Professional Documents
Culture Documents
Rochester Gauges DLCC
Rochester Gauges DLCC
GAUGES,INT.
INSTALLATION MANUAL
Receiver CSU 3
RoHS
COMPLIANT
TABLE OF CONTENTS
1. INTRODUCTION
1.1 Presentation 3
1.2 Components and assembly 3
1.3 Environment terms 4
1.4 ID code structure 4
Receiver CSU 3
1.5 Receiver indentification labels 4
2. GENERAL OPERATION
3. CONNECTION / WIRING
4. RECEIVER SETTINGS
5. ANNEXES
Programming data sheet 17
LiYCY-OB 0.75mm² cable data sheet 18
Troubleshooting 19
Conformity declaration 20
MADE IN
EUROPE
Subjet to change without notification.
2/20
CHAPTRE 1
INTRODUCTION
Next generation of Compact Survey Unit (known as CSU 3) is having all options included (built in) as standard and
therefore no more “modular” (assembled to order with only specified options). On top of all options integrated, the
CSU 3 has an improved design and functionalities.
One major improvement is a bidirectional communication, transmitting informations (signal, content, ouputs and
settings) remotely and able to receive information from remote computer to modify settings and/or parameters;
through USB or RS485 communication port.
The receiver is approved for use in industrial environment allowing the “CE” marking.
All the settings, technical characteristics and parameters, user guide, installation procedure and ordering
informations are detailed in the next pages of this manual.
1.1 Presentation
The CSU 3 receiver has been designed for stationary application, associated with a Voltage output
transmitter, either Eexd 5k? (model 6323S*****) or Hall Effect (model 6320S*****), allows the remote reading
of tank content [expressed in %] onto 2 digits LED display combined with (4) four adjustable level set points
(each with a led on front display). The CSU 3 receiver also incorporates a control of mechanical gauge correct
operation.
The integrated options being:
-Current (4-20mA) output, self powered loop, allowing to convert tank volume (filling / emptying) to a passive
receiver (analogue or digital).
-RS485 communication output.
-USB2.0 communication output.
-Four (4) volt-free inverter relays (250VAC/3A)
associated to the adjustable set points.
3/20
1.3 Environment terms
In order to have the CSU 3 receiver matching the standard norms (see declaration of conformity page 20), it is
mandatory to respect below mentioned terms of environment:
Housing Type
E IP-20 for mounting on 35mm DIN rail
I receiver mounted in IP-65 sealed housing with transparent cover
IB receiver and prewired safety barrier mounted in IP-65 sealed housing
Power supply
3 24Vdc stabilised and regulated (±10%)
9 100 to 240Vac - 50/60Hz
4/20
CHAPTER 2
GENERAL OPERATION
The CSU 3 receiver generates and provides input power of 5VDC to the associated transmitter (Eexd voltage
transmitter or Hall effect Twiniste) and to the 4-20mA current loop.
The internal microprocessor converts the non linear signal received from the transmitter into a two (2) digits display
with 1% resolution and simultaneously controls the correct operation (float travel) of the level gauge thanks to
selected (adjustable) time delay.
The microprocessor allows the configuration for all the adjustable settings of the CSU 3 receiver (see chapter 4):
-calibration of receiver depending on the transmitter model (Eexd potentiometer with/without heel resistance or
Hall effect with/without safety barrier) and measurements line (line and/or contact resistance,…)
-Set points configuration (Min/Max level, time delay, logic).
-calibration of the 4-20mA current loop according to connected receivers (own resistance).
-Activation and settings for communication outputs RS485 and USB.
-Mechanical gauge's float travel check (filling/emptying).
If there is a fault on the sensor line (short-circuit or break in one or more jumpers), the receiver goes into
security mode and responds by:
- blinking the four red LEDs
- showing a flashing HS on the LED display
- switching all relays to their rest position (similar to a main power cut)
- setting the 4-20mA output to 0% (4mA)
- sending the default signal and hiding the volume on the RS485 and USB communication lines.
If the input signal is considered too low (depending on the sensor used, see page 12), the display shows a «
blinking LL »; inversely, if the signal is considered too high, the display shows a « blinking HH ».
If there is no display connected to the 4-20mA output, the receiver indicates this by causing the tank volume
(in %) to blink.
