the moving core of the mechanism occur at the proper time in the closing stroke.
ca
moves to the closed position, a probable cause is The contact must make positively before the end of
failure to reset. Refer to "C", Fig. 6. The gap indi motion of the trip free lever so that the current will
cated between the tripping latch roller and cam always be cut off. In the other direction, cut-off must
is an essential requirement to permit the tripping not occur too early in the stroke or the mechanism
tri
latch to fall into the cam notch. Watch the trigger might fail to complete its closing stroke. Proper, ac
handle (with words "lift to trip"), it should return to tion will be obtained when the switch plunger has
the horizontal position immediately after breaker has from � to lfa inch over travel. In other words be
lec
been opened. tween the position where the contacts touch and the
If the trigger is prevented from returning to the position with the breaker closed and latched at rest,
full reset position by the primary latch roller above there must be Ya2 to lfa inch motion of this switch
it, the cause may be that tripping latch roller cannot plunger. Ordinarily no adjustment is required. The
drop into cam notch. Remove the barrier from the resilience provided in the operating arm by the leaf
.E
breaker. This gives easy access to the gap. Using the spring prevents damage to the switch on the mech
hand closing lever, close the breaker part way, trip anism over travel. If it should be necessary to
it, and then slowly retrieve the moving core. Note change the switch contact time, bend the switch
whether or not the tripping latch roller drops into operating arm to get the proper time.
the cam notch. Latch Check Switch. The action of this switch
If it is necessary to increase the clearance to get may be checked as follows. With the breaker open,
�2 inch gap, loosen the locknut and adjust the
w
latch should be depressed to be sure the tripping The switch should close its contact when the trigger-
25
ADJUSTMENT----
om
arm. ia in an interval from 3fs to 1/s inch above the In order to maintain proper pressure as the contacts
normal reset Poa1fon meuuria9 at the shunt trip
.
erode, it is necessary to readjust the contacts from
plunger centerline. A convenient method of meas time to time to compensate for wear. The contacts
uring this is to raise and lower the trigger arm by are properly adjusted when the over travel at the
pushing with the trip plunger and making pencil
bottom of the outside stationary contact fingers is
.c
·,
marks on the plunger rod. If the breaker is out of the
between lfs inch minimum and ¥.n inch maximum.
cell, switch action may be indicated electrically by
This may be measured through the rectangular open
connecting to contacts number 1 and 2 on the sec
ondary plug. If switch action must be made earlier or ing on each side of the finger stop casting. Refer to
later, bend the switch arm near the middle of its Fig. 24 and Contact Adjustment Paragraph 4 under
ls
length . . Installalion.
Contacts. Each time the breaker is operated, a Always tighten all locknuts securely, and then
small amount of the contact material is eroded away. recheck measurements.
ua
PART SIX
MAINTENANCE
an
The Westinghouse Type DH circuit breakers are of the interrupter, especially if there are many fault
designed to have a long life with a minimum of current interruptions. Large current arcs glaze the
tM
maintenance when operating duty is ordinary or ceramic surfaces inside the arc chutes but leave
average. However, with the many types of applica them clean electrically. On the other hand, frequent
tions of these breakers, the operating duty will vary operation at low or medium currents (about 1,000
greatly as to frequency of operation and as to amount amperes or less) tend to cause the accumulation of
and power factor of current interrupted. Therefore, soot and condensed metal on the parts inside the arc
ar
the frequency of inspection and the amount of chute, particularly on the ceramic arc shields near
maintenance for any particular application must be the contacts. These deposits may be conducting and
chosen with due regard to the kind of duty a breaker may have to be removed as explained later under
lP
is performing. The following remarks are intended Arc Chutes. Breakers which have opened large fault
as a general guide. Experience on a particular currents near the maximum rating, should be in
application may show a need for varying the main spected as soon as practical. The condition of the
tenance practice. contact surfaces and the contact pressure adjust
ca
tions more attention should be paid to cleanliness may hop around the contacts for several cycles.
