CABLE GLANDS
2
10
METAL CABLE GLANDS TYPE ADE (<2000 cm ) Ex-d 3 8.11
11
M E T A L C A B L E G L A N D S T Y P E A D L ( > 2 0 0 0 c m 3) E x - d 8.23
12
E X - C A B L E G L A N D S
Plastic version for Zone 1 and Zone 21
International approvals
8.2
I Ex-cable glands I
1
2
Screw plug Blanking plug Cable gland for Ex-i Cable gland for Ex-e
Technical data 3
Ex-e Cable glands ⎮ Blanking plugs ⎮ Reducing rings
Marking to 94/9/EC II 2 G Ex e II / II 2 D Ex tD A21 IP66
EC-Type Examination Certificate of conformity M12-M16: PTB 99 ATEX 3101 X / M20-M63: PTB 99 ATEX 3128 X
IECEx Certification of conformity
Marking accd. to IECEx
IECEx PTB 05.0004X
Ex e II
4
Permissible ambient temperature –20 °C to +70 °C
–55 °C to +70 °C option1)
Degree of protection accd. EN 60529 IP66 / IP68: 1 m water depth for 0.5 h
Enclosure material Polyamide
10
11
12
COOPER CROUSE-HINDS GMBH 8.3
I Ex-cable glands I
Cable gland for Ex-e Cable gland for Ex-i Enlargement cable gland Multiple cable gland
Ordering details
2
Reducing ring Screw plug Blanking plug
Ordering details 3
For cable ØA Length B Weight OU Order No.
gland mm mm approx. kg (–20 °C up to 70 °C)
Blanking plug
M12
M16
6.0
7.0
30.3
33.0
0.001
0.001
20
20
GHG 960 1944 R0101
GHG 960 1944 R0102
4
M20 8.5 34.5 0.002 20 GHG 960 1944 R0103
M25 11.0 36.0 0.003 20 GHG 960 1944 R0104
M32 14.0 39.5 0.005 20 GHG 960 1944 R0105
M40 20.0 42.0 0.018 10 GHG 960 1944 R0106
M50
M63
26.0
34.0
44.0
45.0
0.033
0.108
10
5
GHG 960 1944 R0107
GHG 960 1944 R0108
5
Thread ØD Length A Length B Weight OU Order No.
mm mm mm approx. kg
Screw plug
M16 x 1.5
M20 x 1.5
21.5
25.5
4.0
4.0
12
13
0.002
0.004
20
20
GHG 960 1952 R0111
GHG 960 1952 R0112
6
M25 x 1.5 30.5 4.0 13 0.007 20 GHG 960 1952 R0113
M32 x 1.5 37.5 5.5 15 0.013 10 GHG 960 1952 R0114
M40 x 1.5 45.5 5.5 15 0.020 10 GHG 960 1952 R0115
M50 x 1.5 55.5 5.5 16 0.030 5 GHG 960 1952 R0116
M63 x 1.5 85 6.5 16 0.040 5 GHG 960 1952 R0117 7
Thread Thread L1 L2 L3 AF Weight OU Order No.
1 2 mm mm mm mm approx. kg
Reducing rings
M20 x 1.5
M25 x 1.5
M16 x 1.5
M20 x 1.5
12
14
8
8
8
8
24
29
0.014
0.016
20
20
GHG 960 1946 R0071
GHG 960 1946 R0072 8
M32 x 1.5 M20 x 1.5 16 10 6 36 0.017 20 GHG 960 1946 R0056
M32 x 1.5 M25 x 1.5 16 10 10 36 0.016 20 GHG 960 1946 R0074
M40 x 1.5 M25 x 1.5 16 10 8 46 0.023 10 GHG 960 1946 R0059
M40 x 1.5 M32 x 1.5 16 10 10 46 0.021 10 GHG 960 1946 R0077
M50 x 1.5
M50 x 1.5
M32 x 1.5
M40 x 1.5
18
18
12
12
10
10
55
68
0.036
0.032
10
10
GHG 960 1946 R0062
GHG 960 1946 R0080 9
M63 x 1.5 M40 x 1.5 18 12 10 68 0.040 5 GHG 960 1946 R0065
M63 x 1.5 M50 x 1.5 18 12 12 68 0.030 5 GHG 960 1946 R0083
Cable glands with PG-thread are available on request.