If the gauge movement detector receives contradictory information, « F » appears on the display.
LED display :
Indicates volume Set-points Leds
of tank in %
NO
NC
C
NO
NC
C
N L
100-240Vac Level 1 Level 2 Level 3 Level 4
88 %
50/60Hz 4W
P
CSU-3
V
Control Sensor USB RS485 4-20mA
C F E Sh S Sh A B Sh Sh
Control buttons
5/20
CHAPITRE 3
CONNECTION / WIRING
3.1 General Instructions
The following instructions are intended to help installers but in no way replace existing regulations, local
standards or laws. Non-compliance of these may undermine the protection.
Electrical installation and earthing of the equipment should be under approval, in compliance with the rules
and regulations for installations currently applicable in the country where the receiver is located. The
electrical system to which the CSU receiver is connected must have been officially checked and approved
and must be in accordance with the currently applicable standards. The main power supply of the CSU
receiver should go through a bipolar disconnector.
All operations (installation and wiring) should be executed by a qualified technician and the receiver should be
connected to the main earth connection of the installation.
The cables used for the various connections must be LiYCY-OB type (or equivalent), especially in an
industrial environment or any other location where electromagnetic interference may be present. Use only
this type of cable (LiYCY-OB) 0.75mm² in section so the line resistance is limited to 26? /Km and the line
capacitance to 130pF/Km at a frequency of 800Hz (see cable data sheet, page 17).
Also ensure that the distance between the transmitter (voltage-divider or with Hall Effect sensor) and the CSU
receiver does not exceed 300m.
3.3 Connecting a Hall Effect sensor with safety barrier (see page 9)
If the CSU is connected to a Hall Effect transmitter (6320S*207**) located in a dangerous area, the + line
MUST be protected with an intrinsec safety barrier as well as the « S » line. The choice of barrier is critical
because it must comply with the safety requirements for the sensor (see specific documentation for Hall
Effect transmitters) but also be as electrically neutral as possible so as not to affect sensor operation and not
interfere with the measurement (see page 9). The internal resistors in the barrier do, in fact, cause a line drop.
As a result, it is essential to ensure that the power to the Hall Effect sensor (see V ) is between 3.8 and 6 Vdc
for Hall Effect Standard. Ideally, it should be of 5VDC output safety barrier
HALL EFFECT JUNCTION CSU 3
SENSOR BOX SAFETY BARRIER RECEIVER
U* = 5 or 6V
EARTH EARTH I* = ~6mA
Max. 300m
- The sield of the cables must be connected the whole lenght of the wiring (see 1 ) if a Hall-Effect transmitter
(6320S*207**) is used (see page 9).
- The earth MAY NOT be connected to the shield of the cable (see 1 and 2 )
- If there is a difference between the sensor reading and the receiver display, it is possible to adjust the reading
6/20 on the display of the CSU (see page 12).
3.4 USB and RS485 outputs
Both USB or RS485 outputs are to be used for a permanent
communication with the CSU receiver. Up to 32 receivers can be
monitored on same communication line. A maximum distance of 300
meters for RS485 output should be observed.
AB
1 :B 6 : nw
2 :A 7 : nw
3 : nw 8 : nw
4 : nw 9 : nw
5 : nw nw = not wired
If the 4-20mA output is enabled in the receiver settings, the display flashes to indicate a fault in the current
loop:
- either the output is not connected
- or a display is faulty
- or there is a break in the current loop.
Shielded Shielded
Shielded
A A A
Ammeter Ammeter Ammeter
n°: 1 n°: 2 n°: X
The total resistance may not exceed 750 Ohms.
7/20
3.6 Connection to a Voltage-divider Transmitter
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
N L
100-240Vac 24Vdc Level 1 Level 2 Level 3 Level 4
88 %
50/60Hz 4W
P
CSU-3
V
Control Sensor USB RS485 4-20mA
C F E Sh S Sh A B Sh Sh
Shielded
Shielded
Shielded
Shielded
Total line lenght between Switch
and receiver MAXIMUM « 300m »
P1
P2 C
P3
MAXIMUM lenght « 3m »
USB 2.0 Type AB
LiYCY-OB 3x0.75² (DIN47100)
Connected to earth
MAXIMUM « 300m »
RS-485
output
6323S*0070*
100
80
60
Junction box 40
20
4-20mA
Shielded Shielded
4-20mA
« PASSIVE display »
ALWAYS break
the shielded line !
