Professional Documents
Culture Documents
2-PX NPCU Manifold Data Sheet 20150318
2-PX NPCU Manifold Data Sheet 20150318
2-PX NPCU Manifold Data Sheet 20150318
The fully automatic manifold shall be a Powerex Genesys™ The header bars shall be equipped with emergency high
NPCU series. No manual resetting of valves or levers shall pressure shutoff valves outside the cabinet to allow for
be required. The unit shall switch from “Bank in Use” emergency isolation of the header bars. The header bar
to “Reserve” bank without fluctuation in line delivery shall incorporate integral check valves for each station.
pressure. Simultaneously, the “Reserve in Use” alarm
shall be triggered by the manifolds circuit board. The
manifold shall continue to provide gas, in the event of a
power failure, until both banks are depleted. After the
switchover, the “Reserve” bank shall then become the
Flow Capacity
Gas Service Standard Line Regulators High Capacity Line Regulators Without Heaters With Heaters
Air, Argon, Oxygen, Medical Air, 2,500 SCFH 4,500 SCFH
N/A N/A
Medical Mixtures, Nitrogen, Tri-Gas (1,180 l/min) (2,120 l/min)
5,000 SCFH
Hyperbaric Oxygen N/A N/A N/A
(2,358 l/min)
40 SCFH 500 SCFH
Nitrous Oxide or Carbon Dioxide X N/A
(19 l/min) (236 l/min)
3,000 SCFH 6,000 SCFH
Nitrogen N/A N/A
(1,415 l/min) (2,830 l/min)
Powerex • 150 Production Drive • Harrison, OH 45030 • USA 12/2014
(T) 1.888.769.7979 • (F) 513-367-3125 • www.powerexinc.com Page 1 of 2
Genesys™ Fully Automatic Analog Manifolds for Industrial
and Healthcare High Pressure Cylinder Applications
Dimensional Drawing
Design Lengths
Total Number of Cylinders 4 6 8 10 12 16 20
STANDARD (10” INCH CENTERS) 5’ - 3” 6’ - 11” 8’ - 7” 10’ - 3” 11’ - 11” 15’ - 5” 18’ - 9”
OVERALL MANIFOLD LENGTH (1.60m) (2.11m) (2.62m) (3.12m) (3.63m) (4.65m) (5.72m)
STAGGERED DESIGN (5” CENTERS) 4’ - 6” 5’ - 4” 6’ - 2” 7’ - 0” 7’ - 10” 9’ - 6” 11’ - 2”
OVERALL MANIFOLD LENGTH (1.32m) (1.57m) (1.83m) (2.08m) (2.34m) (2.85m) (3.35m)
VERTICAL CROSSOVER (10” CENTERS) 3’ - 7” 5’ - 3” 6’ - 11” Contact Contact
N/A N/A
OVERALL MANIFOLD LENGTH (1.10m) (1.60m) (2.11m) Powerex Powerex
Ordering Information
Easy to use modular ordering system. Fill in the 10 blanks to specify the manifold that meets your needs.
Delivery Pressure
Country Final Line Regulation 1 = 50psi
NPC = Cylinders x U = USA 1 = Single Line Regulator 2 = 80psi
Cylinders C = Canada 2 = Dual Line Regulators 3 = 180psi
PX –
Examples:
PX-NPCU12OX1L = Cylinder x Cylinder Genesys™ Analog Manifold, Standard Cabinet, CGA 540 Oxygen service, Dual Line
Regulators, 50 psi delivery, standard flow.