Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

This article has been accepted for publication in a future issue of this journal, but has not been

fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

Impedance Matching for VSC-HVDC


Damping Controller Gain Selection
M. R. Safari Tirtashi, Student Member, IEEE, O. Samuelsson, Senior Member, IEEE, J. Svensson, and
R. Pates

 Generally, modal analysis of a linearized power system model


Abstract— The impedance matching concept is employed in provides valuable information about mode controllability and
this paper to select the optimum gain of a VSC-HVDC damping mode observability to be used to design the damping
controller. The damping controller of the DC link is based on controller [6]. The gain selection task is normally done
control of active power in proportion to the difference in local
frequency at the VSC-HVDC converter stations. To explain
through visual inspection of a root locus or through
impedance matching, the small-disturbance electro-mechanical optimization [7]-[11].
dynamics of a power system is transformed to an equivalent LC- In this paper, the impedance matching concept is applied to
circuit. The VSC-HVDC damping controller corresponds to select the optimum gain of the VSC-HVDC damping
introducing a resistor in the circuit model. Using impedance controller to achieve the maximum possible damping. The
matching to select resistor value in the circuit model is equivalent damping control of the DC link is based on the control of
to selecting damping controller gain that gives maximum
damping ratio. An analytical derivation is conducted for a
active power in proportion to the difference in local frequency
linearized model of a generic two-area power system, including at the converter stations. It can be formulated as P  Kf
an expression for the optimum gain. It is also shown how the where P is a supplementary damping control signal added to
concept may be employed without a circuit model and that the the active power set-point, K is the gain of the controller and
optimum value is hardly affected by changes in power flow. Then f is the difference in local frequency at the VSC-HVDC
the performance of the proposed approach in multi-mode test
converter stations. This type of damping controller is already
systems and with nonlinearities is evaluated using dynamic
simulations in DIgSILENT PowerFactory. The results show that used in reality [12], [13]. It needs no phase compensation and
impedance matching maximizes the targeted mode damping ratio is limited just to gain selection as concerned in the paper.
while non-targeted modes are not negatively impacted. The work presented in [14] has some similarities to what we
have done here in this paper. The same type of the damping
Index Terms— Damping, impedance matching, inter-area controller for the VSC-HVDC link is considered there to
mode, power system dynamics, VSC-HVDC modulate the active power of the DC link to damp out the
electro-mechanical oscillations. The Four-Machine Two-Area
I. INTRODUCTION test system [6] as we used here is considered to evaluate the

I NTER-AREA oscillations in power systems are usually


observed when a group of generators in one part of the
system are connected to a group of generators in another part
controller performance. To find out the optimum gain which
gives the maximum damping, visual inspection of
corresponding root locus plot is carried out.
by weak tie lines. These oscillations may limit the transfer When the gain of utilized damping controller increases, the
capacity of the transmission lines and might lead to system root locus plot starts on the imaginary axis, loops into the left
break up [1]-[3]. To minimize the effect of inter-area half-plane and returns to zeros on the imaginary axis. This is a
oscillations, active power modulation using damping actuators generic property of this type of damping controller. The key
is an effective solution which has been exercised by network point of this paper is to show that impedance matching
operators such as WECC since the 1970s [4]. Among possible concept can be used to find the point of maximum damping.
actuators, VSC-HVDC is particularly attractive since it Compared to advanced optimization and visual inspection
permits direct modulation of active power with no change in of a root locus method for gain selection, the impedance
reactive power. A VSC-HVDC link between two areas in an matching application method presented in this paper is simpler
AC system thus has great leverage on oscillations between for implementation and it could lead to a self-tuning
these areas [5]. Once a VSC-HVDC link is installed between controller. It also gives intuitive understanding which ‘‘is
two areas, to improve the small signal stability, the DC link generally more important to the overall successful operation of
damping controller must be well designed. the power system than the many available, elegant control
design techniques’’ [15].
M. R. Safari Tirtashi, O. Samuelsson and J. Svensson are with the Division Only a limited number of publications concern the
of Industrial Electrical Engineering and Automation, Lund University, SE-221 impedance matching application in power system small-
00 Lund, Sweden (e-mail: ielreza@iea.lth.se).
R. Pates is with the Department of Automatic Control, Lund University, disturbance electro-mechanical stability context. The concept
SE-223 63 Lund, Sweden (e-mail: richard.pates@control.lth.se). has previously been used to qualitatively explain the root locus

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

when active power at one point is modulated in proportion to impacted.