The order No. will show 1 pcs.
Please note that only order units (OU) can be ordered.
10
11
12
COOPER CROUSE-HINDS GMBH 8.5
I Ex-cable glands I
Dimensions drawing
B
A/F
A
G
A
CE
Blanking plug
L1 L2
Cable gland
D
A
B
Thread
Screw plug
L3
PT
Thread 1
Thread 2
B
M
12
.NR
X1.
. EX– 02 .C
5 X M2
CIX
.3
1
42
1.
5
A/F L2
Reducing ring L1
Dimensions in mm
2
Trumpet shaped gland
Technical data 3
Ex-e trumpet shaped cable gland
Marking to 94/9/EC II 2 G Ex e II / II 2 D Ex tD A21 IP66
EC-Type Examination Certificate PTB 00 ATEX 3121
Permissible ambient temperature –40 °C to +85 °C
–50 °C to +80 °C option1)
4
Degree of protection accd. EN 60529 IP66
Enclosure material Polyamide
Ordering details
E
8
9
L1
A/F
L2
10
Thread
Trumpet shaped cable gland
11
Dimensions in mm
12
COOPER CROUSE-HINDS GMBH 8.7
I Ex-cable glands I
Technical data
Ordering details
Dimension drawing
M25x1.5 mm A/F 30 L1 L2
M25x 1.5
A/F30
CEAG
A/F
M25
19.7 9
Ø32
Dimensions in mm
23.5 SW 27 14.5
Drainage plug
36
2
Spanner Gasket Lock nut
Accessories 3
Ordering details lock nut for cable glands
Type A/F Thickness Weight OU Order No.
mm mm g
M12 x 1.5
M16 x 1.5
17
22
5
5 14
9 10
10
GHG 960 1941 R0031
GHG 960 1941 R0032
4
M20 x 1.5 26 6 22 10 GHG 960 1941 R0033
M25 x 1.5 32 6 32 10 GHG 960 1941 R0034
M32 x 1.5 41 7 59 10 GHG 960 1941 R0035
M40 x 1.5 50 7 79 5 GHG 960 1941 R0036
M50 x 1.5
M63 x 1.5
60
75
8
8
98
150
5
5
GHG 960 1941 R0037
GHG 960 1941 R0038
5
Ordering details gaskets for glands
Type ØD L Weight OU Order No.
mm mm g
M12 x 1.5
M16 x 1.5
18
22
1,2
1,2
0.44
0.50
10
10
CAP 221 249
CAP 221 649
6
M20 x 1.5 24 1,2 0.48 10 CAP 222 049
M25 x 1.5 30 1,5 0.69 10 CAP 222 549
M32 x 1.5 42 1,5 1.39 10 CAP 223 249
M40 x 1.5 52 1,5 2.00 10 CAP 224 049
M50 x 1.5
M63 x 1.5
63
77
1,5
2,0
2.00
4.80
10
10
CAP 225 049
CAP 226 349
7
Ordering details special spanner for fastening of cable glands
Type Size SW Weight Order No.
mm kg
Set 1 M12
M16
15
20
8
M20 24
M25 29
M32 36
M40 46 0.825 GHG 960 1951 R0001
Set 2 M50
M63
55
68 0.905 GHG 960 1951 R0002
9
The order No. will show 1 pcs.
Please note that only order units (OU) can be ordered.
10
11
12
COOPER CROUSE-HINDS GMBH 8.9
E X - C A B L E G L A N D S
Metal design for Zone 1 and Zone 21
Internationally approved.
