Professional Documents
Culture Documents
Management Energy in Building 3
Management Energy in Building 3
Acoustic comfort
Visual comfort
Aesthetics
Thermal Comfort (I)
• According to the ANSI/ASHRAE Standard 55-2010, thermal comfort is
defined as “that condition of mind which expresses satisfaction with the
thermal environment and is assessed by subjective evaluation.
• Noticed that the lower limit of effective temperature for winter is 20̊C, the
upper limit of effective temperature in summer is 26̊C. Relative humidity
(RH) between 45% to 70%, depend on temperature. (Chirarattananon,
2005)
• The study on thermal comfort by Karyono and Tri Harso (2000) has been
carried out in Jakarta by survey to 596 officers in seven buildings. The
result is 87% officers feel comfortable in the range 21.7̊C to 29.0̊C with
neutral temperature 25.3̊C.
Thermal Comfort (II)
• thermal comfort zone is shown in psychometric chart
• Dry bulb temperature (DBT) from 24̊C to 29̊C and absolute humidity (AH)
from 4 to 19, it is the vapor content of air, given in grams of water vapor
per kilogram of air.
Thermal Comfort (III)
• Factors in human comfort:
– Metabolic rate (met): The energy
generated from the human body
– Clothing insulation (clo): The amount of
thermal insulation the person is wearing
– Air temperature: Temperature of the air
surrounding the occupant
– Radiant temperature: The weighted
average of all the temperatures from
surfaces surrounding an occupant
– Air velocity: Rate of air movement given
distance over time
– Relative humidity: Percentage of water
vapor in the air
Thermal Comfort (IV)
• A method of describing thermal
comfort was developed by Ole Fanger
and is referred to as Predicted Mean
Vote (PMV) and Predicted Percentage
of Dissatisfied (PPD).
• The Predicted Mean Vote (PMV) refers
to a thermal scale that runs from Cold
(-3) to Hot (+3), originally developed
by Fanger and later adopted as an ISO
standard.
• The recommended acceptable PMV Simulation:
range for thermal comfort from http://sustainabilityworkshop.autod
ASHRAE 55 is between -0.5 and +0.5 esk.com/buildings/human-thermal-
for an interior space. comfort
Thermal Comfort (V)
• Predicted Percentage of Dissatisfied (PPD) predicts the percentage of
occupants that will be dissatisfied with the thermal conditions.
• It is a function of PMV, given that as PMV moves further from 0, or
neutral, PPD increases.
• The maximum number of people dissatisfied with their comfort conditions
is 100% and, as you can never please all of the people all of the time, the
recommended acceptable PPD range for thermal comfort from ASHRAE 55
is less than 10% persons dissatisfied for an interior space.
Thermal Comfort (VI)
• The Math behind PMV & PPD
E=10
Thermal Comfort (VII)
• Adaptive comfort
– Adaptive comfort models add a little more human behaviour to the
mix.
– if changes occur in the thermal environment to produce discomfort,
then people will generally change their behaviour and act in a way
that will restore their comfort
Lighting Comfort (I)
• Candelas (cd): luminous intensity and is a measure of the overall amount
of light being produced
• Lumens:the amount of light that travels in certain directions from the
source is called the "luminous flux" or "radiant flux“
• Lux: The amount of light falling on a surface is illuminance, and is
measured in lux (metric unit = lumen/m2) or foot-candles (English unit =
lumen/ft2). For example, design sky illuminances for cities in Indonesia
refer to 10,000 lux based on SNI 03-2396-2001 about Code on Daylighting
System Planning for Buildings.
• There are2 types of lighting sources:
– Daylighting
– Artificial lighting
Lighting Comfort (II)
• Daylighting
– Daylighting analysis based on static measurement in Daylighting Factor
(DF)- percent ratio between light level inside and outside as follows:
– Where
Iin = Light level inside the room (lux).
DF = Daylighting Factor, the value 0-1 or 0%-100%
Iout = Light level outside, this method use uniform sky 10000 lux based
on Indonesian standard.
– DF could be calculated in different way by room properties as
following:
Lighting Comfort (III)
• The equation simplifies in Table below from SNI 03-2396-2001by knowing
ratio L/D and H/D.
Lighting Comfort (IV)
• In SNI mentioned main distance (MD) and secondary distance (SD) for light
measurement.
• MD measures 0.75 m from the floor and 1/3 room’s length from window.
• Then SD, measure 0.5 m from the side wall. The standard daylighting
shown
LLF= a.b.c.d.e.f.g
Lighting Comfort (VII)
• Total lumen output from the lamp (ɸL) can be obtained
∅𝐿𝐿 = 𝑛𝑛. 𝐸𝐸𝑓𝑓. 𝑃𝑃
Audio Comfort