local frequency deviation [16]. It also has been used to select The small-disturbance electro-mechanical dynamics of a
the optimum gain for PSS [17]. Moreover, in [18], an power system can be translated to an equivalent circuit model
impedance matching based controller is designed to extinguish with inductances and capacitances [23], [24]. A linearized
electro-mechanical waves in power networks. classic second order generator model then translates to an LC-
In [19], we introduced the impedance matching concept circuit and a line to an inductance. The resulting equivalent
application for VSC-HVDC and energy storage gain selection circuit model of the generic two-area power system is shown
in a very short format. This paper comprehensively explores in Fig. 1(c). As it can be seen, the power system includes a
the idea presented in [19] with eigenvalue analysis and time VSC-HVDC link, while the circuit model has a resistor,
domain simulations for different test systems and different RHVDC, which represents damping control of the HVDC link.
loading conditions. It also provides analytical support to X1  X'd1 XT1 V1 1 X3 PAC V2  2 X2  X'd2 XT2
E1 1 E2 2
determine the optimum gain of the VSC-HVDC damping PDC
controller from circuit model parameters also without the G1 G2
(a) P1 P2
circuit model.
To do so, first the proposed method is illustrated using a
linearized model of a generic two-area power system. Then to
extend the concept application and evaluate its performance in
multi-mode test systems, for different operating conditions,
the non-linear time domain simulations are carried out for
Four-Machine Two-Area [6] and NORDIC32 [20] test (b)
L1 L3 L2
systems. Also the eigenvalue analysis is carried out for both i2
C1 i1 C2
test systems. The results are provided and thoroughly  
V 1 R HVDC
V2

discussed.
The remainder of the paper is organized as follows: Section (c)
II describes the optimum gain selection based on impedance Fig. 1. (a) Two-area system with VSC-HVDC with p.u. magnitudes for
normal loading condition:E1δ1=1.070°, E2δ2=1.07-60°,V1θ1=1-21°,
matching with and without circuit model. Section III describes
V2θ2=1-40°. (b) Implemented damping controller of the VSC-HVDC link.
the non-linear test systems. Dynamic simulation results are (c) Equivalent circuit model that reproduces the small disturbance electro-
provided and discussed in section IV and finally section V mechanical dynamics including RHVDC, which represents the damping
concludes the paper. controller.

It should be noticed that the transformation of the power


II. GAIN SELECTION BASED ON IMPEDANCE MATCHING
system model to an equivalent LC circuit is visually similar to
To explain the proposed method, a generic two-area power LCL filters [25] which are usually used to interconnect an
system with one inter-area mode from [21] is considered, see inverter to the utility grid. The active damping methods [25]
Fig. 1. The damping control of active power for the VSC- are applied there to solve the natural resonance problem of the
HVDC link is in proportion to the difference in local LCL filters. In both our method also for active damping
frequency: methods, the converter control is changed in a way (adding
d supplementary control signal) to mimic a resistor operation to
PDC  K (1   2 ) (1)
dt add some damping. In active damping methods, the damping
where K is the gain of the damping controller and i is the controller is implemented for an LCL circuit while in our
voltage phase angle at bus i as shown in Fig. 1. approach the damping controller is ultimately applied for a
The implemented damping controller of the VSC-HVDC power system model. Also, in our approach, we formulate the
link in this paper is depicted in Fig. 1(b). f1, f2 are the damping problem in a way to apply the impedance matching
measured frequencies at converter stations, K is the gain of the to find out the optimum gain which gives the maximum
damping controller, Psch is the scheduled power (set-point) and damping ratio. But in active damping methods there is no such
Pref is the reference power. a formulation to determine the optimum gain and the gain of
Using the local feedback signals for HVDC damping the controller is mainly selected based on the converters
controllers than the wide-area measurement based signals is design requirements, specifications and limitations [25]-[27].
supported in [22]. The local signals are more robust against The procedure to select the optimum gain based on the
the loss of communication and changes in the network. But the impedance matching concept is explained in the following.
authors drop the idea of using the local signals because of the
possible limitation on the maximum damping influence on the A. Power System Model and Equivalent Circuit Model
swing modes due to the nearby-zeros in the associated root The first step to select the optimum gain for the damping
locus plot and the gain margin needed to avoid destabilization controller based on the impedance matching concept is to
of the local non-swing modes. So it is important to achieve the match the power system model with the equivalent circuit
maximum possible damping of the inter-area mode as we model. To do so, first the equations that describe the power
carried out here. Also the other modes are not negatively system are presented then the linearized state-space model for