26
MAINTENANCE-------------------------------- --� B�
� -�- 3�2� 5�
-2�1-3
om
���������
50- DH-150 &-250 AIR CIRCUIT B REAKERS
Hence a breaker which has had many operations at adj usting nut at the bottom of the spring
low currents may be expected to have numerous eyebolt.
small bum spots and pock marks all over the metal The arcing contact assembly is then installed on
parts supporting the arcing contacts. When inspect the main contact forging. Make sure all bolts are
.c
ing arcing contacts, the important condition to be tight, and the snap rings have been replaced on the
observed is the extent of the erosion of the contact hinge pin.
material. When half of the original lfa inch thickness Stationary Main Contacts. The stationary
is gone, the contact should be replaced. This is be main contact is made up of four or six individually
cause the remaining Vi s inch thickness will be me sprung fingers held in the upper bushing contact
ls
chanically weak and might suddenly be broken foot for the 1200 ampere and 2000 ampere rating.
away. See Figs. 12, 13, and 14. These are removed by
On high fault current operations there may be oc partially closing the breaker with the maintenance
ua
casional slight burning on the main contacts. Also closing handle far enough to hold the fingers in
after many operations, the main contacts will some place.
times become roughened. A fine flat file should be
Caution: Do not latch breaker. Remove the
used lightly on the main contact silvers, removing
two 5/r s-1 8 hex head bolts from the finger
an
only enough to take off the high spots. In other cases,
stop. The breaker is allowed to open slowly.
the surfaces may become glazed or shiny, and this
The fingers and their springs may be slipped
may be corrected by the use of fine sandpaper. A
out the side of the contact foot.
moderate amount of pitting on the main contact
A very thin coat of a graphite grease should be
surfaces will not appreciably impair their current
tM
placed on the silver plated contact surface between
carrying ability because of the high contact pressure.
the contact fingers and the contact foot before re
After the contacts have been worn and dressed
placing the fingers. (W} No. 8831-9 is recommended.
off as above, or replaced, contact adjustment should
be checked. Refer to the section on Contact Adjust In replacing the fingers, the thin strip of insulation
must be located between the bottom of the finger
ar
ment.
Moving Contact Assembly. The moving con springs and the contact foot.
tact assembly consists of a copper forging to which The 1200 ampere rating with four fingers has a
is brazed the main contact silver alloy inlay, with the spring for each finger. The 2000 ampere rating has
lP
arcing contact hinged to the top. To change this two concentric springs resting on a spring seat for
contact assembly remove the three bolts which hold each pair of fingers. One side of the spring seat has
the contact between the blades. two ridges. In reassembling, the spring seat must be
placed so that each ridge is parallel to the finger and
ca
To replace the moving arcing contact, the two 3/a-16 hex head bolts at the top of the contact foot.
l/4-20 hex head bolts are removed at the top of the The new contact is then bolted in place.
flexible shunt. For the 50-DH-150-E rating, the 3/a
inch diameter pin at the top of the spring eyebolt is ARC CHUTES
driven out. In replacing the new contact, the pin may The insulation parts of the arc chute remain in the
.E
be started through the eyebolt by prying from the op circuit across the contacts at all times. During the
posite side with a rod of similar diameter to force the time that the contacts are open, these insulating
spring guide down. For the SO-DH-250-E rating, the parts are subjected to the full potential across the
two halves of the arcing contact are slipped off the breaker. Ability to withstand this potential depends
side. If only one half of the contact is changed at a upon the care given the insulation.
tim9t the spring pressure will be reduced. On general inspections, blow-out the arc chutes
w
Caution: There is considerable spring pres with dry compressed air by directing the stream up
sure and the parts will have a tendency to ward from the contact area and out through each
• of the slots between the arc splitter plates. Also
ww
27
-------- -- ---
MAINTENANCE-------
om
shields. These a�e the ceramic liners in the lower late o n the ceramic arc shields sufficiently to impair
end of the chute where the arc is drawn. proper interrupting performance. This dirt can be
The arc chutes should be inspected each time the removed only by rubbing with coarse sand paper
contacts are inspected. Remove any residue, dirt, or other nonconducting abrasive paper.
.c
or arc products with a cloth or by a light sanding. The ceramic arc shields may appear dirty and yet
Do not use a wire brush or emery cloth for this pur have sufficient dielectric strength. The following
pose because of the possibility of embedding con insulation test may be used as a guide in determining
ducting particles in the ceramic material. when this complete or major cleaning operation is
When inspecting an arc chute, look for the follow required. The arc chutes should withstand 15 KV,
ls
ing: . 60 cycle for one minute between the front and rear
1. Broken or Cracked Ceramic Parts. Small arc horns. Also the dirty surface of the ceramic near
pieces broken from the ceramics, or small cracks the contacts should withstand approximately 10 KV
ua
are not important. But large breaks and particularly per inch when test prods are placed directly on the
cracks extending from the inverted V slot in the ceramic surface. When test voltage is applied, there
interrupter plates out to the edge of the plate or to should be no luminous display in the black deposits.
the top may interfere with top performance of the
OPERATING MECHANISM
an
interrupter. Hence if more than one or two broken
With average conditions, the breaker operating
or badly cracked plates are apparent, renewal of the
mechanism may be expected to operate 5000 times
ceramic stack is indicated.
or more with only routine inspection and lubrication.
