Analysis of Coupled Shear Wall Under the Effect of

Wind Load: A Simpli ed Solved Example


By Civilax - September 30, 2017

I Introduction
The effect of wind becomes more influential as a building gets taller. To effectively resist the force from wind,
shear walls, frames, or the combination of both structural forms are normally employed in tall buildings.
When shear walls have openings (pierced) which may serve for aesthetic, lighting or ventilation purposes,
the behaviour of the shear wall is coupled to some degree. This post explores the wind load analysis of
coupled shear wall structures with a fully solved example, under the following assumptions;

(i) The entire wind load is transferred to the shear walls (the contribution of the frames have been neglected)
(ii) The wind load acts as a uniformly distributed force of F/H

The two main parameters which defines the behaviour of pierced shear walls are alpha(α) and beta (β),
which depend on the geometrical properties of the coupling/connecting media (beams or floor slabs) and the
shear wall. For fairly symmetrical arrangements as shown below, the following relationships given below can
be used for the purpose of analysis.

N/B: This is a curtailed information; kindly consult specialist textbooks/publications for full knowledge of the
subject.
The value of Kv can be obtained from the table below;

II Solved Example
The structural arrangement of a tall building is as shown below. The building is 90m tall, with 30 storeys
@3m storey height. We are to determine the internal forces induced in the shear walls due to the wind load.
Data:
Height of building (H) = 90m
Storey height (h) = 3m
Thickness of shear wall (t) = 0.35m
Depth of connecting beam (d) = 900mm
Width of opening (b) = 2500mm
Centreline of connected walls (L) = 8000mm
Basic wind speed = 40 m/s

III Wind Load Analysis (Eurocode 1 Part 4)

(a) Basic wind velocity


The fundamental value of the basic wind velocity Vb,0 is the characteristic 10 minute mean wind velocity
irrespective of wind direction and time of the year, at 10 m above ground level in open-country terrain with
low vegetation such as grass, and with isolated obstacles with separations of at least 20 obstacle heights.

The basic wind velocity Vb,0 is calculated from;

Vb = Cdir .Cseason .Vb,0


Where:
Vb is the basic wind velocity defined as a function of wind direction and time of the year at 10m above the
ground of terrain category II
Vb,0 is the fundamental value of the basic wind velocity
Cdir is the directional factor (defined in the National Annex, but recommended value is 1.0)
Cseason is the season factor (defined in the National Annex, but recommended value is 1.0)

For the area and location of the building that we are considering;

Basic wind velocity Vb,0 = 40 m/s


Vb = Cdir .Cseason . Vb,0 = 1.0 × 1.0 × 40 = 40 m/s

(b) Mean Wind


The mean wind velocity Vm(z) at a height z above the terrain depends on the terrain roughness and
orography, and on the basic wind velocity, Vb, and should be determined using the expression below;

Vm(z) = cr(z). co(z).Vb

Where;
cr(z) is the roughness factor (defined below)
co(z) is the orography factor often taken as 1.0

The terrain roughness factor accounts for the variability of the mean wind velocity at the site of the structure
due to the height above the ground level and the ground roughness of the terrain upwind of the structure in
the wind direction considered. Terrain categories and parameters are shown in the table below;
cr(z) = kr. In (z/z0) for zmin ≤ z ≤ zmax
cr(z) = cr.(zmin) for z ≤ zmin

Where:
Z0 is the roughness length
Kr is the terrain factor depending on the roughness length Z0 calculated using
Kr = 0.19 (Z0/Z0,II )0.07
Where:
Z0,II = 0.05m (terrain category II)
Zmin is the minimum height
Zmax is to be taken as 200 m
Kr = 0.19 (0.05/0.05)0.07 = 0.19
cr(z) = kr. In (z/z0) = 0.19 × In(90/0.05) = 1.424

Therefore;
Vm(90) = cr(z).co(z).Vb = 1.424 × 1.0 × 40 = 56.96 m/s

(c) Wind turbulence


The turbulence intensity Iv(z) at height z is defined as the standard deviation of the turbulence divided by the
mean wind velocity. The recommended rules for the determination of Iv(z) are given in the expressions
below;

Iv(z) = σv/Vm = k1/(c0(z).In(z/z0)) for zmin ≤ z ≤ zmax

Iv(z) = Iv.(zmin) for z ≤ zmin

Where:
kI is the turbulence factor of which the value is provided in the National Annex but the recommended value is
1.0
Co is the orography factor described above
Z0 is the roughness length described above.
For the building that we are considering, the wind turbulence factor at 90m above the ground level;

Iv(90) = σv/Vm = k1 / (c0 (z).In (z/z0)) = 1/(1 × In(90/0.05) ) = 0.1334


(d) Peak Velocity Pressure
The peak velocity pressure qp(z) at height z is given by the expression below;

qp(z) = [1 + 7Iv(z)] 0.5.ρ.Vm2(z)= ce(z).qb

Where:
ρ is the air density, which depends on the altitude, temperature, and barometric pressure to be expected in
the region during wind storms (recommended value is 1.25kg/m3)

ce(z) is the exposure factor given by;


ce(z)= (qp(z))/qb
qb is the basic velocity pressure given by;
qb = 1/2.ρ.Vb2

qp(90m) = [1 + 7(0.1334)] × 1/2 × 1.25 × 56.962 = 3921.313 N/m2


Therefore, qp(90m) = 3.921 kN/m2

(e) Wind Pressure Coefficient

h/d = 90/22.5 = 4
Pressure coefficient for windward side (zone D) = +0.8
Pressure coefficient for leeward side (zone E) = -0.65 (from linear interpolation)

Net pressure coefficient = 0.8 - (-0.65) = 1.45

According to clause 7.2.2(2), the force generated from zone D and E simultaneously should be corrected for
lack of correlation.

Since h/d = 4 in our calculation, we have to interpolate between h/d ≥ 5(1.0) and h/d ≤ 1.0 (0.85).
On interpolating;
Correction factor = 0.9625
Therefore, net wind pressure = 0.9625 × 1.45 × 3.921 = 5.472 kN/m2

IV Structural Analysis

The wind force of the structure;


F = 5.472 KN/m2 × 24m × 90m = 11819.52 KN (taking structural factor as 1.0 because building is less than
100m tall, and h/d = 4)

If we assume that this load is shared equally among the two shear walls, then the load on each shear wall =
5909.76 KN

Geometrical Properties of Elements


Area of shear walls = A1 = A2 = 0.35 × 5.5 = 1.925 m2
Second moment of area of walls = I1 = I2 = (0.35 × 5.53)/12 = 4.852 m4
Moment of inertia of connecting beam Ib = (0.35 × 0.93)/12 = 0.02126 m4

be = (2b + 5d)/3 = [(2 × 2.5) + (5 × 0.9)] / 3 = 3.167

αH = 19.962
Therefore, the axial force (N) at the bottom of wall;

The bending moment at the bottom of the wall elements;

The shear force at the connecting beams;

The bending moment on the connecting beams;

These internal forces should be factored, and combined with other appropriate load cases for the purpose of
design.