8/20
3.7 Connection to a Hall-Effect Transmitter
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
N L
100-240Vac 24Vdc Level 1 Level 2 Level 3 Level 4
88 %
50/60Hz 4W
P
CSU-3
V
Control Sensor USB RS485 4-20mA
C F E Sh S Sh A B Sh Sh
Shielded
Shielded
Shielded
Total line lenght between Switch
and receiver MAXIMUM « 300m »
Safety Barrier
MTL 7761ac
1 2
P1
3 4
(see page 15)
3 position
P2 C
MAXIMUM lenght « 3m »
USB 2.0 Type AB
LiYCY-OB 3x0.75² (DIN47100)
Total line lenght between
transmitter and receiver
RS-485
MAXIMUM « 300m »
50
40
60
70
output
30
80 85
20
MAX
10
90
90
E
6320S*207***
100
80
60
Junction box 40
20
4-20mA
Shielded Shielded
4-20mA
« PASSIVE display »
NEVER break
the shielded line !
9/20
CHAPTRE 4
RECEIVER SETTINGS
4.1 « ON-SITE » settings through receiver push-buttons
Before settings, technician should carefully inspect there are no damages on the receiver's enclosure; If it
would be, the receiver should be first repaired while it is disconnected from power supply, before using the
push-buttons.
The CSU receiver settings are adjusted using four pushbuttons flush with the front of the unit:
- The « P » button is used to select the Parameters.
- The « V » button is used to enter parameter Values.
- The « + » button is used to scroll up the menu or to increase the value of a parameter
- The « - » button is used to scroll down the menu or to decrease the value of a parameter.
NO
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
N L
100-240Vac Level 1 Level 2 Level 3 Level 4
88 %
50/60Hz 4W
P
CSU-3
V
Control Sensor USB RS485 4-20mA
C F E Sh S Sh A B Sh Sh
The different settings are entered using an endless menu (for details, see next page). This means that once
the end of the menu has been reached, it returns automatically to the start, and vice-versa.
You navigate through the menu using the flush « P » button and pressing the « + » and « - » buttons to scroll up
and down.
To change the value of a parameter, you navigate to the parameter to be changed. You then hold down the V
button until the display shows the value of the parameter (the value will flash to indicate it can be changed).
Continue holding the « V » button, and press the « + » and « - » buttons to increase or decrease the parameter
value.
Before making changes, always put the receiver in adjustment mode. To do so, enter value «13» for
parameter «99» and illuminating the green programming LED.
If after entry of an incorrect value the device no longer works properly, you can reinitialise all
parameters and return them ALL to their initial « status RESET » (for details see column
« RESET » on page 17). To do so, simply enter « 50 » for parameter « 99 » (RESET all values).
10/20
4.2 Setting menu - details
Parameters are displayed one after the other (10, 11, 12, 20, ... ). Once the last parameter (99) appears, the
menu returns to the start and displays the first parameter (10).
Parameters Values
10 1 1 12 Set-point 1
Set-point level [%] from 0 0 to 9 9
Min or Max logical L or h
Delay before engagement [sec.] from 0 0 to 9 9
20 2 1 22 Set-point 2
Set-point level [%] from 0 0 to 9 9
Min or Max logical L or h
Delay before engagement [sec.] from 0 0 to 9 9
30 3 1 32 Set-point 3
Set-point level [%] from 0 0 to 9 9
Min or Max logical L or h
Delay before engagement [sec.] from 0 0 to 9 9
40 4 1 42 Set-point 4
Set-point level [%] from 0 0 to 9 9
Min or Max logical L or h
Delay before engagement [sec.] from 0 0 to 9 9
50 5 1 52 Transmitter settings
Define transmitter type from 0 0 to 0 4
Lower limit [%] from 0 0 to 9 9
Upper limit [%] from 0 0 to 9 9
53 54 55 4-20mA output settings
Output activation « 4-20mA » - or O 1
« 4mA » output setting [mA] from 0 0 to 9 9
« 20mA » output setting [mA] from 0 0 to 9 9
56 Set-point operation logic
Type of logic used 0 0 , 0 1 or 0 2
60 6 1 RS485 and USB output setting
Output « RS-485 » activation - or 0 1
Output « USB » activation - or 0 1
62
Address of CSU receiver from 0 0 to 3 1
63
Programmation type (Not active) 0 0 or 0 1
7 1 72 Detection of filling movement
Level setting [%] from 0 0 to 9 9
Time setting [min.] from 0 0 to 9 9
73 74 Detection of empting movement
Level setting [%] from 0 0 to 9 9
Time setting [min.] from 0 0 to 9 9
99 MENU settings from 0 0 to 9 9
1 3 Modification authorisation code
50 Parameter RESET (factory settings)
11/20
4.3 Calibrating receiver to match transmitter
The receiver input signal can be supplied by several kinds of sensors:
- a classic 5K? voltage-divider transmitter (with 2 x 330? reference resistances) in an explosion-proof
housing (6323S*0070*) (see specific documentation), for mounting on a Magnetel (series 63xx) gauge or
on a Senior gauge (series 629x or 729x).