Z. Erosion of Ceramics. When an arc strikes During inspection, the following points should be
tM
a ceramic part in the arc chutes, the surface of the kept in mind: (1) Remove loose dust and dirt with a
ceramic will be melted slight!y. When solidified again, compressed air stream. (2) Wipe off latch and roller
the surface will have a glazed whitish appearance. surfaces. (3) With maintenance closing lever, move
At low and medium current, this effect is very slight. mechanism parts slowly closed to point where arc
However, large current arcs repeated many times
ar
ing contacts just touch; and then allow contact arms
may boil away appreciable amounts of the ceramic. to fall slowly to open position, observing any evi
When the width of the slot at its upper or narrow end dence of stickiness or excessive friction. (4) Holding
(originally \11 6 inch) has been eroded to twice its trigger up, move maintenance closing lever up
lP
original size, (about lfa inch), the ceramic stack and down slowly. The core should move freely in
assembly should be replaced. the solenoid, and the linkage system should reset
3. Dirt in Arc Chute. In service the arc chute positively when the weight of the maintenance
assembly will become dirty from three causes. First,
ca
the contacts which may be removed by wiping with operating parts, lubricants can be avoided. In cer
cloths free of grease or metallic particles. Third, tain other parts, the use of special lubricant is de
very tightly adhering deposits from the arc gases on sirable and beneficial-PROVIDED IT IS DONE
lec
the ceramic arc shields near the contacts. These CAREFULLY. This means applying it in small quan
deposits from the metal vapors boiled out of the tities to ·avoid drippings and accumulation. Experi
contacts and arc horns, may accumulate to a harm ence will dictate the amount required. Those break
ful amount only in breakers which receive many ers having only a few operations per year, will per
operations at low or medium interrupted currents. form best with the moving surfaces of the mechanism
.E
4. Cleaning Arc Shields. Cleaning methods for clean and only a very light film of lubrication. While
the first two types of dirt are obvious as mentioned those breakers having many operations per day will
above. Particular attention should be paid to any require more lubrication to prevent excessive wear.
dirt on the glass polyester or Redarta surfaces ex If any excessive friction or binding is discovered
posed to the arc below the ceramic arc shield. Wipe on inspection, relieve it either by adding lubricant
clean if possible. If wiping will not remove the dirt, or if necessary by cleaning old dried lubricant Jrom
w
clean with sand paper to remove all traces of carbon the bearing surfaces. In general, the addition of a
or metallic deposit. On breakers which receive few drops of oil should be sufficient. In a few cases,
thousands of operations at low and medium inter after long service, the accumulation of dried or
ww
rupted currents, tightly adhering dirt may accumu- oxidized lubricant may make it necessary to disas-
28
� B - 32-251-3
om
JIAINTENANCE--------------------------------������������
50-DH-150 & - 250 AIR CIRCUIT B.������
REAKERS
semble parts and clean them. Carbon tetrachloride back plate and the four large magnetic return studs.
is a good solvent for this. This will change the position of the stationary core
Apply a small amount of a light oil to the wearing with respect to the latching points in the mechanism
surfaces. Use a stable oil with a low rate of oxidation frame.
.c
and with a low pour point. Wemco C is suggested. After about 15,000 operations, replacement of
Avoid putting oil on insulating material surfaces. some parts may be required. During routine main
Also put no oil on the breaker contacts, the auxiliary tenance, the amount of wear should be observed on
switch, the puffer diaphragm, nor the rubber bump latch surfaces, rollers, pins and pin holes. If it be
ers. Soft petrolatum may be used on the drawout comes impossible to obtain correct adjustments or if
ls
connectors both primary and secondary. latches fail to hold, replacements should be con
For the closing magnet core use graphite grease sidered.
(W) No. 8831-9. Apply a small quantity all around
ua
the core when the breaker is in the open position, PUFFER
and close and open the breaker several times to work The puffer diaphragm is made of long lasting,
in the grease. wide temperature range material, and should never
The silver plated contact surfaces on the hinge require replacement unless through accidental
an
of the moving contact arms should be lubricated with puncturing. If replacement is necessary, proceed as
graphite grease (W) No. 8831-9. follows. Refer to Figs. 19 and 28.
When the stationary main contact fingers are 1. Remove ground contact.
replaced, the knuckle joint between the fingers and 2. Remove two 3f.i-10 castle nuts from clamping
the contact foot should have a light film of graphite
tM
plate. The right castle nut will be captive until the
grease (W) No. 8831-9. right hand puffer rod is lowered.
