Professional Documents
Culture Documents
Eurotherm 2132i 2116i Alarm Units Manual HA026248
Eurotherm 2132i 2116i Alarm Units Manual HA026248
Eurotherm 2132i 2116i Alarm Units Manual HA026248
24mm OP1
OP2 22.2
-0.0 +0.3 3. Spring the panel retaining clips into place. Secure the
(0.95in) -0.0 +0.6
x 45 indicator in position by holding it level and pushing both
retaining clips forward.
Inch 4. Peel off the protective cover from the display
Latching ears Panel retaining clips -0.0 +0.1
0.88
-0.0 +0.02
x1.77 Unplugging the indicator
The indicator can be unplugged from its sleeve by easing the
latching ears outwards and pulling it forward out of the sleeve.
When plugging the indicator back into its sleeve, ensure that the
Model 2116i
latching ears click into place to maintain the IP65 sealing.
48mm (1.89in) 103mm (4.01in)
Recommended minimum
Panel cut-out spacing of indicators in
2216
both sizes
OP1
45 x 45mm
48mm
(1.89in)
OP2
SP2
REM
D -0.0 +0.6
10mm 38mm
1.77 x 1.77in
MAN
RUN
HOLD
-0.00 +0.02 (0.4in) (1.5in)
(Not to
Latching ears Panel retaining clips
scale)
- +
Sensor input Output ratings
V- V+ AB AA N L Relay: 2A, 264Vac resistive
20-29Vac/dc Logic: 9Vdc, 12mA (non-isolated from sensor input).
T/C Relay*
Output 24 24 Over current protection
Pt100 Neutral Use a maximum 2A fuse for the indicator supply and relay output.
Line Low voltage supply
A suitable fuse is EN60127 (type T).
mA 85-264Vac
2.49Ω Wire Sizes
The screw terminals accept wire sizes from 0.5 to 1.5 mm (16 to 22
AWG). Hinged covers prevent hands or metal making accidental
*Not fitted in indicator only units. Also terminals 1A and contact with live wires. The rear terminals screws should be
1B not fitted in indicator only unit. tightened to 0.4Nm (3.5lb in).
Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -1- HA026248
OPERATION TO VIEW THE DISPLAY UNITS
Switch on the indicator. Following a 3 second self-test sequence, Press and release quickly the or button. The display units
you will see the display shown below. It is called the HOME will be flashed for 0.5sec
display.
0.5 sec Display Units
J J
Degrees Centigrade
Output 1 OP1 J Degrees Fahrenheit
Output 2
OP2
The process value (PV)*
J' Kelvin
Linear inputs - no units displayed
* See HOME display options for
other possibilities
or
ALARM INDICATION If you get lost, pressing and together will return you to
the HOME display.
The indicator has three internal ‘soft’ alarm setpoints which can be
If, at any time, no key is pressed within 45 seconds, the display
attached to either the logic or relay outputs.
will always return to the HOME display.
OP1 will flash when an alarm attached to the logic output becomes
true. (This is normally alarm 1). It will go steady when the alarm HOME DISPLAY OPTIONS
is acknowledged but still true. Press or to select:
Quickly press twice
OP2 will flash when an alarm attached to the relay output becomes 6 Not used by indicator
true. (This is normally alarm 2 or 3). It will go steady when the 2 secs
0 Not used by indicator. (Only
alarm is acknowledged but still true. applies to software version 1.4)
Process Alarms
TO CHANGE THE ALARM SETPOINTS (TRIP LEVELS)
Message Meaning The button steps through parameter list headings. The first list
) Alarm 1 is active and it is a Low alarm. is the alarm setpoints. The other lists are shown on the next page.
# Alarm 1 is active and it is a High alarm. Pressing or displays )O6
) Alarm 2 is active and it is a Low alarm. 0.5 sec to indicate that this a list heading
2 secs
# Alarm 2 is active and it is a High alarm.
)O6
) Alarm 3 is active and it is a Low alarm.
J
D5 Sensor Break: Input sensor is open circuit or high
2nd ) Next list
resistance. Check the sensor. press
In addition to the above messages, the displayed process value will 1st
press
Press
flash if the input signal or the displayed value is out of range.
The table above shows normal process alarms. In the event of a There are three
failure in the indicator or the sensor the following diagnostic alarm alarm setpoints.
messages are provided. The first character Alarm 1 BBB Press or to
Diagnostic alarms is the alarm
change the setpoint.
Message Meaning and (Action)
setpoint number,
the next three the
D5 Electrically Erasable Memory Error:
alarm type, as
A parameter value has been corrupted.
Contact Eurotherm Controls. follows:
#<D5 Hardware error: ( Return for repair) B) Low alarm Alarm 2
BBB
)))) Low display range exceeded: (Check input signal)
B# High alarm Press or to
change the setpoint.
#### High display range exceeded: (Check input signal) If an alarm has
55 Error 1: ROM self-test fail. (Return for repair) been disabled, it
55
Error 2: RAM self-test fail. (Return for repair) will not appear in
55
Error 3: Watchdog fail. (Return for repair) this list.
