Professional Documents
Culture Documents
Project Report On Absorption Chillers
Project Report On Absorption Chillers
Project Report On Absorption Chillers
1. PREFACE
This advanced Project guidelines have been developed to assist designers, program
energy saving measures.. There are two basic types of gas absorption chillers:
absorption systems and gas engine driven chiller systems. This project report deals
specifically with gas absorption systems. These guidelines are intended to be a step
how cost effective it is, and how its energy savings are describied. These guidelines
describe effeciency measures that are more advanced than standard practise, yet still
cost effective in all, or select markets. Design guidelines are used by individuals and
with the comparision of a single effeciency measure and its baseline. This
means that the analysis assumes that all other features of the building are
fixed. This is done primarily for clarity of the analysis, and allows one to
2. DESCRIPTION
1.1 The two basic principles on which all air conditioning and refrigeration
plants operate are:
that heat. This heat is called the latent heat of evaporation and latent heat of
condensation respectively.
The absorption cooling works on the affinity of some pairs of chemical to dissolve
in one another. For example, lithium bromide solution has affinity towards water,
water hasaffinity towards ammonia etc. this affinity depends on two factors –
evaporator. At this pressure the refrigerant boils at very low temperature. This boiling causes
the refrigerant to absorb the heat from the medium being cooled, thus lowering the
temperature. On absorbing the heat the refrigerant gets vaporized. The refrigerant vapours thus
formed tend to increase the pressure in the vessel. This will in turn increase the boiling
temperature and the desired cooling effect will not be obtained. So, it is necessary to remove
the refrigerant vapours from the vessel. A liquid having affinity towards the refrigerant
iii
vapour is sprayed in the absorber which absorbs the vapour and maintains the low pressure
in the shell. As the absorbent absorbs the refrigerant vapor, it becomes dilute & losses its
that the absorbent is enriched to its original level of concentration and the refrigerant
vapours are condensed to the liquid. This is achieved by pumping the dilute solution
continuously from absorber to the generator. In the generator the addition of heat boils off
the refrigerant from the absorbent and the absorbent regains its original level of
absorption process.The refrigerant vapour released in the generator flows to the condenser.
In the condenser cooling water is circulated through the coils, which picks up the heat
carried by the refrigerant vapour and vapour condenses back to the liquid phase. The
condensed liquid is returned back to the evaporator thus completing the absorption cycle.
with Figure 2.1. In its simplest design the absorption machine consists of
Evaporator
Condenser
Absorber
Generator
Solution pump
iv
In an absorption cycle chiller, the absorber, the solution pump and the generator in
refrigerant vapour. Vapour generated in the evaporator is absorbed into a liquid absorbent
in the absorber. The absorbent that has taken up refrigerant, spent or weak absorbent, is
pumped to the generator where the refrigerant is released as vapour. Which vapour is to be
condensed in the condenser. The regenerated or strong absorbent is then led back to the
comparatively high temperature and rejected from the absorber at a comparatively low
level, analogously to a heat engine. The words “ thermo chemical compressor” have
actually been used in specialised literature to describe the function of the generator and
Refrigerant and absorbent in an absorption cycle form what is called a working pair,
many pairs have been proposed through the years but only two of them have widely used:
ammonia together with water as absorbent and water together with a solution of lithium
bromide as absorbent. The ammonia water pair is mostly found in refrigeration applications,
with low evaporation temperatures, below 0 Deg C. the water – lithium bromide pair is widely
used for air conditioning applications, where it is not necessary to cool below 0 Deg . the
pressure levels in ammonia – water are usually above the atmospheric pressure and while the
The basic cycle illustrated in Fig1.1 may be modified in several ways. One
is to utilise all possible opportunities fro heat recovery within the cycle in order to
improve the heat economy within the cycle. For example, it is customary to heat
exchange the streams of weak absorbent leaving the absorber with the regenerated
or strong absorbent that is led back into the absorber. When all heat recovery
opportunities that can reasonably be used have been incorporated into the design of
for the water – lithium bromide system and approximately 0.6. Further
temperature heat available to power the generator. The so called double- effect
systems incorporate two generators- absorber blocks that are staged, see figure
2.2, in order to utilise the heat supplied more or less twice. Heat is supplied at
170 Deg C to the first generator and heat rejected by the corresponding
temperature 100 Deg C of a single effect machine according to Figure 2.1. The
working pair may be 1.2, which is significantly better than the C.O.P of 0.7 of
In direct –fired units, the heat sources can be gas or some other fuel that is burned
in the unit. Indirect – fired units use steam or some other transfer fluid that brings
in heat from a separate source, such as boiler or heat recovered from an industrial
process. Hybrid systems, which are relatively common with absorption chillers,
combine gas systems and electric systems for load optimisation and flexibility.