The rollers and pins on the hand trip assembly,
3. Remove the links to the 9-pole auxiliary switch
Item 32 on Fig. 27, should receive a very small
and the operation counter. Remove two drive pins
quantity of a molybdenum lubricant (W) No. 8577-2.
from the front of the levering-in device shaft, and
ar
The levering-in device rollers and shutter rollers
slip off the indicator collar.
should also receive molybdenum lubricant (W) No.
8577-2. The levering-in shaft bearings and worm 4. After removing the four 3/a-16 bolts from the
gear should receive (W) Material No. 5435-1. mechanism front panel, the panel may be swung to
lP
Any good grade of grease can be used for the the side without disturbing any wiring.
breaker wheel bearings. 5. Remove the lf2 inch diameter pin between the
In dusty, dirty locations, surplus oil may catch bottom of the right hand puffer rod and the trip free
ca
and hold grit near bearings and latches and cause lever of the mechanism. The rod will then move
faster wear. In such locations, it is recommended forward to clear the levering-in gear housing.
that all oil be omitted, and the steel parts in the 6. Remove twenty lj4-20 clamping ring screws.
mechanism be lubricated by rubbing with (W) Mol With the levering-in device arms pointing to the
tri
kolube Powder, Material No. 8565-3. rear, two of the screws may be reached through the
Clearances. After a mechanism has operated openings in the side frame.
several thousand times, the following points should 7. Remove the clamping ring, and the diaphragm
be checked as part of routine inspection. With the
lec
The overlravel should be approximately Y32 mini unW the pin has been replaced in the bottom of the
mum to %2 maximum. With wear in the link holes right hand puffer rod.
1 2. After moderate tightening, secure the two
ww
29
------- - -- · -----
om
MAINTENANCE'-----
clamping rings screws being careful to not crush Any burned segments and contact fingers should
the diaphragm. be replaced. The rotor is removed from the switch by
13. Replace the cotter pins in the puffer rod pin, loosening the operating lever and removing the end
and return the front panel and links. plates. The rotor is dismanUed by removing the
.c
lj4-20 clamping bolt and end clamp. Refer to ..
PUFFER NOZZLE
Fig. 29. �
The puffer nozzle is molded direcUy to the puffer
tube. The tube passes through the lower bushing In reassembling, care must be taken that the in
foot and into the puffer casting. It can be changed sulating spacers are placed on the rotor shaft in the
by removing the bolt from the clip at the base of the
ls
correct order. The various widths are given in
tube where it passes through the breaker frame. Fig. 29 with the �2 and 1 %2 spacers starting at the
When replacing the tube, be sure the clip is in the third position and alternating to the end of the rotor.
ua
notch in the tube before tightening the bolt.
Auxiliary Switch INSULATION
The contact fingers and rotor segments of the
nine pole auxiliary switch may be inspected when Flame retardant, glass-mat polyester insulating
an
the breaker main barrier and the insulating angle materials are used in high voltage air circuit break
cover on the switch frame are removed. Refer to ers for bushing ties, barriers, braces, arc chutes and
Fig. 29. similar purposes, where it has been found to be more
The rotor moves approximately 90 degrees start suitable than porcelain, The material used on West
ing from a position 22lf2 degrees below the hori inghouse breakers is Redarta, which has a long
zontal when the breaker is closed. This is adjusted
by loosening the lf4-20 locknut at the end of the
operating lever and moving the serrated plate. The
"V" tip of the stationary contact finger should be
tM
established record for insulation and mechanical
dependability.
Insulation maintenance consists primarily in keep
ing the surfaces of the material clean. This can be
ar
near the center of the contact segment when that done by wiping the surfaces with cloths free of
stage is closed. Check "a" contacts with the breaker grease or metallic particles each time the breaker is
closed, and "b" contacts with the breaker open. removed from the cell for inspection.
Normal operation is sufficient to keep the contacts
lP
clean. If the contacts do require cleaning, a very fine In case there is any tighUy adhering dirt which
file should be used; and care taken not to remove will not come off by wiping, it can be removed with
more material than necessary. Westinghouse solvent No. 1609-1 or -2.
ca
PART SEVEN
PARTS IDENTIFICATION
tri
lec
Detailed parts identification for the breaker are Renewal Parts. A list of renewal parts recom
shown on the various figures throughout this book. mended to be kept in stock will be furnished upon
Figure 3 shows the major components of the breaker. request. When ordering renewal parts, always
Figures 6 and 27 shows the mechanism linkage. specify the part name and style identification from
the renewal parts data. If this is not available, identi
Figure 7 shows the various components mounted on
fy the part by name from a particular figure in this
.E
the mechanism front panel. Figure 25 shows the instruction book, include the LB. number. Also,
parts for the moving contact assembly, while Fig. always supply full information from the stamped
26 shows the parts for the stationary contact assem nameplate on the front of the breaker along with
bly. Figure 28 shows the parts in the puffer assembly. the order.