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

power system with inclusion of the VSC-HVDC link is X1 X 2 X


derived. The focus is to derive the state matrix of the 1   , 2  3 (12)
K1 K 2 K3
linearized power system model. Moreover, the state-space
K1, K2 and K3 are the linearization constants.
model for the equivalent circuit is derived. By making the
To validate the linearized power system model of Fig. 1(a)
system matrices for power system and equivalent circuit equal,
presented in (9), K=0.2 (damping controller gain) is
then the parameters for the equivalent circuit model are
considered as arbitrary value and the response of the power
determined. This derivation process is explained here.
system non-linear and linear models to an impulse disturbance
The classic second order generator model [6] is considered
in G1 mechanical power are compared and shown in Fig. 2 for
for G1 and G2 as follows:
G1 speed deviation in rad/s. The power system data used for
di the simulation (normal loading condition) is provided in Table
 i  s (2)
dt I. Based on the Fig. 2, the linearized model in (9) agrees well
2H i di with the non-linear model in the small-disturbance electro-
 Pmi  Pei  D i i (3)
s dt mechanical dynamic behavior.
where i , i , s , Hi, Pmi , Pei and Di are rotor angle, rotor 0.14
non-linear
linear

speed, rotor synchronous speed, inertia constant, mechanical


power, electrical power and damping coefficient of generator
i.
0.06
Applying the power balance at buses 1 and 2 leads to the
following:
EV VV 0
P1  1 1 sin(1  1 )  1 2 sin(1  2 )  PDC (4) 0 2 4 6 8 10
X1 X3 Time (s)
Fig. 2. G1 speed deviation (rad/s) for non-linear and linear power system
V2 E 2 VV
P2  sin(2   2 )  1 2 sin(1  2 )  PDC (5) models for closed-loop system with gain K=0.2 following the impulse
X2 X3 disturbance in G1 mechanical power (5% for 100 ms).
Next introduce:
For the equivalent circuit model the following state vector is
z1  1  1 (6)
considered:
z 2  1  2 (7) X  V1 V2 i1 i 2 
T
(13)
 2  2 depends on z1 and is not needed to derive the state Then the state matrix is:
space model.
 1 
Considering (1), the damping control of VSC-HVDC link is 0 0 0 
written as: C1
 
1
d
PDC  K (z 2 ) (8) A   0 0 0 

(14)
dt C2
    R R HVDC3 
 3 HVDC 3 
The above equations yield the following linearized power 3

system model:  0 0 R HVDC 4  R HVDC 4 


d where:
( X )  AX (9)
dt 1 1
3  , 4  (15)
where the state vector ΔX is: L1  L 2 L3
T
  Clearly the state matrices, (11) and (14), have the same
 z1 z 2  structure and if the circuit parameters are chosen as:
X  1  2  (10) 2 H1 2H 2
 X1 X3  C1  , C2  , RHVDC=1/K
 K1 K 2  s s

and the state matrix A with Di=0 is: X1 X X
L1  , L 2  2 , L3  3 (16)
  s  K1 K2 K3
0 0
2H1
0 
the two state matrices in (11) and (14) are exactly the same
  and the models are exactly equivalent. The equivalence can
0 s
0 0  only be expected to be valid at the operating point where the
 2H 2 
A (11)
1 1 1 1  power system model was linearized. This equivalence is more
  accurate than the approximate method presented in [23]. Here
 1 1 K1 K1 
 the operating point is considered for determination of the
1 1 
0 0  inductances of the equivalent circuit as considered in [24]
 K 2 K 2  also, while it has not been taken into account in [23].
Where: The power system model data complemented with normal,

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

reverse and zero loading conditions and the associated model. KHVDC=1/RHVDC=0.344 thus gives maximum damping
equivalent circuit model from (16) are provided in Table I. ratio.
The optimum RHVDC and OPT can also be determined
TABLE I analytically from the circuit model parameters as presented in
POWER SYSTEM AND EQUIVALENT CIRCUIT MODEL DATA
Appendix B. This gives the same values as the iterative
Power System Equivalent Circuit
procedure.
H1=4.63, H2=4 MJ/MVA
(a) (b)
D1=D2=0 (p.u./(rad/s)) (Normal and reverse loading
11.5 12.5
p.u. magnitudes: conditions)
X1=X2=0.25, X3=0.35 C1=0.0295, C2=0.0255 10.5 11.5

