Observations in substation/PCA bldg

Actuator installed for HVAC ducts on roof top of Substation BLDG & PCA bldg for outdoor Nema IP Rating is IP 40.
Observations in substation/PCA bldg

PVC conduits for Grounding cables laid on roof top without supports and clamps
Observations in substation/PCA bldg

In cable cellar room no distance maintain between for AC & DC cables.


Observations in substation/PCA bldg

480 Volt Power cable for EMCC Panel nstalled in control cable tray.
Observations in substation/PCA bldg

Small Power tx’s directly glanded Into FRP Insualtion of transformer body without gland plate body. It
should be typical with gland plate installed for all other transformers.

UPS batteries cable length more then 3 meters without support & cable touching to the ground and
sharp edges of cable trays for tag no: 40-UBT-4001B