w
ww
30
PARTS IDENTIFICATION _____________________________________________
I_.a_._3_
2--2- -3
51�
50-DH-150 &-250 AIR CIRCUIT BREAKERS
om
.c
ls
ua
an
tM
ar
lP
ca
1. Moving Contact Assembly-Com- 14. Moving Arcing Contact Spring, 26. Moving Arcing Contact
plete Inner 27. Truarc Rings
2. Spacing Washers 1 5 . Eyebolt 28. Pin
3. Operating Rod Upper Pin 16. Upper Spring Guide 29. Moving Main Contact
tri
FIG. 25. Type 50-DH -150-E, 1200 Ampere Moving Contact Assembly
.E
w
ww
31
om
PARTS IDENTIFICATION _________________________________________________
.c
ls
ua
an
·. .. ,
tM
ar
lP
- . -. - -
10
-
ca
tri
lec
1 . Stationary Contact Assembly 4. Arcing Contact Bolt 9. Stationary Main Contact Fingers
Com plete 5. Stationary Arcing Contact 10. Main Contact Finger S prings
2. Bushing, Stud, and Contact Foot 6. Finger Stop Casting 1 1 . Spring Insulating Stri p
Assembly 7. Lockwashers
3. Lockwasher 8. Bolts
.E
FIG. 26. Type 50-DH - 1 50-E, 1 200 Ampere Stationary Contact Assembly
w
ww
32
· 32 25 - 3
PARTS IDENTIFICATION ________________________
� --�����--����·8�.��-��1�
50- DH-150 &-250 AIR C I RCUIT BREAKERS
om
.c
22A ��:
�UE
7
�
228 �
ls
.-2- 0
� w:;:
�� � L '22
22C e 22GF
ua
3 32
an
17
32 /�/f32�1 2E-� �:�
328
32C 32 K
F
��032H =f �
� \
32 J , \
tM I' 32N l2L 32M
ar
,
lP
30
1. Mechanism Frame 2 1 . Operating Arm Screws 3 1 . Mechanism Stop Bolt and Locknut
ca
2. Solenoid Back Plate 22. Link Assembly 32. Hand Trip Assembly
3. Back Plate Bolts 22A. Spacers for Closing Link 32A. Bracket
4. Boll Locking Clips 22B. Lower Trip Free Links 32B. Bracket Locating Boll and Lock-
·
5. Back Plate Shim Washer 22C. Cam Links washer
6. Core Guide Tube 220. Washers 32C. Bracket Mounting Bolts and
7. Solenoid Coil 22E. Pin Joining Upper and Lower Lockwashers
8. Moving Cor e Trip Free Links 320. Trigger and Roller Lever Pins
tri
9; Stationary Core 22F. Pin Joining Cam and Cam Link 32E. Trigger Roller Pin
10. Stationary Core Shim Washer 22G. Tripping Cam 32F. Trigger Roller
1 1. Stationary Core Bolts 22H. Upper Trip Free Link 32G. Roller Lever
12. Lockwashers 221. Cam Stop Rollers 32H. Truarc Rings
13. Closing Link Pin 23. Pin for Upper Trip Free Link 321. Roller Lever Spring
lec
.,
ww
33
¥ �P�RTS I DENTIFICATI ON �-
om
________________________________________________
/ .·
.c
ls
1. · ·
ua
an
i �
i
tM
l. P uffe r Assembly Complete 7. Clamping Ring 1 3. Diaphragm Center Clamp Nuts
2. PuHer Casting 8. Clamping Ring Screws 1 4. Diaphragm Center Clamp Bol t s
3. Rear Clamping Plate, Steel 9. Puffer Tubes a n d Nozzles 1 5. Puffer Rod Castelated Nuts
4. Gasket Plate 10. Sprir;y Stop Pins 1 6. Cotler Pins
5. Diaphragm 1 1. Washers 17. Puller R o d Pins
6. Front Clamping Plate 1 2. Puffer and Accelerating Springs 1 8. Puller Rod, Long, Right Hand
1 9. Puller Rod, Short, Left Hand
ar
FIG. 2 8 . P u ffer Assembly
I'
'
•
lP
ca
tri
5 7
32 32
13 15
lec
ROTOR A S S E M B LY
32 32
END V I EW
7 5 j� 1 . Operating Lever
.E
((�
2. Collar
3. Insulating Barrier
4. Spacer, 5h2 wide
5. Spacer, 1 %2 Wide
lf 9
6. Spacer, %2 Wide
7. Spacer, 1 5f32 Wide
d. Se g me nt , Long, " a "
8 10 9. S egme nt, Short, "b"
"a
S H O R T " b" SHORT " a"
w
34
om
A I R C I RCU I T B R E A K E R TYPES 75 DHE- 1 5 0 D HE
D E S C R I PT I ON
.c
The Type 75 DHE and 1 5 0 DHE A i r C i rc u i t Break e r s are 3 - po l e , e l ec t r ic a l ly o p e ra t ed , ho r
i zontal d r awout un i t s for metal - c l ad sw i tchgear. The rat i n g of the b reak e rs are as fo l l ow s :
ls
I n t e r rup t i ng Rat i ng 250 MVA 5 00 MVA 150 MVA 250 MVA 500 MVA
ua
Rat ing 1 200- 2000 A . 1 200- 2000 A. 1 200 A. 1 200- 2000 A . 1200- 2000 A.