Alarm 3
)
55 Error 4: Keyboard failure. Stuck button, or a button Press or to
was pressed during power up. change the setpoint.
55 Error 5: Input circuit failure. (Return for repair) Press and together to return
0=5D Power failure. The line voltage is too low. to the HOME display.
Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -2- HA026248
PARAMETER LISTS TO HIDE PARAMETERS OR MAKE THEM READ-ONLY
Use these lists to change: • The alarm setpoints •The alarm setpoint
limits •User calibration.
Press to reach the Access List Heading.
HOME Alarm Setpoint Input Access
List
X2
List List List List Press
) 0 O1 Press or to enter the password.
0 The factory default is 1. 0 will be
X2 displayed when the correct password
/ has been entered.
O0 BBB 1 ) O)6 /
to select O6 level.
BBB 0 # %J !/6/ Press Use or
Other options are:
) ,; O6 05 For Operator level
9)) Shows the ‘Full’ set of
#@ !/6/ available parameters
/. Gives access to
)D0 configuration level.
Selecting and adjusting a parameter ) Press to return to the Access list header.
1. Press to step across the list
headings. 0.6D) You are now in Edit level. Press and
2. Press to step down the
parameters within a particular list.
D) to select a parameter in the normal way.
You will eventually return to the list 0.6D# Example: High alarm 2 has been selected.
heading. #O When or is pressed, instead of
Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -3- HA026248
CONFIGURING THE INDICATOR Linear input scaling (-12.00 to +80.00mV)
Select configuration level to change: •The display units •The N.0D) mV input low Displayed value
input sensor type •The scaling of linear inputs •The alarm N.0D# mV input high ;)D#
configuration • The passwords.
;)D) Displayed value low
To select configuration level ;)D# Displayed value high ;)D) mV
N.1D) N.1D#
Press to reach the Access List Heading.
Alarm Configuration
Press The ) list configures the three internal ‘soft’ alarms and causes
the appropriate alarm message to be flashed in the HOME display.
Use or to enter the password.
/0 The factory default is 1. 0 will be ) Alarm list Options Meaning
displayed when the correct password ) Alarm 1 The alarm is disabled
has been entered. ) Low alarm
Press # High alarm
Not used : Deviation band alarm
Use to select /. #O
!/6//.
or in the Deviation high alarm
indicator )/ Deviation low alarm
)6$ Alarm latching ./ Non-latching
Press @ Special - Not used
Use or to enter the configuration ,. Latched (manual reset)
level password. The factory default is 2.
/.0 0 will be displayed when the )/ Alarm blocking ./ No blocking
@ Blocked until first good
correct password has been entered.
The above sequence is repeated for )
& )
(Alarms 2 & 3)
Press to enter configuration level.
1D)O Alarm setpoint O Limited by display range
limits /. Limited by setpoint limits
Press to step across the configuration list headings.
Relay and Logic input/output Configuration
N.6 O0 ) The and lists attach the three internal alarms to the relay
and logic outputs. The logic can be configured as an alarm output
or as an alarm acknowledge input.
?O6 0 Relay output Options Meaning
Logic output
Having selected a list heading, press to select a parameter O Identity of output 5)A Relay
. within a particular list. Press and to change the setting. )/! Logic
9. Function O! Digital output
N.6 Instrument list Options Meaning Logic only D) Alarm Ack input
9.O6 Display units J Centigrade Functions: #6, ), 5D and 55 are not
J Fahrenheit used by the indicator and require separate instructions
J' Kelvin
O!D Digital output functions ./$ No change
./. None (for linear inputs) Any combination of alarms )5 Clear all
D0 Decimal places .... None can be attached to the logic or alarms
in display ...D. One
relay output. Press and DD) Alarm 1*
..D.. Two
DD# Alarm 2*
to select a desired alarms
65) Control type ) Always set to ) After a two second pause the
DD) Alarm 3*
Selecting .D or 0O will convert the indicator into a display blinks and returns to DD5 Sensor
controller which requires separate instructions. O!D. Pressing and break
The parameters that follow, (6, 0D65 and 0=5), are not used again will show two decimal
by the indicator and require separate instructions. points in those alarms that .= New alarm
have been added to the output
Functions: )5, ), ,., ., & 6,! , to 6," are
not used by the indicator and need separate instructions
O0 Sensor Input Options Meaning
. Sense of the output. ./5 Normal
O.06 Input type &D6 J thermocouple O.: = output de-energised in N.: Inverted
(D6 K thermocouple alarm.
)D6 L thermocouple *The last three letters will correspond to the alarm type set in the )
5D6 R thermocouple list. If the alarm is disabled, ) or )
or )
will be shown.