Imag

Imag
(Normal loading condition) L1=L2=0.2690, L3=0.3688 10.5
9.5
P1=P2=1.5, PAC=0.9, PDC=0.6
9.5
(Reverse loading condition)
8.5
P1=P2=-1.5, PAC=-0.9, PDC=-0.6 Zero loading condition: -2 -1 0 1 2 8.5
-2 -1 0 1 2
Real
(Zero loading condition) C1=0.0295, C2=0.0255 Real
Fig. 3. Root locus of oscillatory mode when changing KHVDC=1/RHVDC with
P1=P2=0, PAC=0, PDC=0 L1=L2=0.2336, L3=0.35 pole locations corresponding to no control (x), zeros (o) and impedance
matching (*) indicated as well as lines through (*) and the origin. (a) Normal
and reverse loading conditions. (b) Zero loading condition. Plots for circuit
model and power system coincide.
B. Impedance Matching for Optimum Gain Selection
Once the power system model is equal to the equivalent To evaluate the robustness of the proposed method, also
circuit model, the optimum gain for damping controller is reverse and zero loading conditions from Table I are
selected based on the impedance matching concept as investigated. For the reverse loading condition, the root locus
described here. Without damping control (K=1/RHVDC =0), the plot is the same as for the normal loading condition, Fig. 3(a).
systems in Fig. 1 are both undamped and when the swing Also the optimum gain is calculated as the same as normal
mode is excited, energy will oscillate between the two areas in loading condition. For the zero loading condition, the root
power system or between the two capacitances in the locus plot is shown in Fig. 3(b). Using L and C values in Table
equivalent circuit. When damping control is introduced with a I for the zero loading condition and based on the iterative
low gain, i.e. low value of K=1/RHVDC, swing energy will be procedure provided in the Appendix A gives KHVDC= 0.348 at
dissipated in RHVDC and the oscillation is damped as OPT  10.8 rad/s. In this case, although the root locus plot
oscillatory eigenvalues move left, see root locus plot in Fig. changes pretty much from the normal loading condition the
3(a). It should be noted that the root locus plots for the power calculated optimum gains are very close to each other.
system and circuit model coincide. When the damping To further investigate, the robustness of the proposed
controller gain increases and reaches high values, the method is evaluated for different initial damping of the
oscillatory eigenvalue moves to the undamped zeros on the electro-mechanical mode. By setting the mechanical damping
imaginary axis corresponding to RHVDC being (close to) a of the synchronous generators D to 0, +2 and -2, the cases
short-circuit leaving the circuit again without RHVDC. To select where the oscillatory eigenvalue lies on the imaginary axis, in
the optimum gain, optimum RHVDC, the impedance matching the left halfplane and in the right halfplane are investigated. In
concept is applied: the maxim oscillation energy is dissipated all cases the method gives maximum damping ratio at
in RHVDC when RHVDC=RHVDCOPT=|Z| where Z is the complex optimum gains that differ first in the third digit.
impedance of the circuit model seen from the terminals of
RHVDC evaluated at the resonance frequency. Having the C. Optimum Gain Selection without Circuit Model
damper, adding RHVDC in the equivalent circuit, changes the In a circuit, impedance matching means applying a
resonance frequency. To calculate this frequency, an iterative voltage, uˆ sin t  , at the terminals of RHVDC, then measuring the
procedure is applied, see Appendix A. Using L and C values current amplitude iˆ and setting the RHVDC to |Z|= uˆ / iˆ . This
in Table I gives RHVDC=2.91 at OPT  10.2 rad/s, where procedure can be translated to a power system context: the
OPT is the absolute value of the relevant eigenvalue. active power output of VSC-HVDC link is modulated to
The resulting poles indicated in Fig. 3 show that impedance excite the electro-mechanical dynamics in open-loop, then
matching indeed gives pole locations with maximum damping measuring the difference in local frequency at VSC-HVDC
ratio. Damping ratio is used by many TSOs to specify converters. Doing this for a range of frequencies gives the
minimum damping; usually 5% [2]. For the pole location at Bode magnitude plot of the transfer function from active
  j the damping ratio is calculated as: power input to frequency deviation output; see Fig. 4. It
should be noted that to derive the Bode plot, the damping
   /  2   2 (17)
control is off but mechanical damping D1=D2=2 is introduced
As the circuit and power system model in Fig. 1 are to avoid infinite and zero amplitude gains.
equivalent, the root locus in Fig. 3 for changing RHVDC is thus The critical issue is to know at which frequency to read the
valid also for changing the gain KHVDC in the power system amplitude. Based on the proof provided in Appendix B for the

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

equivalent circuit model, the relevant frequency is the


0.02
(a) Frequency deviation (pu) (b) K=0.347

geometric mean of the open-loop pole frequency P and the


Active power (pu) K=0
0.03 0.01

frequency of the corresponding zero Z, OPT= PZ . At 0.01


OPT the Bode-diagram in Fig. 4 for normal loading condition
0

reads 9.29 dB=1/0.343. This means a gain KHVDC=0.343 which -0.01 -0.01

agrees well with the circuit model value.