an
Max i mum De s i g n Vo l tage 8250 V. 8250 v . 1 5000 v . 15000 v. 15000 v.
I n t e r r u p t i ng Current
At Rated Vol tage
F I G. I T Y P I C A L B R E A KE R C 0 .1 P L ET E LY A S S E t 1 B L E D
2
om
AIR C I RCU I T BREAKER TYPES 75 D II E • I S O D II E
.c
ls
BLOWOUT
'""'L--
ua
M A GN E T
HINGE BRACKET
H I N G E PIN
an
tM
ARC CHUTE
SUPPORT
S E CONDARY
CONTACT ROLLER ARM
SLIDE AND ROLLER
ar
MANUAL
CLOSING
SOCKET
lP
ca
3
om
A I R C I RCU I T B RE A K E R TYPES 75 DHE· l S O DHE
.c
chut e , and is an i n t egral par t o f the arc c h u t e assemb l y . To prov ide easy access i b i l i ty fo r
c o n t a c t ma i n tenance and i nspect io n , t he a r c c h u t e s are h i nged at t he rea r , and a s i mp l e t i l t
i n g d ev i c e is p rov ided. F i gure 3 shows t he b r e ak e r w i th t he arc c h u t e s t i l t ed back . The
l ever ing- i n dev i c e i s used to supp ly t he mec han i c a l ad vantage for t i l t i ng the arc c h u t e s .
ls
ua
an
-- ---- --
_I J
/ tM
ar
lP
ca
tri
lec
bo l ts w h i ch a t t ac h to t he frame s t r u c t u r e .
ww
II
om
A I R C I RC U I T BREAK ER TYPES 7 5 O I! E · 1 5 0 D IIE
R EC E I V I N G , H A N D L I N G A N D STOR I N G
.c
The rece i v i n g , hand l i ng and s t o r i n g o f the b reakers s ho u l d be done i n the manner set
fo r t h i n t he i n s t ruc t io n book I . B . 3 2· 25 1 · 3. The appro x i ma t e we i g h t o f the b re a k e r s and t he
var ious parts are as f o l l ow s .
ls
Break e r P a r t s
ua
and bar r i e r s 950 pounds
an
Comp l e t e b reak e r 1 9 4 5 pounds 2225 p o unds
tM
I N S T A L LAT I O N
W i t h the except i o n of the arc i n g c hamb e r s and t he bar r i e rs , these b reakers are s h i pped
compl e te l y assemb l ed and adj usted . No adj ustment s ho u l d be r equ i red and none sho u l d be made
u n l e s s obv ious l y needed.
ar
C A UT I ON : Severe i n j u ry may b e s u s t a i n ed i f a n y p a r t o f t h e b od y i s s t r u c k b y the con
tact a rm s s i n c e t h e y move v e r y ra p i d l y i n t h e o p e n i n g s t r ok e . Personne l work i ng about t h e
lP
b r e a k e r s h o u l d s t a y c l e a r o f t h e s p a c e i n w h i c h t h e c o n t a c t a r m s move w h i l e t h e b re a k e r is
c l o s ed o r b e i n g c l o s ed . I f b r e ake r h a s b e en c l o s ed by h a n d , a l w a y s remov e t h e h a nd c l o s i n g l e v e r
before t r i pp i ng .
ca
2. W i t h t he b reak e r i n the c l o s ed pos i t ion , check the contacts t o make c e r ta i n that the ad
j ustments have not b een d i s t u rbed. For proper set t i ng s , refer t o F i g ure 24 o f
.E
I . B . 3 2 - 25 1 - 3 . I f adj ustments are requ i red, t h ey may be made as desc r i bed on Page 2 3 .