D6 B thermocouple
.D6 N thermocouple
Passwords
6D6 T thermocouple
D6 S thermocouple 0 Passwords Range Default
0)
Platinell II D0 Full and Edit level password B
56 100Ω Pt thermometer .D0 Configuration level password B
Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -4- HA026248
ORDERING CODE
The indicator is supplied configured according to the ordering code shown below.
Model Function Supply Manual Logic Alarm Sensor Setpoint Setpoint Units External Input
number voltage I/O Relay input min max relay adaptor
Output module
2132i
2116i
Function
ND Indicator only*
Input Adaptor
AL Indicating alarm
Sensor input Display range and XX None
unit
Setpoint min & max limits V1 0-10Vdc
Supply voltage Thermocouples °C °F A1 0-20mA sense
VH 85-264Vac J Type J -210 to 1200 -340 to 2192 resistor (2.49Ω.
VL 20 -29V dc or ac K Type K -200 to 1372 -325 to 2500 0.1%)
T Type T -200 to 400 -325 to 750
L Type L -200 to 900 -325 to 1650 External relay module
Manual
N Type N -200 to 1300 -325 to 2370 XX Not fitted
XXX None
R Type R -50 to 1768 -58 to 3200 R7 Fitted (Operated
ENG English
S Type S -50 to 1768 -58 to 3200 by the logic
FRA French
B Type B 0 to 1820 32 to 3308 output)
GER German
P Platinell II 0 to 1369 32 to 2496
NED Dutch
Resistance thermometer Units
SPA Spanish
Z Pt100 -200 to 850 -325 to 1562 C °C
SWE Swedish
Custom downloaded inputs F °F
ITA Italian
C Type C -W5%Re/W26%Re 0 to 2319 32 to 4200 K Kelvin
(default custom sensor) X Linear input
Logic I/O D Type D - W3%Re/W25%Re 0 to 2399 32 to 4350
XX Disabled* E E thermocouple -200 to 999 -325 to 1830
Logic input Alarm Relay Output 1 Ni/Ni18%Mo 0 to 1399 32 to 2550
AC Alarm ack/reset XX Disabled* 2 Pt20%Rh/Pt40%Rh 0 to 1870 32 to 3398
KL Keylock Non-latched alarms 3 W/W26%Re (Engelhard) 0 to 2000 32 to 3632 *If ‘ND’ (Indicator only) is
Non-latched alarms FH High alarm 2 4 W/W26%Re (Hoskins) 0 to 2010 32 to 3650 specified in the function field,
FH High alarm 1 FL Low alarm 2 5 W5%Re/W26%Re (Engelhard) 10 to 2300 50 to 4172 then XX must be entered in
FL Low alarm 1 AL High alarm 2 & 6 W5%Re/W26%Re(Bucose) 0 to 2000 32 to 3632
Latched alarms the Logic I/O and alarm 2
low alarm 3 7 Pt10%Rh/Pt40%/Rh 200 to 1800 392 to 3272
HA High alarm 1 Latched alarms
relay fields.
8 Exergen K80 I.R. Pyrometer -45 to 650 -49 to 1202
LA Low alarm 1 HA High alarm 2 Process inputs (linear)
NW New alarm LA Low alarm 2 M -9.99 to +80mV Scalable -999 to 9999
AA High alarm 2 & Y 0 to 20mA Scalable -999 to 9999
low alarm 3 A 4 to 20mA Scalable -999 to 9999
NW New alarm V 0 to 10Vdc (input adapter required) Scalable -999 to 9999
TECHNICAL SPECIFICATION
Display 4 digit, green. 10mm high characters
Supply voltage High voltage unit: 100Vac -15% to 240Vac +10%, 48-62Hz. Power consumption: 5Watts maximum
Low voltage unit: 24Vdc or ac -15%, +20% DC to 62Hz, Power consumption: 5Watts maximum
o
Operating ambients 0 to 55 C. 5 to 95%RH, non condensing
o o
Storage temperature -30 C to +75 C.
Output ratings Relay(isolated): Maximum: 264Vac, 2A resistive. Minimum: 12Vdc, 100mA
Logic I/O: 9Vdc at 18mA (non-isolated from sensor input). Can be used as alarm output or alarm acknowledge
input
± 1 C or ±0.25% of reading whichever is greater
o
Calibration accuracy
TM
Cold junction compensation >30 to 1 rejection of ambient temperature change. Uses INSTANT ACCURACY cold junction sensing
technology to eliminate warm-up drift and respond rapidly to ambient temperature changes.
Input filtering Off to 999.9 seconds
EMC standards Generic emissions standard EN50081-2 and immunity standard EN50082-2 for industrial environments
Safety standard EN 61010. Installation category II. (Voltage transients on the power supply must not exceed 2.5kV). Pollution
degree 2. All isolated inputs and outputs have reinforced insulation to protect against electric shock.
Atmosphere Not suitable for use above 2000m or in explosive or corrosive atmospheres
Panel sealing IP65 (EN 60529), or NEMA 4X
Issue 3, Nov-98. Applies to software versions 1.3 & 1.4 -6- HA026248