- a 5k? , 0-10V voltage-divider transmitter in an explosion-proof housing (6323S*0071*) (see specific
documentation), for mounting on a Magnetel (series 63xx) gauge or on a Senior gauge (series 629x or
729x) .
Magnetel Transmitter
6323S5007** with
this core.
- Hall Effect transmitter “6320S*207**” (see specific documentation) for mounting on a Magnetel (series
63xx) gauge or on a Junior or Senior (series 62xx) gauge.
Non-significant values :
Finally, it is possible to define non-significant values for a transmitter type. This derives from the fact that the
gauges have limit stops (their operating angles are different from those of the transmitters). It is therefore
interesting to indicate when these stops have been reached.If one of these values is reached, the receiver
displays « LL » for low overshoot values and « HH » for high overshoot values.To indicate to the receiver the
type of transmitter it is communicating with: Modify the value of parameter « 50 » as shown in the table below.
Parameter 50
Value Transmitter Type Non-ssignificant value
LL HH
00 no transmitter defined (factory setting)
01 Voltage-divider transmitter with « 3-97% » dial £
2% ³
98%
02 Voltage-divider transmitter with « 5-95% » dial £
4% ³
96%
03 « Hall Effect » transmitter with « 10-90% » dial £
7% ³
93%
04 « Hall Effect » transmitter with « 10-90% » dial and Safety Barrier £
7% ³
93%
12/20
4.4 Setting « 4-20mA » output
The 4-20 mA output needs to be calibrated to suit the measuring circuit loop.
The receiver is pre-set at the factory and simply needs to be adjusted (if necessary).
To do so, first connect an ammeter (Direct Current) directly to the 4-20mA output on the receiver (you could
also use a multimeter set to « mAdc », for example).
First, navigate to parameter « 53 » in the menu and intorduce the value « 01 » for activate the 4-20mA output.
Then navigate to parameter « 54 » in the menu. Press the « V » button; the receiver sends an output signal to
the current loop. If the ammeter does not indicate 4mA, adjust the current using the « + » and « - » buttons
(while pressing the « V » button) until the ammeter indicates 4.00mA. Repeat the procedure with parameter «
55 » until the ammeter indicates 20.00 mA.
Note: The values of parameters 54 and 55 do not represent the output current but
are simply an indication of the level in the available settings range.There is no
direct correspondence between « % » and « mA».
Finally, replace the ammeter by the measuring circuit loop and check that the displays are showing the correct
value. If this is not the case, reset parameters 54 and 55, but this time using the measuring circuit loop. You
can connect the ammeter used to calibrate the 4-20mA output to the current loop to check whether the error is
coming from the line load or from one or more ammeters connected to the current loop.
NOTE:
- Measure the current loop because this should not exceed 750W .
- If the unit is RESET, parameter « 53 » receives the value « - », which blocks the 4-20mA output. It is then
necessary to reset the output as explained above.
For systems needing a pump and/or valve control, the CSU receiver also allows you to change up to four set-
points using potential-free change-over relays, but with a maximum limit of 250Vac or 30Vdc / 3A per output. It
is possible to define the type of set-point (Min. or Max.) independently for each relay. You can also define a
different trip delay for each of the output relays. The different functions of the set-points are adjustable on site
and when processing. Note, however, that changing the status of a relay may affect the operation of a device
attached to its change-over contact.