8.10
I Ex-cable glands I
1
2
ADE 4F NPT ADE 4F ISO ADE 1F NPT ADE 1F ISO
Technical data 3
Ex-e cable glands metal design ADE 1F ⎮ ADE 4F
Marking to 94/9/EC II 2 G Ex e II / Ex d IIC (IIC ≤ 2000 cm³) / II 2 D Ex tD
EC-Type Examination Certificate LCIE 97 ATEX 6008 X
IECEx-Certificate of Conformity
Marking accd. to IECEx
IECEx LCI 05.0004X
Ex d IIC / Ex e II / Ex tD
4
Permissible ambient temperature –40 °C up to +100 °C
–70 °C up to +220 °C (option)
Degree of protection accd. EN 60529 IP66 / IP68 - 10 bar
Thread ISO-thread accd. ISO 965/1, ISO 965R and EN 60423
Enclosure material Brass, nickel-plated
5
10
11
12
COOPER CROUSE-HINDS GMBH 8.11
I Ex-cable glands I
ADE 1F ISO
Ordering details
Cable gland type ADE 1F MsNi for unarmoured cables with ISO thread
M12 x 1.5 4 4.0 - 8 15 15 20 15 0.020 CAP 816 404
M16 x 1.5 4 4.0 - 8.5 15 19 20 15 0.025 CAP 816 594
M16 x 1.5 5 6.0 - 12 19 19 22 15 0.030 CAP 816 504
M20 x 1.5 4 4.0 - 8.5 15 24 20 15 0.056 CAP 816 674
M20 x 1.5 5 6.0 - 12 19 24 22 15 0.038 CAP 816 694
M20 x 1.5 6 8.5 - 16 24 24 25 15 0.045 CAP 816 604
M25 x 1.5 5 6.0 -12 19 30 22 15 0.088 CAP 816 774
M25 x 1.5 6 8.5 - 16 24 30 25 15 0.055 CAP 816 794
M25 x 1.5 7 12 - 20.5 30 30 27 15 0.070 CAP 816 704
M32 x 1.5 7 12 - 21 30 36 27 15 0.100 CAP 816 894
M32 x 1.5 8 16 - 27.5 41 41 34 15 0.150 CAP 816 804
M40 x 1.5 8 16 - 27.5 41 44 34 15 0.175 CAP 816 994
M40 x 1.5 9 21 - 34 48 48 36 15 0.210 CAP 816 904
M50 x 1.5 9 21 - 34 48 55 36 16 0.245 CAP 817 094
M50 x 1.5 10 27 - 41 55 55 39 16 0.285 CAP 817 004
M63 x 1.5 11 33 - 48 64 67 41 17 0.400 CAP 817 294
M63 x 1.5 12 40 - 56 72 72 43 17 0.490 CAP 817 204
M75 x 1.5 12 40 - 56 72 80 43 18 0.560 CAP 817 394
M75 x 1.5 13 47 – 65 85 85 49 18 0.735 CAP 817 304
M80 x 2.0 13 47 – 65 85 85 49 20 0.885 CAP 817 494
M80 x 2.0 14 54 – 73 95 95 56 20 1.060 CAP 817 404
M90 x 2.0 14 54 – 74 95 95 56 22 1.300 CAP 817 594
M90 x 2.0 15 63 – 82 110 110 61 22 1.665 CAP 817 504
M100 x 2.0 15 63 – 83 110 110 61 22 1.850 CAP 817 694
M100 x 2.0 16 72 – 92 120 120 62 22 2.160 CAP 817 604
Please use sealing washers (see page 8.18).
Enlarged temperature range from –70 °C up to +220 °C please use Order No.: CAP...5 instead of CAP...4
Dimension drawing
CA PRI
Ax1,1
Bx1,1
A
L E
Type ADE 1F
Dimensions in mm
2
ADE 1F NPT
Ordering details 3
Thread Type Cable Ø A B L E Weight Order No.