The single-effect “cycle” refers to the transfer of fluids through the four major
hot water as the heat source. The water is able to evaporate and extract heat in
the evaporator because the system is under a partial vacuum. The thermal
is sound, the low efficiency has inhibited the cost competitiveness of single –
where waste heat is readily available. Single –effect chillers can be used to
produce chilled water for air-conditioning and for cooling process water, and are
differs from the single-effect , in that there are two condensers and two
generators to allow for more refrigerant boil –off from the absorbent
solution. Figure 2.4 shows the double effect absorption cycle on a pressure –
supplied steam to boil the refrigerant from the weak absorbent. The
refrigerant vapour from the high temperature generator is condensed and the
These systems use gas fired combustors or high pressure steam as the heat
The triple-effect cycles are the next logical improvement over the double-effect.
Triple-effect absorption chillers are under development, as the next step in the
and medium temperature generators is condensed and the heat is used to provide
heat to the next lower temperature generator. The refrigerant from all three
One uses two condensers and two absorbers to achieve the triple effct. A
2.4 Efficiencies
performance(COP), which is defined as the net refrigeration effect by the net heat
input . Single – effect absorption chillers have COPs of approximately 0.6-0.8 out
of an ideal Since the COPs are less than one, the single-effect chillers are normally
used in applications that recover waste heat such as waste steam from power plants
or boilers. Double- effect absorption chillers have COPs of approximately 1.0 out
of an ideal while not yet commercially available, protype triple effect absorption
The COP metric is also applied to electric chillers. However, since COP is based
on site energy, it is not good for comparing gas and electric chiller efficiencies.
A better metric is the resource COP, which accounts for the source to site efficiency
of the fuel, accounting for electricity generation and transmission losses. Fig 2.6
shows typical values for both electric chillers and absorption chillers
Source –to-
Chiller Site COP Resource COP
site factor
Electric 2.0 – 6.1 0.27 0.54 – 1.65
Absorption 0.65 – 1.2 0.91 0.59 – 1.1
operating costs by avoiding peak electric demand charges and time of day rates. The
use of gas absorption chillers eliminates the high incremental cost of electric cooling.
Natural gas cooling systems have greater resource efficiency than similar to electric
65% - 75% loss in the initial energy resource of fuel. In contrast, only about 5% to 10%
of the fuel resource is lost with a gas system. Additionally, electricity costs per Kwh
are typically three to four times the cost per Kwh for electricity, so the cost of a unit of
Utilising waste heat that would otherwise be unused greatly increases the
cost effectiveness of the systems, compared to consuming gas directly.
xiii
2.5.1 Absorption systems have several non- energy benefits over conventional
electric systems
Since the 1960’s, several improvements have been made to absorption chiller,
which include:
Automatic purge systems eliminating the need for manual purging and
lowering the potential for corrosion.
Faster system response due to the use of electronic controls and solution
concentration sensing
Electronic controls and sensors that make crystallisation of the chiller far less
likely than in the past.
2.5.3 Limitations :
available free waste heat. Even double effect systems are non cost effective
in the right situation, their exact economics must be worked out on a project-
by-project basis.
Absorption systems also require greater pump energy than electric chillers.