-0.03 -0.02
For the reverse loading condition, the Bode-diagram and the 50 51 52 53
Time (s)
54 55 0 5 10
Time (s)
15 20

optimum gain is the same as the normal loading condition. For


the zero loading condition, the Bode-diagram is derived and Fig. 5. Simulation of two-area system in open-loop. (a) VSC-HVDC link
active power modulation. (b) Response in active power on the parallel AC
plotted in Fig. 4(b). At the geometric mean frequency, the line to impulse disturbance in G1 mechanical power (5% for 100 ms) for
Bode-diagram reads 9.31 dB=1/0.342 which corresponds to closed-loop system with gain KHVDC=0 and 0.347.
the gain KHVDC=0.342.
The Bode-diagram can be obtained from a linearized power III. MULTI-MODE TEST SYSTEMS IN DIGSILENT
system model. But it can also be obtained from repeated time POWERFACTORY
simulations of a model that may be non-linear. To exemplify To validate the proposed approach on more complex
this, Fig. 5 shows simulation of the (linearized) power system networks, two test systems are considered; 1) Four-Machine
model where the VSC-HVDC link active power is Two-Area system with inclusion of VSC-HVDC link, Fig. 6
sinusoidally modulated with amplitude 0.01 p.u and frequency and 2) NORDIC32 test system, Fig. 7. Both test systems and
OPT. The output signal amplitude is 1/0.347 times the input their associated controllers are modeled in DIgSILENT
signal amplitude, which again agrees with the circuit model PowerFactory [28].
value. For the first test system, the VSC-HVDC link with 200 MW
Sinusoidal excitation of the output active power of the nominal capacity is installed in parallel to the AC lines
VSC-HVDC link is however unrealistic in reality due to the between buses 7 and 9, see Fig. 6. This test system is mainly
large gain near the resonance frequency. A better option, to be used in the paper to evaluate the performance of the proposed
investigated, is a non-sinusoidal, possibly low-level, probing controller for three different loading conditions; 1) Normal
signal [13] together with appropriate system identification loading with 350 MW AC transfer from West to East. 2) Zero
methods to extract the relevant gain information. If successful, loading with 0 MW AC transfer. 3) Reverse loading with 350
the result is then an impedance matching-based self-tuning MW AC transfer from East to West.
procedure for VSC-HVDC damping controller. On the other hand, the main reason for using the
To demonstrate the performance of damping control with NORDIC32 test system is because of its many electro-
optimum gain in the time domain simulation, Fig. 5 also mechanical modes. Thereby, the impact of the impedance
shows the response of the power system model at normal matching based gain selection for the damping controller on
loading condition to an impulse disturbance. As it can be seen, non-targeted modes can be well investigated. This test system
with optimum gain, the electro-mechanical oscillations die out has similarities with the Swedish power network and its
within 5 s. original form is well damped, mainly because of well-tuned
(a) (b) PSS units. To challenge the impedance matching based gain
selection for the damping controller, all PSS units are
30
30 disabled.
20 The VSC-HVDC link with 250 MW nominal capacity is
Magnitude (dB)
Magnitude (dB )

20

10 10
installed between buses 4072 and 4044. This position
represents the Fenno-Skan link [29] between Sweden and
0 0
Finland.
-10 -10

10 (rad/s) 15 10 (rad/s) 20
Fig. 4. Gain plot of Bode-diagram of power system in Fig. 1 with VSC-HVDC
active power as input and difference in frequency at the converters as output.
Damping control is off but mechanical damping D=2 is introduced to avoid
infinite and zero amplitude gains. Indicated frequencies are P (left), OPT
(middle) and Z (right). (a) Normal and reverse loading conditions. (b) Zero
loading condition.

Fig. 6. Four-machine two-area test system with VSC-HVDC link.