mm mm mm mm mm kg
Cable gland type ADE 1F MsNi for unarmoured cables with NPT thread
1/4“
3/8“
4
4
4.0 - 8
4.0 - 8.5
15
15
15
19
20
20
12
12
0.020
0.025
CAP 818 404
CAP 818 594
4
3/8“ 5 6.0 - 12 19 19 22 12 0.030 CAP 818 504
1/2“ 4 4.0 - 8.5 15 24 20 16 0.062 CAP 818 674
1/2“ 5 6.0 - 12 19 24 22 16 0.040 CAP 818 694
1/2“ 6 8.5 - 15.5 24 24 25 16 0.045 CAP 818 604
3/4“
3/4“
5
6
6.0 - 12
8.5 - 16
19
24
30
30
22
25
16
16
0.097
0.055
CAP 818 774
CAP 818 794
5
3/4“ 7 12 - 20.5 30 30 27 16 0.070 CAP 818 704
1“ 7 12 - 21 30 36 27 20 0.110 CAP 818 894
1“ 8 16 - 26 41 41 34 20 0.160 CAP 818 804
1“1/4 8 16 - 27.5 41 44 34 20 0.180 CAP 818 994
1“1/4
1“1/2
9
9
21 - 34
21 - 34
48
48
48
51
36
36
20
20
0.220
0.260
CAP 818 904
CAP 819 094
6
1“1/2 10 27 - 41 55 55 39 20 0.300 CAP 819 004
2“ 11 33 - 48 64 64 41 20 0.420 CAP 819 294
2“ 12 40 - 53 72 72 43 20 0.510 CAP 819 204
2“1/2 12 40 - 56 72 80 43 28 0.600 CAP 819 494
2“1/2
3“
13
14
47 – 62.5
54 – 74
85
95
85
95
49
56
28
30
0.800
1.400
CAP 819 404
CAP 819 594
7
3“ 15 63 – 78 110 110 61 30 1.700 CAP 819 504
3“1/2 15 63 – 83 110 110 61 32 1.900 CAP 819 694
3“1/2 16 72 – 92 120 120 62 32 2.300 CAP 819 604
Please use sealing washers (see page 8.18).
Enlarged temperature range from –70 °C up to +220 °C please use Order No.: CAP...5 instead of CAP...4 8
Dimension drawing
9
CA PRI
Ax1,1
Bx1,1
A
11
Dimensions in mm
12
COOPER CROUSE-HINDS GMBH 8.13
I Ex-cable glands I
ADE 4F ISO
Ordering details
Cable gland type ADE 4F MsNi for armoured cables with ISO thread
M12 x 1.5 5 6.0 - 12 4.0 - 8 0.9 19 19 36 15 0.048 CAP 846 404
M16 x 1.5 5 6.0 - 12 4.0 - 8.5 0.9 19 19 36 15 0.057 CAP 846 594
M16 x 1.5 6 8.5 - 16 6.0 - 12 1.25 19 24 36 15 0.078 CAP 846 504
M20 x 1.5 5 6.0 - 12 4.0 - 8.5 0.9 19 24 36 15 0.080 CAP 846 674
M20 x 1.5 6 8.5 - 16 6.0 - 12 1.25 24 24 42 15 0.090 CAP 846 694
M20 x 1.5 7 12 - 21 8.5 - 15.5 1.25 30 30 46 15 0.123 CAP 846 604
M25 x 1.5 6 8.5 - 16 6.0 - 12 1.25 24 30 42 15 0.122 CAP 846 774
M25 x 1.5 7 12 - 21 8.5 - 16 1.25 30 30 46 15 0.170 CAP 846 794
M25 x 1.5 8 16 - 27.5 12 - 20.5 1.6 41 41 56 15 0.270 CAP 846 704
M32 x 1.5 8 16 - 27.5 12 - 21 1.25 41 41 56 15 0.310 CAP 846 894
M32 x 1.5 9 21 - 34 16 - 27.5 1.6 48 48 63 15 0.400 CAP 846 804
M40 x 1.5 9 21 - 34 16 - 27.5 2.0 48 48 63 15 0.445 CAP 846 994
M40 x 1.5 10 27 - 41 21 – 34 2.0 55 55 68 15 0.540 CAP 846 904
M50 x 1.5 10 27 - 41 21 - 34 2.0 55 55 68 16 0.600 CAP 847 094
M50 x 1.5 11 33 - 48 27 - 41 2.5 64 64 74 16 0.735 CAP 847 004
M63 x 1.5 12 40 - 56 33 - 48 2.5 72 72 77 17 0.996 CAP 847 294
M63 x 1.5 13 47 - 65 40 - 56 2.5 85 85 85 17 1.480 CAP 847 204
M75 x 1.5 13 47 -65 40 - 56 2.5 85 85 85 18 1.590 CAP 847 394
M75 x 1.5 14 54 -74 47 - 65 2.5 95 95 92 18 2.305 CAP 847 304
M80 x 2.0 14 54 -74 47 - 65 3.15 95 95 92 20 2.270 CAP 847 494
M80 x 2.0 15 63 - 83 54 - 73 3.15 110 110 104 20 3.150 CAP 847 404
M90 x 2.0 15 63 - 83 54 - 74 3.15 110 110 104 22 3.175 CAP 847 594
M90 x 2.0 16 72 - 93 63 - 82 3.15 120 120 108 22 3.675 CAP 847 504
M90 x 2.0 17 85 - 107 63 - 82 3.15 135 120 108 22 3.675 CAP 847 574
Please use sealing washers (see page 8.18).