The size of condenser water pumps are generally a function of the flow rate
The primary disadvantage of the absorption system are their size and weight
and they are larger and heavier than the electric chillers of the same capacity.
xv
3.1 History
Absorption systems have been used in air – conditioning applications for over
50 years. Ammonia – water absorption equipment was found to be well suited for
large capacity industrial applications that required low temperature for process
cooling. In the late 1950’s the first working double-effect lithium bromide – water
currently used to produce chilled water for space cooling and can also be used to
In the 1960’s the natural gas industry was very effective in promoting this
chillers were successfully marketed on the basis of lower operating costs, and better
motors and controls increased the performance and decreased the cost of electric
cooling systems. Additionally, and perhaps more importantly, the gas crunch of the
seventies curtailed gas cooling promotion and forced prospective buyers to remain
with conventional electric systems. Since 1987 when the Montreal Protocol first
came into existence many issues surrounding electric cooling including the use of
CFC refrigerants and electric utility rates, have become increasingly complicated.
Coincident with these electric cooling issues, gas costs have remained relatively
As a result of rising electric rates and the increased efficiency, reliability and
accessibility of gas equipment Figure 3.1 shows the Absorption cooling market
390
334
287 140
121
95
Currently there are no state or federal standards that regulate gas absorption
cooling systems. However, there are several metrics that are used to define
COP
IPLV
APLV
the energy input, in BTU. This same metric is applied to electric chillers, but
since it is based on site energy, it is not good for comparing gas and electric
chiller efficiencies. Gas absorption chillers, as well as electric chillers, are rated to Air
below:
load profile and the part load characteristics of chillers. It was originally conceived
as part of ANSI/ASHRAE standard 90.1 (standard for energy Efficient design of New
Non residential and High-rise Residential buildings) in response to need for directly
comparing manufacturers part load data. The method assumes that the chiller operates
at a specific part load for a specific number of hours during the year. According to the
following equation:
IPLV = 1
____________________________________
0.17 + 0.39 + 0.33 + 0.11
_____ ____ ____ _____
A B C D
Chiller Load Chilled water Mfgr Rated COP Part Load Hours(%)
(%) Return Temp (F)
100 85 A 17
75 78.75 B 39
50 72.5 C 33
25 66.25 D 11
COP ratings A,B,C, and D at each part load condition are obtained from the chiller
manufacturer and should be derived from actual chiller tests. Note that the calculation
allows for a 2.5 Deg C reduction in the entering cooling water temperature for every
10% drop in cooling load. A lower entering cooling water temperature corresponds to
part load (reduced) cooling demand, that results from a drop in ambient temperature.
when cooling load is dominated by internal gains) this estimate of part load
modeled to actual building load profiles tailored to site- specific ambient conditions
The applied Part Load value, APLV is calculated using the same IPLV
formula, except that actual chilled and condenser water temperatures and flow
rates are used. The advantage of using the APLV over the IPLV, is that this rating
The figure no. 3.3 shows the economics of absorption systems vs. electric chillers.
They are driven by the additional investment cost and several factors
influencing operating cost, including:
Relative costs of the electricity and gas, and their billing structures,
Relative performance characteristics
Operating characteristics
Relative maintenance costs.
The first three factors are discussed in the following sections and combined to
It is essential that the complete utility rates and rate structures are used for an accurate
economic analysis. Utility rate structures may include one or more of the following:
Block rates : - The electric block rates may be in terms of kWh, with different rates for
various levels of energy consumption. It may also be stated in kWh per kw of demand.
In this case kWh rate is function of demand. A lower demand typically results in a large
allowed amount of kWh at a lower rate. A high demand results in a smaller amount of
kWh before the higher rate kicks in. typically, although not always, the unit price per
Time of use rates – The electric rate may vary depending on the time of day. The time
of use rate is typically described in terms of on-peak and off peak and sometimes partial
peak.
Ratchets – The electric rate may include a demand which allows for a variation on
how the demand kW is defined.
Taxes – applicable taxes and franchise fees, which can be over 10% in many ares.