A l i ght f i l m o f g rease i s app l i e d t o b o t h t he arc i n g and ma i n contacts b e fo r e t h e b reaker
is operated at t h e factory. Thi s f i l m is norma l l y removed b e f o re sh i p m e n t . Be fore the
b reak e r is p l aced in serv i c e , i ns p e c t a l l contacts t o see t hat they are free o f o i l or
grease.
w
3. The b reak e r i s more eas i l y hand l ed w i th t he arc chutes and b ar r i er s removed. Mount these
parts after t he b reake r has been moved near the metal c l ad c e l l s t ruc t ur e . B e fo r e i n
ww
5
om
A I R C I RCU I T B R E A K E R TYPES 75 0 11 £ • 1 5 0 DHE
_ ,.., ,
.c
a. P l ac e a r op e s l i n g t hrough t h e 5/8 d i a. stud loc ated at the ton c en t e r o f eac h arc c h u te .
ls
c. Remove t h e h i nge p i n from t h e uppe r bus h i n g f l ang e.
d. Low e r arc chute i n t o n l ace so that back end i s between h i n t!:P b racke t on ur n e r· b u s h i n g
ua
f l ange . Use c are i n 1 i n i ng up the arc chute so that rear a re horn el i p mak (' s f!:Ood con
e. I n s e r t h i nge p i n and p u t c o t t e r p i n s i n p l ac e .
an
f. Bo l t a r c ho rn connec t o r t o front arc h o r n i n t h e chute.
g. T i gh t en lower connec t io n o f arc horn connec t o r s i nce it ma.Y have come l oosp rl u r i n g s h i p
tM
me n t .
h. Make f i nal check b y ope rat i n g b r eake r s l o w l y b y hand , and s e e that the r e i s n o i n t e r f e r
e n c e w i t h t he moveme nt o f t h e c o n t ac t s .
ar
5. T h e i n t e r p hase barr i e r sho u l d now be p u t i n p l ac e . Because o f t he s i ze a n d we i g h t , t he
b ar r i e r assemb ly i s d iv ided i n to four p a r t s . Three o f the parts con s i s t o f i n s u l a t i ng
comp a rt ments - l e f t phase , c e n t e r phase and r i ght phase. The compar tmen t s a r P not i n t e r
lP
6. The b reaker i s now ready to be ope r at ed e l ect r ic a l l y . Each b reak e r should be c l osed and
t r i pped e l ec t r i cal ly several t i mes b e fo r e b e i n g connected to h i g h vol t ag e . T h e s e ope ra
lec
operat i n g pos i t i o n .
C A U T I ON : Do n o t a t t em p t t o c l o s e t h e b re a k e r b y h a n d a g a i n s t a n e n e r g i z e d c i r c u i t . To
i n s u re s u f f i c i en t c l os i n g force a n d s p e ed , t h e b r ea k e r s h o u l d b e c l o s ed e l e c t r i c a l l y f r om a n
a d e q u a t e p o we r s o u r c e . S e e H E MA s t a n d a r d S G - 6 - 2 1 3 .
w
6
om
A I R C IRCU I T BREAKER TYPES 75 DHE• l 5 0 DHE
O P E R A T I O N A N D ADJ U S TM E N T
.c
The ope rat i o n a n d ad j us t ments o f the break e r i s the same as t h a t for the b re ak e rs d e
s c r i bed i n I . B. 3 2 - 25 1 - 3 . Reference shoul d be made to Pages 9 t hrough 1 2 o f the I . B . f o r i n
forma t i o n cov e r i n g t he Mechan ism, Mec han i s m Pan e l w i t h i t s asso c i ated t r i p p i n g d e v i c e and
aux i l i a r i es , and Mech a n i s m Adj us t men t s .
ls
C O N TA C T A D J U S TME N T
ua
The contac t s o n t h i s b reaker are the same a s t h o s e d e s c r i bed on Pages 23 a n d 26, i n t h e
i ns t ruct ion book. Any adj us t men t s t ha t are nec essary sho u l d be made as o ut l i ned i n that sec
t ion.
an
ARC C H U TE S
tM
co i l s , t ransfer a rc ho rns, t rans f e r stacks, m a i n i n t e r ru p t e r stacks, a front arc ho r n , and a
rear arc horn, al l assemb l e d i n and about a fab r icated rec tangul ar c hu t e j ac k e t . Th e arc
c h u t e i s h i nged t o t he break e r and when it is in the normal pos i t i o n , i t s l o wer e nd comp l e t e l y
s u r ro unds t h e contac t s t ruc t u r e .