Enlarged temperature range from –70 °C up to +220 °C please use Order No.: CAP...5 instead of CAP...4
Dimension drawing
CA PRI
Ax1,1
Bx1,1
A
L E
Type ADE 4F
Dimensions in mm
2
ADE 4F NPT
Ordering details 3
Thread Type Cable Ø Cable Ø Armour A B L E Weight Order No.
outside mm inside mm up to mm mm mm mm mm kg
Cable gland type ADE 4F MsNi for armoured cables with NPT thread
1/4“
3/8“
5
5
6.0 - 12
6.0 - 12
4.0 - 8
4.0 - 8.5
0.9
0.9
19
19
19
19
36
36
12
12
0.048
0.057
CAP 848 404
CAP 848 594
4
3/8“ 6 8.5 - 16 6.0 - 12 1.25 24 24 42 12 0.075 CAP 848 504
1/2“ 5 6.0 - 12 4.0 - 8.5 0.9 19 24 36 16 0.095 CAP 848 674
1/2“ 6 8.5 - 16 6.0 - 12 1.25 24 24 42 16 0.090 CAP 848 694
1/2“ 7 12 - 21 8.5 - 15.5 1.25 30 30 46 16 0.120 CAP 848 604
3/4“
3/4“
6
7
8.5 - 16
12 - 21
6.0 - 12
8.5 - 16
1.25
1.25
24
30
30
30
42
46
16
16
0.136
0.170
CAP 848 774
CAP 848 794
5
3/4“ 8 16 - 27.5 12 - 20.5 1.6 41 41 56 16 0.270 CAP 848 704
1“ 8 16 - 27.5 12 - 21 1.25 41 41 46 20 0.310 CAP 848 894
1“ 9 21 - 34 16 - 26 1.6 48 48 63 20 0.400 CAP 848 804
1“1/4 9 21 - 34 16 - 27.5 2.0 48 48 63 20 0.445 CAP 848 994
1“1/4
1“1/2
10
10
27 - 41
27 - 41
21 – 34
21 - 34
2.0
2.0
55
55
55
55
68
68
20
20
0.540
0.600
CAP 848 904
CAP 849 094
6
1“1/2 11 33 - 48 27 - 41 2.5 64 64 74 20 0.800 CAP 849 004
2“ 12 40 - 56 33 - 48 2.5 72 72 77 20 1.000 CAP 849 294
2“ 13 47 - 65 40 - 53 2.5 85 85 85 20 1.500 CAP 849 204
2“1/2 13 47 - 65 40 - 56 2.2 85 85 85 28 1.700 CAP 849 494
2“1/2
3“
14
15
54 - 74
63 - 83
47 – 62.5
54 - 74
2.5
3.15
95
110
95
110
92
104
28
30
2.400
3.300
CAP 849 404
CAP 849 594
7
3“ 16 72 - 93 63 - 78 3.15 120 120 108 30 3.800 CAP 849 504
Please use sealing washers (see page 8.18).