Special rates – For gas cooling equipment or special load-management electric rates
xxiii
are sometimes available. Using average electric and gas cost is rarely adequate to
capture the cost of operating cooling equipment, especially when the rate structure
includes demand charges or declining blocks. The marginal electric price for
cooling has a larger demand component relative to usage, which drives up the unit
price. The details of the actual electric rates must be considered in the total
hours per day, five days per week. Equipment in hospitals will operate near
full load for much of the day and at reduced, but still significant load for the
overcome higher initial costs fro gas- engine driven chillers to be cost
where the equipment runs at part load, favors gas engine-driven chillers
load for relatively few hours and not at all for most hours will result in too
business requirements.
xxiv
Hours (EFLH)Are defined as the total cooling load supplied over the
running at full load. While this method does not reflect the efficiency of
such as DOE-2, HAP or TRACE, which predicts when, where and how
Refrigeration
150 TR to 2500 TR (525 kW to 8,775kW)
Capacity
Refrigeration
95 TR to 1460 TR (333 kW to 5,125 kW)
Capacity
Refrigeration
45 TR to 360 TR (158 kW to 1,264 kW)
Capacity
Refrigeration
150 TR to 1200 TR* (525 kW to 4,210 kW)
Capacity
The list is certainly not exhaustive. Daikin(Japan) withdrew from the absorption
cycle field in the 1980’s, but it seems from recent reports that some activities have
been taken up again. In addition to these in the list, there are manufacturers that
working pair is designed for air cooling applications. For historic reasons
capacities are given in US RT(refrigeration tons), one US ton of ice per hour, in
Hotels
Commercial buildings
Education centers
Hospitals
Super markets
Pharmaceutical companies
Refineries & Petrochemicals
Chemicals
Electronics
Engineering Industries
Thermal Power Plants
Dairy and confectioneries
3
> 500TR
200 - 500 TR
< 200 TR 16
2
11 9 5 8
1 4
5
5 2 14
4
3 8
5 6 6 4 2
4 1 3
2 1 1
rocess g O he
rs T t
es Power Refiner
y Che ical ls
Hote
Hos s s
in il al
dP t t roche m x m p Commercial
e
oo Pe
F
xxxiii
4. DESIGN ANALYSIS
4.1 Overview
efficiency code bodies. The results of a detailed energy and rates analysis for seven
The cities and buildings are representative of the range of climates and
building occupancies where gas cooling options would be used. The list of cities,
building type and size are provided in Figure 4.2. The economic analysis is of course
dependent upon gas and electric rates. Building description and city specific utility
The results are graphed for various gas rates and various electric rates. Due to
The complexities of the interactions between fuel type usage and utility rates. It was not
possible to develop “typical” gas to electric cost results. These graphs can be used, as
will be shown by example in the following chapter to determine relative increase in gas
chiller to an electric chiller. The results of separate fuel type analysis can then be
CITY CDD 50
San Francisco 2.833
Chicago 2.941
Washington DC 3.473
Los Angeles 4.77
Atlanta 5.083
San Diegeo 5.223
New Delhi 3.221
River side 5.295
Miami 9.474
Figure 4.2 shows the building types included in the analysis, along with the
building size in square feet, and the cooling equipment sizes represents the variation
in cooling load for the cities analysed. The sizing of the cooling plant follows
the standard and high efficiencies assumed for the various types of chillers.
> 800
Centrifugal
systems, results of any hybrid systems analysis cannot be generalized. They were
therefore intentionally not included in this analysis. However, if the results indicate
that a gas absorption chiller is cost effective, or even marginally not cost effective, a
hybrid system under the same conditions, will typically be cost effective.
simulation models. The models provide comprehensive data on energy use and
The graphs in the figure 4.5 present the energy savings for watch of the cities for a
range of marginal gas and electrical prices. The graphs present the annual energy
cost savings, in rupees per year, versus the marginal cost of gas, in rupees per therm,
or the marginal cost of electricity in rupees per kWh. The marginal energy cost, gas
in therms or kWh. The marginal cost accounts for varying rates that may apply
ratio(SIR), SIR is defined as the Life Cycle Cost (LCC) savings, in dollars, divided
by the incremental measure cost per unit capacity, in rupees per ton capacity, as
Incremental Cost
The SIR uses an investment model over the life of the equipment rather than
the simplistic and short range perspective of simple payback.