EXAMPLE : 8 sec. £
T 8 sec. > T
{
{
Delay
Set-point with
positive logic
These values can, of course, be changed. To do so, proceed in the same way as explained earlier and
referring to the table above where P=parameter and V=value.
13/20
It is possible to define a logic type (parameter: 56) for the operation of all set-points.
- Negative Logic without HS and F error relays code management (value: 00)
The LED comes onbut the relay is powered when the set-point is reached.
- Positive Logic (value: 01)
The LED comes onbut the relay is not powered when the set-point is reached.
- Negative Logic (value: 02)
The LED goes out and the relay is powered when the set-point is reached.
Negative Logic
Positive Logic(01) Negative Logic (02)
without HS and F (00)
Power supply Lvel in the tank (N) Type L Type H Type L Type H Type L Type H
Relay Led Relay Led Relay Led Relay Led Relay Led Relay Led
ON « LL » empty C-NO 2 C-NC 0 C-NC 2 C-NO 0 C-NO 2 C-NC 0
ERROR CODE
ON « HH » full C-NC 0 C-NO 2 C-NO 0 C-NC 2 C-NC 0 C-NO 2
ON « HS » error C-NO 0 C-NO 0 C-NC 2 C-NC 2 C-NO 2 C-NO 2
ON « F » Failure C-NO 0 C-NO 0 C-NC 2 C-NC 2 C-NO 2 C-NO 2
CSU CSU
2 1
R1
TX-
TX+
CSU CSU
32 3
R2
R1 & R2 = 470W
/ 0.6W MRS25 type or same
There are not settings required for the RS485 output, it just needs to be activated while setting parameter “60”
with value “01” (factory set) and setting the address value for the receiver (between 00 & 31) into parameter
“62”.
CAUTION:
-The address value set (parameter 62) for the receiver will be identical for RS485 and USB outputs.
-The following informations define the communication protocol for the CSU 3 receiver, which is valid for
both RS485 and USB outputs.
14/20
4.7 RS-485/USB communication protocol
SIGNAL CARACTERISTICS :
- No Loopback
- Baudrate : 19.200 bauds
- No parity
- 8 bits
- 1 stopbit
Example:
CHKSUM1 = [START=2] [NBR BYTE=12] [ADR1=0] [ADR2=0] [ADR3=0] [ADR4=0] [CMDH=128] [CMDL=146] ...
CHKSUM1 = (2+12+0+0+0+0+128+146) modulo 256 = 288 modulo 256 = 32
ADR1/ADR2/ADR3/ADR4
[00] [00] [00] [Adresse] avec Adresse (0=>16)
Answer: [02h] [NBR BYTE] [ADR1] [ADR2] [ADR3] [ADR4] [80h] [D2h] [CHKSUM1] [n * EXTRA BYTE...] [CHKSUM2] [STOP]
[n * EXTRA BYTE...] = [0BD-00.00.01] – Version software
Measures
CMDH: CMD_DIRECT(80) / CMDL: COMMANDEREQUEST (009 / 09h)
Call: [02h] [NBR BYTE] [ADR1] [ADR2] [ADR3] [ADR4] [80h] [D2h] [CHKSUM1] [00] [CHKSUM2] [STOP]
Answer: [02h] [NBR BYTE] [ADR1] [ADR2] [ADR3] [ADR4] [80h] [D2h] [CHKSUM1] [n * EXTRA BYTE...] [CHKSUM2] [STOP]
[n * EXTRA BYTE...] = [[Project Name][-][Version soft 8bytes][Tank Level%][Relay][Led][Alarms][Level1][Logic1][Delay1][Level2]
[Logic2][Delay2][Level3][Logic3][Delay3][Level4][Logic4][Delay4][Name 10bytes][Comment 20bytes]]
00 Level 1 1 0 99
01 logic 1 1 0 1
02 Delay 1 1 0 99
03 Level 2 1 0 99
04 Logic 2 1 0 1
05 Delay 2 1 0 99
06 Level 3 1 0 99
07 logic 3 1 0 1
08 Delay 3 1 0 99
09 Level 4 1 0 99
10 logic 4 1 0 1
11 Delay 4 1 0 99
12 Trans Type 1 0 4
13 Trans setting Low 1 0 99
14 Trans setting High 1 0 99
15 4-20mA - On/Off 1 0 1
16 Setting 4mA 1 0 99
17 Setting 20mA 1 0 99
18 Logic 1 0 2
19 RS485 On/Off 1 0 1
20 USB On/Off 1 0 1
21 Adress 1 0 16
22 Protocol 1 0 0
23 Filling Level 1 0 99
24 Filling Time 1 0 99
25 Emptying Level 1 0 99
26 Emptying Time 1 0 99
27 Name 10 0 255
28 Comment 20 0 255
29 Version soft 8 0 255
15/20
4.8 Setting the detection « motion gauge »
The receiver includes a mechanical detector for
gauge level movement and/or for the transmitter. A
mechanical fault is indicated by displaying « F » on P1 = Emptying check
the receiver screen and switching the four relays, P2 = No check
contact between « C» and « NO». P3 = Filling check
This function can be activated when filling or
emptying the tank by causing a short-circuit 3 positions C
between terminals « C » and « F » (position P3) for rotary
filling and terminals « C and E » (position P1) for switch
emptying. P1 P3
P2
If there is no short-circuit (position P2), the receiver
will not carry out a check.
