CKT.

CIRCUIT BREAKER
DESCRIPTION PHASE VOLTS VA PER CIRCUIT CURRENT
# AT
1 230
1 LIGHTINGS 1 230 800 3.48 20
2 CONVENIENCE OUTLET 1 230 1400 6.09 20
3 POWER TOOLS 1 230 1400 6.09 20
4 POWER TOOLS 1 230 1400 6.09 20
5 SPARE 1 230 1400 6.09 20
6 SPARE 1 230 1400 6.09 20
TOTAL CONNECTED LOAD: 1 230 7800

CURRENT TOTAL = 7800/230 = 33.91*0.8 D.F


= 27.13 Amps.

FEEDER SIZE: Use: 2- 8.0 mm² + 1- 3.5 mm² THHN in 40 mm dia. ASC

MAIN DISCONNECTING MEANS: Use: 60 AT, 100 AF, 2P, 240V, 10 KAIC, BOLT-ON TYPE in NEMA 3R Enclosure
CIRCUIT BREAKER
SIZE OF WIRE
AF POLE TYPE

50 2 BOLT-ON 2-3.5 mm² THHN in 15 mm dia. pipe


50 2 BOLT-ON 2-3.5 mm² THHN in 15 mm dia. pipe
50 2 BOLT-ON 2-5.5 mm² THHN in 15 mm dia. pipe
50 2 BOLT-ON 2-5.5 mm² THHN in 15 mm dia. pipe
50 2 BOLT-ON 2-5.5 mm² THHN in 15 mm dia. pipe
50 2 BOLT-ON 2-5.5 mm² THHN in 15 mm dia. pipe

m dia. ASC

YPE in NEMA 3R Enclosure