C6200 Generator Controller

• Combined Synchronizer and Loadsharer


• Synchroscope on the front panel
• Reverse power protection 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 58 58 59 60 61 62 63 64 65 66 67

AUX GOV AVR UN C/B PROT UNLOAD PROGRAMMABLE ANA


ALARM
• Excitation loss protection SUPPLY CONTROL C/B LOAD CLOSE TRIP TRIP OUTPUTS OUT

+ - + - 1 2 3 4 5 6 7 8

• 8 programmable inputs and outputs for


auxiliary functions
C6200 RS232

• RS485 Modbus communication GENCONTROLLER


123456

• CAN bus for optional user interface


RS485 CANBUS
• Direct control of electronic governors SYNC 1 2 3 4 5 6 7 8

• Increase/ decrease pulse outputs for BUSBAR


VOLTAGE
GENERATOR
VOLTAGE
GENERATOR
CURRENT
PROGRAMMABLE
INPUTS
ANA
IN
PAR
LINES
PRG

speed and voltage control 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28

Figure 1. Front of C6200

Application In case the engine is equipped with relays which will control the motorized
C6200 is a combined synchronizer and an electronic governor, the analogue potentiometer.
loadsharer for paralleling of generators. outputs can be used for control of the
The unit can be used in any application speed. The output signal can be a vol- Synchronizing
where generator should run in parallel tage, current or PWM signal. In case increase/ decrease pulse
with each other or with the grid. For contacts are used for speed control,
easy commissioning the unit includes a It is possible to program the output synchronizing is performed according
synchroscope on the front panel. signals regarding level and reference, to the dynamic synchronizing principle.
so they can be adapted to virtually any This means that the incoming generator
C6200 also includes reverse power and governor in the market such as GAC or will be connected with a slightly higher
excitation loss protection of the genera- Woodward. frequency than the busbar frequency.
tor.
In case it alternatively is desired to The purpose of this function is to make
8 sets of programmable auxiliary inputs control the speed through a motorized sure that the incoming generator will be
and outputs are available. They can be potentiometer or the servomotor of a loaded immediately in order not to take
used for auxiliary functions like exter- conventional governor a set of open col- reverse power.
nal commands for start synchronizing lector outputs can be used.
or load ramp functions. If alternatively the analogue outputs are
Voltage Control used, synchronizing is done according
RS485 Modbus communication allows For voltage matching and reactive load to the static synchronizing principle.
read out of the status of the unit or ex- sharing (kVAr) C6200 offers two sets of Frequency and phase angle will then
ternal control of the unit e.g. by a PLC. outputs for voltage control: be adjusted so the parameters of the in-
An analogue output can be used for The Automatic Voltage Regulator (AVR) coming generator match the parameters
indication of actual measurement of the alternator can be controlled by of the busbar (frequency of the incom-
values such as load or frequency of the an analogue signal (voltage, current or ing generator = frequency of the bus-
generator. PWM signal). bar). This is possible as the regulation
is much faster when using the analogue
A User Interface Unit S6500 can be con- It is possible to program the output outputs. The loadsharer will load the
nected through CAN bus. signals regarding level and reference, generator immediately after connection
Easy accessible modular connectors are so they can be adapted to virtually any thus avoiding a reverse power situation.
furnished on the front side of the unit. AVR on the market.
Voltage Matching
Speed Control In case a motorized potentiometer shall During synchronizing C6200 will adjust
For synchronizing and active load be used for control of the AVR a set of the voltage of the generator according
sharing (kW) C6200 offers two sets of open collector outputs can be used. The to the busbar voltage.
outputs for speed control: open collector outputs will then control
Load Sharing (kW) It is possible to define a trip level in % generator will be tripped. As the
The load sharing function will make of the nominal power and a trip delay healthy generators will keep supply-
sure that the active load in an installa- in seconds [s]. ing the busbar, this function can avoid
tion will be proportionally distributed blackouts.
between the parallel running genera- The unit includes two trip relays, one
tors. The load will be shared according for protection trips and another for The excitation loss protection is defined
to the percentage of nominal power of operational (unload) trips. The reverse by a trip level in % of the nominal reac-
the generators. It is possible to adjust power protection function trips the tive power in reverse direction and a
a load deviation in case a generator protection trip relay. trip delay in seconds [s]. It will trip the
should be loaded at a different rate than protection trip output relay.
the other generators. Excitation Loss Protection
In case generators are running in paral- Programmable Auxiliary I/O
Reactive Load Sharing (kVAr) lel their output voltages are the same. If C6200 includes 8 programmable inputs
The reactive load sharing function will one of the generators looses its excita- and 8 programmable outputs that can
make sure that the reactive load in an tion, it will take a reverse inductive be used for functions such as indication
installation will be proportionally di- current. As this phenomenon will load of protection trips, external commands
stributed between the parallel running the other generator with reactive load, for start of synchronizing or load sha-
generators. The reactive load will be it can lead to a decreasing busbar vol- ring and manual control of speed and
shared according to the percentage of tage. Eventually this could cause a low voltage.
nominal reactive power of the genera- voltage trip on all connected generators
tors. Also here it is possible to adjust a resulting in a blackout.
load deviation.
To avoid this, C6200 can measure the
Reverse Power Protection level and direction of the reactive cur-
C6200 includes a reverse power protec- rent. If the reactive current is leading
tion function with fixed time charac- into reverse direction and is larger than
teristics. a certain level, the C/B of the faulty
L1
L2
L3