The receiver goes to default mode when a short-circuit happens between the three terminals « C, F et E ».
The receiver checks the filling and/or emptying time in order to detect any mechanical blockage of the sensor
or the float gauge on which the sensor is mounted.
It is necessary first to define the time (expressed in minutes) needed for the volume to vary by a certain
amount (expressed in %). This applies also to filling and emptying.
The times and volumes must be expressed in units without decimal points.
Finally, it is necessary to enter (two or four) values in the CSU receiver software.
Procedure :
When filling:
- Turn the rotary switch to P3 (or introduce a short-circuit between C and F)
- Proceed to physical tank filling.
- The receiver calculates the time (specified in parameter 72) necessary for the volume to increase by a
certain percentage (specified in parameter 71). If the predefined volume (P71) is not reached in the
predefined time (P72), the receiver considers that the conditions have not been met and indicates this by
displaying « F », flashing the four red level LEDs and switching the four relays to the default position, see
page 14 (the short-circuit between C and F must be eliminated so the CSU receiver can return to normal
operation).
- Once filling is complete, turn the switch to P2 (or short-circuit C-F).
In our example, (see green box above), P71 = 03 (3 %) and P72 = 01 (1 minute). In this case, the receiver
checks whether the volume transmitted by the sensor in 1 minute has well changed by a minimum 3%. If it
has not, the receiver considers that the conditions have not been met, displays « F », flashes the four red
level LEDs and switched the four relays, see page 14.
When emptying:
- Turn the rotary switch to P1 (or introduce a short-circuit between C and E).
- Proceed to physical tank emptying.
- The receiver calculates the time (specified in parameter 74) necessary for the volume to decrease by a
certain percentage (specified in parameter 73). If the predefined volume (P73) is not reached in the
predefined time (P74), the receiver considers that the conditions have not been met and indicates this by
displaying « F », flashing the four red level LEDs and switching the four relays to the default position, see
page 14 (the short-circuit between C and E must be eliminated so the CSU receiver can return to normal
operation).
- Once emptying is complete, turn the switch to P2 (or short-circuit C-E).
16/20
PROGRAMMING DATA SHEET
Paramters Values
RESET RGI CUSTOMER
10 1 1 12 Set-point 1
Set-point level [%] 85
Min or Max logical H
Delay before engagement [sec.] 00
20 2 1 22 Set-point 2
Set-point level [%] 80
Min or Max logical H
Delay before engagement [sec.] 00
30 3 1 32 Set-point 3
Set-point level [%] 15
Min or Max logical L
Delay before engagement [sec.] 00
40 4 1 42 Set-point 4
Set-point level [%] 10
Min or Max logical L
Delay before engagement [sec.] 00
50 5 1 52 Transmitter settings
Define transmitter type 00
Lower limit [%]
Upper limit [%]
53 54 55 4-20mA output settings
Output activation « 4-20mA » -
« 4mA » output setting [mA] 50
« 20mA » output setting [mA] 17
56 Set-point operation logic
Type of logic used 01
60 6 1 RS485 and USB output setting
Output « RS-485 » activation -
Output « USB » activation -
62
Address of CSU receiver 00
63
Programmation type (Not active) 00 00 00 00
7 1 72 Detection of filling movement
Level setting [%] 00
Time setting [min.] 00
73 74 Detection of empting movement
Level setting [%] 00
Time setting [min.] 00
99 MENU settings
BATCH N°
__.___
Temperature range :
Installation and service -20°C à +80°C
Transport and storage -30°C à +80°C
Use :
Shielded connecting cables used for the transmission of signals, measuring, controls,
telephony, interphone systems and for applications in the electrical industry.