ar
The b l owout mag n e t i s l o c at ed s o that t h e magn e t i c c o r e passes t h ro ugh t h e c e n t e r o f t h e
arc chute. T h e b l o wo u t co i l s are wound about t h e c o r e and l i e i n w i ndows cut in t h e chute
side sheet s . One t e rm i n a l of each c o i l connec t s to a t ransf e r arc horn and the o th e r t e r m i nal s
lP
s tacked w i t h the s l o ts al t e rnat i ng from one s ide to the o t h e r , t h e arc mus t t ake a serpen t i n e
path a s i t moves up i n to t h e arc c h u t e , t h us i nc reas i ng the l en g t h o f the arc .
arc t rans fers from the arc i ng con tac t s . The front arc horn i s c onne c t ed e l ec t r i c a l l y to t he
mov i n g contac t h i n ge , and t h e rear arc horns automat i c a l l y connects to the s t a t ionary con tac t
when the arc chute i s l owered to i ts normal pos i t i o n .
lec
i n t er r u p t ed p l ac i n g t h e b lowout c o i l i n s e r i e s w i t h t h e a r c .
7
om
A I R C I RCU I T B R E A K E R T YPE S 75 D HE• 1 S 0 DH E
A RC C H U T E L I F T E R
.c
In order t o raise t he a r c chutes f o r contac t inspec t ion and maint enanc e , an a r c chute
l i ft e r i s p ro v i d e d . T h i s attac hment which uses t he mechan i c a l advan tage of the l eve r i ng - i n
dev i ce t o prov i de the l i f t i n g fo r c e , cons i s t s o f a 1 " d iame t e r stee l ba r , and two c hann e l
shaped arms. The s te e l b a r i s i n s e rt ed t hrough t h e a r c chute open ings , and t h e arms a r e s e
c u r e d i n p l ace a s shown i n F i g . 3.
ls
T o r a i s e t h e a r c chutes r e f e r t o F i g ure 3 and p roceed a s fol l ows :
1.
ua
Remove bar r i e r assemb l y .
an
4. P l ace c rank o n l ev e r ing- i n dev i c e opera t i n g shaft and rotate c l oc k w i s e s o that the ro l l e r s
at each s ide o f t h e b reak e r advance forward enough t o i ns e r t the oppos i te e n d o f the c han
nel arms. C l amp the arms over t he ro l l er s .
5.
6.
D i sconnect shunt st raps from front a r c ho r n .
tM
P l ace c rank on l e ve r i ng - i n operat i n g s h a f t a n d cont i nue t o rotate c lockw i s e to r a i se t h e
a r c chute t o pos i t ion shown i n F ig u r e 3.
ar
I t i s impo rtant t h a t the arc c h u t e s b e r a i sed unt i l t he i nd i cato r on t h e f r o n t o f the
b reake r shows t hat t h e f ul l t r ave l of t h e l ev e r ing- i n device has been used. Th i s r e l eases
lP
1 to 6 i n reverse o rd e r .
C A U T I ON : After i n s p e c t i n g t h e co n t a c t s a n d a rc c h u t e s a n d b e f o r e r e t u r n i n g t h e b r e a k e r
t o s e rv i c e , mak e c e r t a i n t h a t t h e s h u n t c o n n e c t i on t o t h e f ron t a r c h o r n s i s bo l t e d t i g h t .
tri
H O R I Z O N T A L D RAWOUT A R R A N G EM E N T
lec
The b reak e r i s arran ged fo r use in ho r i zo n t a l d r awout metal c l ad equi pment and any que s
t i ons pert a i n i ng to t h i s ar rangeme nt , w h i c h i nc l ud e s o p e rat ion o f t h e break e r l ev e r ing- i n de
v ic e , s ho u l d be re fer red to I . B . 32- 25 1 - 3 Pages 8 t hrough 22.
.E
MA I N T E N A N C E
PARTS I D EN T I F I C AT I O N
8
om
A IR C IRCU I T BREAKE R T Y P F. S 75 D II E • l S O D II E
type and rat i ng o f the b r eak e r for wh i c h the par ts are r e q u i red . The break e r namep l a t e w i l l
.c
i d en t i fy the b reaker type and rat i ng.
MO T O R O P E RA T E D B R E A K E R S
ls
i n g mechan i sm, a n d are suppl i ed w i t h the o rd e r i nvo l v i n g t h i s t y p e o f equ i pmen t .
ua
an
tM
ar
lP
ca
tri
lec
.E
w
ww
9
ww
w
.E
lec
tri
ca
lP
ar
tM
an
ua
ls
.c
om
�;
r •• ·"