Service entrance conductors subjected to physical damage shall be protected in any of the
following ways or methods:
1. By RMC
2. By IMC
4. By EMT
The service disconnecting means for each set or each subset of service entrance conductor shall
consist of not more than six switches or six circuit breakers mounted in a single enclosure, or in a
switchboard.
LOCATION:
The service disconnecting means shall be installed either inside or outside the building or other
structure at a readily accessible location nearest the point of entrance of the service entrance
conductor
RATING:
The service disconnecting means shall have a rating of not less than the load to be carried. In no
case shall the rating be lower than specified through:
1. One circuit installation -- The service disconnecting means shall have a rating of not less than
15 amperes.