LiYCY-OB standards :
Manufactured in accordance with standards VDE 0295, 0250, 0271, 0812, 0814, 0817.
In accordance with CEI 20-35/IEC 332.1 and CEI 20-22/IEC 332.3 Cat. C, lead-free CEI 20-52
Nominal section : 0.75mm²
Conductor diameter : 2.2mm
No. strands : 24 x 0.22 mm diameter
Cable Description :
Core : multi-strand, red copper
Insulation : coloured PVC in accordance with DIN 47100, 105°C PVC
Twisted : by layer
Assembly : by mylar sheet
Screening : tinned copper braid (90% density)
Outer sheath : RAL 7001 grey PVC, flame-retardant NPI CEI 20-22
Cable specifications :
Bending radius : 10 x cable diameter
Insulation resistance : minimum 20M? /Km
Operating voltage : 500V
Test voltage : minimum de 1.200V (1.2KV)
Mechanical properties :
Number diameter weight
of conductors extérieur
[mm²] [mm] [Kg/Km]
1 white
2 brown
3 green
4 yellow
5 grey
6 pink
Source : Valentin catalogue (0.75mm² part specification)
Legrand electrical catalogue (part standard DIN 47100)
18/20
TROUBLESHOOTING
This section covers the most often encountered faults resulting from incorrect manipulation of the receiver program or
following a connection problem.
If a fault is found, carefully check the various connections before suspecting the faulty operation of a single item. Also
check the compatibility of the different devices connected to the CSU receiver.
If no solution is found, carry out a full RESET of the receiver, then reprogram it. If the fault is still present, proceed as
follows:
-note down the serial number of the receiver and transmitter
- note down all the different devices connected to the receiver
- describe the fault as closely as possible
- provide your supplier with this information. This will permit him to assist you as quickly as possible.
The transmitter is defective. Replace the transmitter with a new one or exchange it
for another that is working correctly.
The receiver display works but The current loop is broken. Check all the connection points in the measurement
flashes. loop as well as the ammeter(s).
The current loop is not connected to the Check that parameter « 53 » is set to « - ». If it is not,
receiver. note all the values, RESET the receiver (see page 10)
and reprogram it or insert a bridge between the + and –
terminals.
The receiver display shows One of the movement detection functions is Either deactivate these functions by entering «00» in
« F ». active. parameters « 71 » to « 74 », or check for short-circuits
between terminals « C », « F » and/or « E » (see page
15).
The receiver display works but The receiver has not been calibrated to suit its Calibrate the receiver as shown on page 12.
does not show the same values transmitter (line resistances, safety barriers,
as the transmitter. etc.).
The 4-20mA output works but The receiver has not been calibrated to suit the Calibrate the receiver as shown on page 13.
does not indicate the same current loop (line resistances, ammeter internal
values as the receiver display. resistance, etc.).
The 4-20mA output on the A mistake during calibration of the Note all the values and RESET the receiver (see page
received indicates a constant measurement loop has caused the adjustment 10).
value. range to be exceeded. Re-enter all parameters except for « 54 » and « 55 ».
Calibrate the receiver as explained on page 13.
The 4-20mA output on the The 4-20mA output is shorted. Check for a short-circuit.
receiver indicates 0mA.
The 4-20mA output on the The 4-20mA output is not active. Check that parameter «53» is not set to «-». If it is,
receiver indicates ~3mA. calibrate the receiver as shown on page 13.
The 4-20mA output on the The 4-20mA loop is open. Check for a open-circuit
receiver indicates 0mA and the
display is flashing.
19/20
CONFORMITY DECLARATION
Wavre, September 2014
6370S*0001*
Housing Type E IP-20 for mounting on 35mm DIN rail
PIERRE Lionel
Managing Director
20/20