The cable passed all tests according to the required standards. It is a 1x120 sq mm black BYA cable for Robi Axiata Ltd with a 450/750V voltage grade. Physical tests found the cable had a 120 sq mm copper conductor and over 16 mm diameter as required. Electrical tests found resistance and insulation values within limits and it withstood a 3kV voltage test. Mechanical tests found tensile and elongation values exceeded minimums before and after ageing. A flame test found propagation was over 50 mm as required.
The cable passed all tests according to the required standards. It is a 1x120 sq mm black BYA cable for Robi Axiata Ltd with a 450/750V voltage grade. Physical tests found the cable had a 120 sq mm copper conductor and over 16 mm diameter as required. Electrical tests found resistance and insulation values within limits and it withstood a 3kV voltage test. Mechanical tests found tensile and elongation values exceeded minimums before and after ageing. A flame test found propagation was over 50 mm as required.
The cable passed all tests according to the required standards. It is a 1x120 sq mm black BYA cable for Robi Axiata Ltd with a 450/750V voltage grade. Physical tests found the cable had a 120 sq mm copper conductor and over 16 mm diameter as required. Electrical tests found resistance and insulation values within limits and it withstood a 3kV voltage test. Mechanical tests found tensile and elongation values exceeded minimums before and after ageing. A flame test found propagation was over 50 mm as required.
Standard as per : BS 6004 & BDS 900 Date : 17.04.2018
Size of Cable : 1x120 RM (sq.mm) Colour : Black Type of Cable : BYA Party : Robi Axiata Ltd. Voltage Grade : 450/750 V Sl. Description of test Unit Required Observed No. Value Value 01 Physical Nominal Cross-sectional Area of Conductor mm2 120 120 Test Number of core no. 1 1 Conductor Material Copper Copper Circular Stranded Circular Stranded Shape of conductor Compacted Compacted Minimum Number of wire no. 18 37 Min. & Max. Diameter mm 12.3-13.5 13.07 Insulation Material - PVC PVC Nominal thickness mm 1.6 1.64 Minimum thickness mm 1.34 1.59 Approximate overall diameter mm 15.5-16.7 16.35 02 Electrical Max. D.C. Resistance of conductor at 20 oC Ω/km 0.153 0.124 Test Min. Insulation resistance constant ki at 20 0 C M.ohm-km 36.7 125.42 A.C. Voltage Test kV 3.0 Withstood 03 Mechanical Before ageing Test Tensile Strength of Insulation, minimum N/mm2 12.5 15.73 Elongation of Insulation, minimum % 125 272 04 Flame Test Flame propagation of a single cable a. The test if the distance between the lower edge of the top support and the onset of charging is mm 48 385.0 greater than 50mm
Remerks: The above test results are found Passed.
Tested by- Checked by-