Enlarged temperature range from –70 °C up to +220 °C please use Order No.: CAP...5 instead of CAP...4
8
Dimension drawing
9
CA PRI
Ax1,1
Bx1,1
A
L E
11
Dimensions in mm
12
COOPER CROUSE-HINDS GMBH 8.15
I Ex-cable glands I
2
Lock nut Earth tag
12
COOPER CROUSE-HINDS GMBH 8.17
I Ex-cable glands I
Gasket
Dimension drawing
Ax1,1
C
ØD
ISO
L
L
B ØD
Earthing washer Strain clamp Ø
A
ØC
ØD E
Shroud Earth tag
Dimensions in mm
2
CMDEL NPT CMDEL ISO
Technical data 3
Ex-e cable glands metal design CMDEL
Marking to 94/9/EC II 2 G Ex e II / II 2 D Ex tD
EC-Type Examination Certificate LCIE 97 ATEX 6005 X
Permissible ambient temperature –40 °C up to +100 °C
–70 °C up to +220 °C (option)
4
Degree of protection accd. EN 60529 IP66 / IP68 - 10 bar
Thread ISO thread accd. ISO 965/1, ISO 965/2 and EN 60432
Enclosure material Nickel-plated brass (stainless steel, bronze, natural brass option)
Ordering details
5
Thread Cable Ø A L E Weight Order No.
mm mm mm mm approx. kg
Cable gland type CMDEL MsNi for unarmoured cables with ISO thread
M10 x 1.0 1.5 – 5.0 15 17 7 0.017 CAP 221 004
M12 x 1.5
M16 x 1.5
4.0 - 8.0
7.0 - 11
18
22
17
20
7
8
0.021
0.036
CAP 221 204
CAP 221 604
6
M20 x 1.5 8.0 - 13 24 20 8 0.043 CAP 222 004
M25 x 1.5 13.0 - 18 30 24 9 0.071 CAP 222 504
M32 x 1.5 17.5 - 25 41 28 10 0.143 CAP 223 204
M40 x 1.5 24.5 - 33.5 52 38 11 0.263 CAP 224 004
M50 x 1.5
M63 x 1.5
33.0 - 43
43.0 - 55
63
77
42
47
12
13
0.386
0.583
CAP 225 004
CAP 226 304
7
Cable gland type CMDEL MsNi for unarmoured cables with NPT thread
1/2“ 7.5 - 13 24 20 16 0.045 CAP 183 134
3/4“ 12.5 - 18 30 24 16 0.022 CAP 183 144
1“
1 1/4“
17.5 - 25
24.5 - 33.5
41
52
28
38
20
20
0.034
0.041
CAP 183 154
CAP 183 164
8
1 1/2“ 24.5 - 33.5 52 38 20 0.042 CAP 183 174
2“ 33 - 43 63 42 20 0.046 CAP 183 184
2 1/2“ 42.5 - 55 77 47 28 0.066 CAP 183 194
Please use sealing washers (see page 8.18).
9
Dimension drawing
Ax1,1
Ax1,1
10
A
L E
11
Dimensions in mm
12
COOPER CROUSE-HINDS GMBH 8.19
I Ex-cable glands I
Shroud
2
Lock nut Earth tag
12
COOPER CROUSE-HINDS GMBH 8.21
I Ex-cable glands I
Gasket
Dimension drawing
ØD Ax1,1
ØD
Ø
ISO
A
L
B
L
ØD
Shroud
Dimensions in mm
2
Type ADL 4F Type ADL 1F
Technical data 3
Ex-e cable glands metal design ADL 1F ⎮ ADL 4F V> 2000 cm 3
Marking to 94/9/EC II 2 G Ex d IIC / Ex e II / II 2 D Ex tD
EC-Type Examination Certificate LCIE 97 ATEX 6006 X
Permissible ambient temperature –40 °C to +100 °C
–70 °C up to +220 °C (option)
4
Degree of protection accd. EN 60529 IP66 / IP68 - 10 bar
Thread ISO thread acc. ISO 965/1, ISO 965/2 and EN 60423
Enclosure material Natural brass (stainless steel, MsNi, bronze option)
10
11
12
COOPER CROUSE-HINDS GMBH 8.23
I Ex-cable glands I
Type ADL 1F
Ordering details
Dimension drawing
CA PRI
Ax1,1
Bx1,1
A
L E
Dimensions in mm
2
Type ADL 4F
Ordering details 3
Thread Type Cable Ø2) Dimensions Weight Order No.