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

controller from 0 to 7, the relevant part of root locus plot of


the targeted mode is derived from DIgSILENT PowerFactory
and is shown in Fig. 8(b). It should be noted that the targeted
mode is the most impacted mode (inter-area mode for this test
system) by the VSC-HVDC link. As it can be seen, impedance
matching indeed gives pole locations with maximum damping
ratio.

(a)
20
(b)4.4

4
0

Magnitude (dB)

Imag
3.6
-20

3.2
-40
2 4 6 8 10 -0.8 -0.4 0
Frequency (rad/s) Real

Fig. 8. (a) Gain plot of Bode-diagram of Four-Machine Two-Area test system


under normal loading condition with VSC-HVDC active power as input and
difference in frequency at the converters as output. (b) Root locus of targeted
mode when changing the gain from 0 to 7 with pole location corresponding to
impedance matching (*) indicated as well as line through (*) and the origin.

To evaluate the performance of the impedance matching


based gain selection for the damping controller, a solid three-
Fig.7. NORDIC32 test system with VSC-HVDC link corresponding to the
Fenno-Skan link.
phase fault is applied at the middle of one of the AC lines
between buses 7 and 8, see Fig. 6. The self-clearing fault is
IV. DYNAMIC SIMULATION RESULTS applied at 5 s and removed at 5.1 s. The non-linear simulation
results including the faulted line active power, angular
In this part, to evaluate the performance of the impedance separation between G1 and G3, VSC-HVDC link active power
matching based gain selection for the damping controller in and the control effort (modulated active power) are shown in
the presence of many electro-mechanical modes, nonlinearities Fig. 9.
and for different operating conditions, the two test systems As it can be seen, without any supplementary control, the
presented in section III are considered. system response is poorly damped while with the proposed
A. Four-Machine Two-Area Test System impedance matching based gain selection damping controller,
As mentioned, this test system is mainly used to evaluate the oscillations are well-damped and disappear within 5-10 s.
the performance of the proposed controller at different loading Moreover, to evaluate the robustness of the proposed
conditions. This test system has one poorly damped inter-area impedance matching based gain selection approach against the
mode and two local modes, see Table II. network parameters change, disconnection of the faulted line,
see Fig. 6, 100 ms following the fault is considered. The
TABLE II optimized gain for normal loading condition without any
ELECTRO-MECHANICAL MODES OF THE FOUR-MACHINE TWO-AREA SYSTEM network parameters change, KOPT=3.84, still gives very good
Mode Electro-mechanical modes Damping ratio (%) performance in damping the electro-mechanical oscillations.
K=0 K=3.84 K=0 K=3.84 To assess the impact of the impedance matching based gain
1 -0.07  j3.53 -0.59  j3.87 2.34 15.06 selection for the damping controller on system electro-
2 -0.59  j6.72 -0.61  j6.73 8.75 9.09 mechanical modes, Table II shows the eigenvalues of the
Four-Machine Two-Area system for zero and optimum gains.
3 -0.75  j6.90 -0.77  j6.93 10.90 11.15
With optimum gain, the inter-area mode, mode 1, damping is
greatly improved and the damping ratio of the non-targeted
To improve the damping of the inter-area mode, the modes (local modes) improved slightly.
optimum gain of the supplementary controller should be To further investigate the performance of the proposed
selected. To calculate the optimum gain based on the impedance matching based gain selection damping controller
impedance matching concept, the Bode-diagram of the Four- over radically different loading conditions, Fig. 10 shows the
Machine Two-Area test system with VSC-HVDC active faulted AC line active power and angular separation between
power as input and difference in frequency at the converters as G1 and G3 for zero and reverse loading conditions with fixed
output for normal loading condition is derived and is shown in gain optimized for the normal loading condition. The same
Fig. 8(a). Reading the Bode-diagram at the geometric mean three-phase solid self-clearing fault as applied for normal
frequency gives KOPT=3.84 as optimum gain. loading condition is considered here.
By changing the gain of the VSC-HVDC damping

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

(a) 250 the Fenno-Skan link connects these areas, it is expected to


55
Optimum
(b) Optimum

200
Zero
50
Zero
have considerable leverage on mode 2.
Tie-line active power (M W)

Angular separation (deg)


To calculate the optimum gain of damping controller to
150 45
improve mainly the damping ratio of mode 2 based on the
100 40 impedance matching concept, the Bode-diagram of the
50 35
NORDIC32 test system with VSC-HVDC active power as
input and difference in frequency at the converters as output is
0
0 5 10 15 20 25
30
0 5 10 15 20 25 derived and is shown in Fig. 11. Reading the Bode-diagram at
(c) 280 Time (s)
(d)60
Time (s)
the geometric mean frequency gives KOPT=4.96.
260
50 The studied fault case used to evaluate the performance of
40
the impedance matching based gain selection for the damping
DC link power (MW)