GND GND

1 2 29 31 40 41 42 43 44 45 46 47 48 49 50 51 52 53 1 2 29 31 40 41 42 43 44 45 46 47 48 49 50 51 52 53
GND L1 L2 + - GND L1 L2 + -

C/B
C/B

Unload
Unload

Disable
Disable

Manual
Busbar Aux. Busbar Aux.

Freq. Ctrl.
Freq. Ctrl.

C/B Block

Figure 3. Simple 2 generator application


Reset Alarm
Reset Alarm

Voltage Supply C/B Close Prot. Trip Unload Trip Voltage Supply C/B Close Prot. Trip Unload Trip

C /B C6200 C /B C6200

Gen. Gen. Analogue Out 1 Alarm Gen. Gen. Analogue Out 1 Alarm
Parallel Lines Parallel Lines
Voltage Current Speed Control Voltage Current Speed Control
S2/ S1/ V/ S2/ S1/ V/

Prg. Out. 1
Prg. Out. 2
Prg. Out. 3
Prg. Out. 1
Prg. Out. 2
Prg. Out. 3

L1 L2 ref pwm mA kW gnd VAr L1 L2 ref pwm mA kW gnd VAr


L3 L3 DC L3 L3 DC
5 6 13 14 32 33 34 35 26 27 28 54 55 56 65 66 67 5 6 13 14 32 33 34 35 26 27 28 54 55 56 65 66 67

S1
S1

G o ve rno r G o ve rn o r

DG1 DG2
Specifications
C6200 Engine Controller
Voltage 24 VDC (-30% / +20%)
Generator voltage 63V to 690V
Generator rated frequency 50Hz/ 60Hz
Generator max. current 30.000A
Current transformer secondary current 5A
Power consumption Max 200mA
Ambient temp. range -20°­ C / +70° C
Relay contacts 230VAC / 2A & 30VDC / 2A
Open collector outputs 200mA per channel
External communication MODBUS RTU
Programmable digital inputs 8
Programmable digital outputs 8
Programmable analogue outputs 2
Current measurement Single phase
Weight 1,500 Kg
Dimension (mm) (282 x 182 x 50)mm

Type Selection
Type Supply voltage Generator voltage Current transformer
C6200.0010 24VDC 63V – 690V 5A
C6200.0020 24VDC 63V – 690V 1A

SELCO Worldwide

SELCO Denmark
SELCO subsidiary
SELCO representation

Main office:
SELCO A/S
Betonvej 10
DK-4000 Roskilde
Denmark
Phone: + 45 7026 1122
M6295 - 82UK

Fax: + 45 7026 2522


e-mail: selco.dk@selco.com
www.selco.com