The LCC savings describe the present worth of the energy cost savings over
the life of the investment. If the LCC savings are greater than the incremental cost,
then the SIR will be greater than one and the measure is assumed to be cost effective.
Building type,
xxxvii
Equipment,
Climate,
Utility rate, and
Scalar ratio.
Another element of the first cost for gas absorption chillers is the potential
savings from interactions with other building elements. For example, installing a
gas absorption chiller may reduce the building’s electric service drop and load
center. These savings could be significant, but are not included due to the
analysis. The scalar ratio is a single term that combines discount rate, period of
analysis, fuel escalation and other factors. The first year savings are multiplied by
the scalar to arrive at the life cycle savings. In technical terms, the scalar ratio
4.4 Effective Utilisation of waste heat from Diesel Genset to Run Air
conditioning Plant:
stations. Industries depending heavily on electrical energy are the most affected
ones. Industries are encouraged to have their own captive power stations. Diesel
generating sets are the most common captive power stations. The exhaust gases of
these gensets have a very large amount of heat(about 700 Degree Celsius at full
load), which is wasted, can be effectively exploited. Waste heat of coolant (about
120 Degree Celsius)from diesel gensets, equipped with evaporative cooling system
can also be exploited. The waste heat of exhaust gas & coolant so exploited can run
Absorption chiller based central air conditioning plant can be run by tapping
waste heat of the exhaust (14.5TR) and coolant heat(15.5TR) of 125 HP genset.
Kaltimex, etc are reported. Such system with combined heating & power (CHPC)
is the need of time for conservation of the energy.
xxxix
Key words :
Nomenclature:
Condenser temperature = 45 C
Absorber temperature = 45 C
Thermodynamic Calculations :
P o = 6.54 mm Hg( At 5 C)
P = 71.9 mm of Hg & t = 91 C
h1 = -50 kj/kg
h1 = -22 kj/kg
State 4 :
t = 45 C ξ Li Br2 = 0.63
h 4 = -140 kj/kg
h3 = h2 - [ f ( h1 – h4) / ( f – 1) ]
h = (250 + 1.88t) kj / kg
State 7 :
h7 = h6 = 188.4 kj / kg
State 8 :
qb = h5 – h2 + f (h2 – h1)
= 3189 kj / kg of vapour.
xliv
Coefficient of Performance :
= 0.728
= 70 kW
= 105.56 kW
= 30 TR
xlv
Figure 4.5 - Layout of Vapour Absorption Chiller with Wasste heat of Diesel genset
With increased natural gas availability and ever widening demand supply gap
to meet their ever increasing power needs. Industries are utilizing the tri-
generation systems which utilizes the waste heat from the engine Exhaust
directly along with the jacket water to generate chilled/Hot water to cater to
Figure 4.6 – Sankey Diagram for IC engine with & without heat recovery
xlvii
The following graphs that describe the performance of gas absorption chillers in a
variety of cities and building types. As described earlier, these graphs were
developed from DOE-2.1E runs done for representative prototype buildings using
the actual utility rate structures currently published for each cities.
Two sets of energy cost savings are calculated for each building type. One is for a
range of marginal gas costs and a fixed marginal electric cost. The other is for a
The top graph in figure 4.7 is typical of the annual energy cost savings Vs marginal
cost graphs. The bottom graph is same for the same conditions showing the energy
cost savings Vs marginal costs. These particulars are for the medium office building
type prototype. The comparison is between a gas absorption chiller and a standard
The vertical y-axis shows the annual energy cost savings, between the base
equipment and the gas Absorption Chiller. As shown on the top graph, as gas prices
Figure 4.7 – Energy Cost Savings for Absorption Chillers vs. Standard
Efficiency Electric chiller for Medium Office
xlix
Figure 4.8 – Energy Cost Savings for Absorption Chillers vs. Standard
Efficiency Electric chiller for Large Office
l