Control effort (MW)

240 30

20
controller is a three-phase short-circuit at bus 4012, at 5 s, for
100 ms cleared by disconnection of the line 4012-4022. The
220
10

200 0
simulation results are shown graphically in Fig. 11 for zero
and optimum gains.
-10
180
-20

160 -30 It can be clearly seen that with the impedance matching
0 5 10 15 20 25 0 5 10 15 20 25
Time (s) Time (s) based gain selection for the damping controller, the electro-
Fig.9. Dynamic response of the Four-Machine Two-Area test system under mechanical damping characteristics of the system are
normal loading condition. (a) Faulted Tie-line active power. (b) Angular
separation between G1 and G3. (c) VSC-HVDC link active power. (d) Control improved and the proposed approach gives a very good
effort. damping profile. This improvement is in line with the
(a) 50
(b)110 eigenvalue movements in Table III. As it can be observed,
100 with the optimum gain, the damping ratios of the critical
0
modes increased or are constant generally and specifically for
Tie-line active power (MW)

90
Angular separation (deg)

Zero loading
the targeted mode, mode 2, the improvement of the damping
-50 Zero loading
Reverse loading 80
Reverse loading

-100 70
ratio is substantial. This positive movement led to better
-150
60
simulation results for the optimum gain in Fig. 11.
50
-200
TABLE III
40
EIGENVALUES OF THE NORDIC32 TEST SYSTEM; FENNO-SKAN LINK
-250
0 5 10 15 20 25
30
0 5 10 15 20 25 Mode Electro-mechanical modes Damping ratio(%)
Time (s) Time (s)

Fig.10. Dynamic response of the Four-Machine Two-Area test system under K=0 K=4.96 K=0 K=4.96
zero and reverse loading conditions. (a) Faulted Tie-line active power. (b) 1 -0.12  j4.96 -0.20  j4.86 2.47 4.12
Angular separation between G1 and G3.
2 -0.15  j3.77 -0.69  j4.13 4.13 16.45
It is clear that with the proposed impedance matching based 3 -0.28  j6.18 -0.36  j6.21 4.59 5.87
gain selection for the damping controller, the system is stable 4 -0.34  j5.70 -0.34  j5.70 5.99 5.99
and the damping of the inter-area mode, the dominant mode, is 5 6.94 6.95
-0.42  j6.13 -0.42  j6.13
quite satisfactory with the fixed gain for different loading
conditions. (a) (b)2200
0
Optimum
B. NORDIC32 Test System -5 2000 Zero
Tie-line active power (MW)

The second test system used to conduct the non-linear 1800


Magnitude (dB)

simulations is the NORDIC32 test system. The impact of the -15 1600

impedance matching based gain selection for the damping 1400

controller on non-targeted modes is well studied using this test


-25 1200
system. The position of the considered VSC-HVDC link
represents the Fenno-Skan link, between buses 4072-4044, see 2 4 6 8 10
1000
0 5 10 15 20 25

(c)-20
Frequency (rad/s) Time (s)

Fig. 7. The five least damped modes of the NORDIC32 test (d)60
Optimum
system once the DC link is in operation are shown in Table III. -25 Zero
40

As it can be seen, without the supplementary control, K=0, the -30


Angular separation (deg)

Control effort (MW)

-35
damping ratios for the critical modes are relatively low. Mode -40
20

1 corresponds to generators in Central and South parts of the -45


0

NORDIC32 test system swinging against each other. With -50


-20
Fenno-Skan link siting, it is not possible to improve its -55

damping ratio significantly because of low mode -60


0 5 10 15 20 25
-40
0 5 10 15 20 25

observability. The two areas swinging against each other in


Time (s) Time (s)

Fig.11. (a) Gain plot of Bode-diagram of NORDIC32 test system with VSC-
mode 2 are the External area in NORDIC32 test system (buses HVDC active power as input and difference in frequency at the converters as
4071, 4072 corresponding to Finland), and the South area output. (b) Total active power of the five interconnecting transmission lines
between northern and central parts. (c) Angular separation between generators
(buses 4061, 4062, 4063 representing southern Sweden). Since at buses 4072 and 4063. (d) Control effort.