Outside Inside Armour A B L1) E approx.
mm mm up to mm mm mm mm mm kg
2)
The threaded up to 3/4” NPT compatible with ISO 7/1 conic 9
Dimensions with max. cable
Enlarged temperature range from –70 °C up to +220 °C please use Order No.: CAP...5 instead of CAP...4
10
11
12
COOPER CROUSE-HINDS GMBH 8.25
I Ex-cable glands I
Type ADL 4F
Ordering details
Dimension drawing
CA PRI
Ax1,1
Bx1,1
A
L E
Dimensions in mm
2
Shroud Strain clamp
10
11
12
COOPER CROUSE-HINDS GMBH 8.27
I Ex-cable glands I
2
Gasket
Dimension drawing
8
Ax1,1
C
ØD
ISO
L
L
ØA
Gasket Lock nut
9
B ØD
Earthing washer Strain clamp Ø
10
A
ØC
ØD E
Shroud Earth tag
11
Dimensions in mm
12
COOPER CROUSE-HINDS GMBH 8.29
I Ex-cable glands I
Technical data
Ex-d cable glands metal design Reducing rings ⎮ Screw plug ⎮ Adapter ISO-NPT
Marking to 94/9/EC II 2 G Ex e II / Ex d IIC / II 2 D Ex tD
EC-Type Examination Certificate LCIE 98 ATEX 0001 U
Permissible ambient temperature –40 °C to +100 °C
Degree of protection accd. EN 60529 IP66 / IP68 - 10 bar
Enclosure material Brass, nickel-plated (stainless steel, bronze, natural brass option)
Please use sealing washers (see page 8.18).
2
Reducing rings
Ordering details 3
Thread 1 Thread 2 A L E Order No.
(male) (female) mm mm mm
3
/ 2“
/ 4“
36
36
3.5
3.5
20
20
CAP 744 894
CAP 745 154
9
1“1/4 3 / 4“ 44 4.0 20 CAP 745 164
1“1/4 1“ 44 4.0 20 CAP 745 424
1“1/2 1“ 50 5.0 20 CAP 745 434
1“1/2 1“1/4 50 5.0 20 CAP 745 694
2“
2“
1“
1“1/4
64
64
5.5
5.5
20
20
CAP 745 444
CAP 745 704
10
2“ 1“1/2 64 5.5 20 CAP 745 964
2“1/2 1“1/2 75 6.0 28 CAP 745 974
2“1/2 2“ 75 6.0 28 CAP 746 234
3“ 2“ 90 8.0 30 CAP 746 244
3“
3“1/2
2“1/2
2“1/2
90
110
8.0
10.0
30
32
CAP 746 504
CAP 745 654
11
3“1/2 3“ 110 10.0 32 CAP 745 664
4“ 3“ 120 11.0 32 CAP 746 834
4“ 3“1/2 120 11.0 32 CAP 745 734
12
COOPER CROUSE-HINDS GMBH 8.31
I Ex-cable glands I
Screw plugs
Ordering details
2
Reducing rings
Ordering details 3
Thread 1 Thread 2 A L E ØD Order No.
(male) (female) mm mm mm mm
3
/2 “ NPT
/4 “ NPT
24
30
18
18.5
15
15
15.5
15.5
CAP 744 704
CAP 744 964
4
3
M25 x 1.5 /4 “ NPT 30 18.5 15 20.3 CAP 744 974
M25 x 1.5 1 “ NPT 38 22.5 15 20.3 CAP 745 234
M32 x 1.5 1 “ NPT 38 22.5 15 27.3 CAP 745 244
M32 x 1.5 1 “ 1/4 NPT 48 22.5 15 27.3 CAP 745 504
M40 x 1.5
M40 x 1.5
1 “ 1/4 NPT
1 “ 1/2 NPT
48
52
22.5
22.5
15
15
35.3
35.3
CAP 745 514
CAP 745 774
5
M50 x 1.5 2 “ NPT 64 22.5 16 45.2 CAP 746 044
M63 x 1.5 2 “ NPT 67 22.5 17 53.6 CAP 746 054
M63 x 1.5 2 “ 1/2 NPT 77 31 17 57.8 CAP 746 314
9
Ax1.1
Thread2
Thread1
A
L E
10
11
Dimensions in mm
12
COOPER CROUSE-HINDS GMBH 8.33