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

V. CONCLUSION Then the response of v to excitation by current source i is:


v(s)=(RHVDC-1+Z1-1+Z2-1)-1i(s) (19)
This paper shows that the impedance matching concept can be
used as criterion to select the gain of the supplementary VSC- The task is choosing RHVDC to maximize the damping ratio of
HVDC damping controller that gives maximum damping the inter-area mode. This is equivalent to the feedback
ratio. The damping control of the DC link controls active problem, design RHVDC to maximize the damping ratio of:
power in proportion to the difference in local frequency at G(s)=RHVDC /(1+ RHVDC (Z1-1+Z2-1)) (20)
converter stations. The optimum gain can be obtained from an It can be shown that:
equivalent circuit model, from a linearized power system ŝ
1  ( 2 )2
model, from time simulations and possibly from probing -1 -1 a
RHVDC(Z1 +Z2 )= k (21)
signal tests. The required analytical derivation to apply the ŝ(1  ŝ 2 )
impedance matching concept has been conducted on the
Where:
linearized model of a generic two-area power system. The
optimum gain selection and the use of a Bode diagram to find Lt
k=RHVDC L t C t /L3 , ŝ= L t C t s , a= 4 (22)
it is supported by an analytical proof. The performance of the L t  L3
proposed method has been evaluated on two non-linear multi- We will continue the optimal damping problem in terms of k,
mode test systems for different loading conditions. The results
ŝ and a since it is simpler.
show that the impedance matching based gain selection
The damping ratio of a specified pole is defined in (17). The
increases the targeted mode damping ratio dramatically and
poles are the values of ŝ that solve the equation:
also the non-targeted modes are not negatively impacted. This
led to well-damped system response in non-linear time domain ŝ
1  ( 2 )2
simulations with optimum gain for the damping controller. -1= k a (23)
ŝ(1  ŝ 2 )
APPENDIX A To solve (23), it is necessary that:
Z=Z0=RHVDC0=1/K0  ŝ 2 
While Z   1  ( a 2 ) 
Im 2 
0 (24)
  mode frequency for the current value of Z  ŝ(1  ŝ ) 
Z  Z  Z()
 
Letting
Z  Z  Z
ŝ  n (cos   j sin ) (25)
end.
Where Z0, RHVDC0 and K0 are the initial values for Z and doing some algebra leads to solving the following
(impedance), RHVDC (VSC-HVDC damping controller equation:
sin (a 4  4n  2n )  a 42n sin 3
equivalent resistor) and K (gain),   0.1 and   104 are 0 (26)
arbitrary values [16]. a 4n (4n  22n cos 2  1)
For  shows that:
APPENDIX B   (2  1)(a 4  2 ) 

  0,   arccos n n 
(27)
In the equivalent circuit model shown in Fig. 1, the  2 a 2
 
inductances L1, L2 and capacitances C1 and C2 are in series   n

connection. That model can be rearranged as shown in Fig. 12 It is therefore not possible to achieve a larger damping ratio
while an ideal current source is connected in parallel to RHVDC. than:
  (2  1)(a 4  2 )  
 n 
opt  sup  cos   arccos n

Lt  n    2a 2n  
i v RHVDC L3    (28)
Ct
(2n  1)(a 4  2n )
sup
Fig. 12. Rearranged model of the equivalent circuit with an ideal current  n  2a 2n
source that represents a perturbation to the power flow along the RHVDC, DC
link.
The above minimization can be solved by differentiating and
setting the derivative to zero. This shows that:
The current source represents a perturbation to the power opt  (1  a 2 ) / 2a 2 (29)
flow along the RHVDC, DC link, that can be used to excite the which is achieved by n  a . Provided there exists a k  0
system and the voltage v corresponds to the frequency
that achieves this damping ratio, the proof is complete. Try
deviation across the DC link. Lt is the total inductance of L1
k=a3.
and L2, Ct is the total inductance of C1 and C2.
For this value of k, the poles of G(s) are given by the solution
The circuit in Fig. 12 consists of three parallel impedances:
of ŝ3+(1/a) ŝ2+ ŝ+a3=0 which are:
Z1=(1+LtCts2)/Cts , Z2=L3s , Z3= RHVDC (18)
where s is the Laplace operator variable.

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

 ACKNOWLEDGMENT
1  a 2  (1  a 2 )(1  3a 2 ) 
 a ,   (30) This work was supported by the Elektra program of
 2a  Energiforsk and the Swedish Energy Agency, which is
Then it is verified that the damping ratio of these poles is gratefully acknowledged.
equal to  opt as above. Then, we have solved the optimal
damping problem while the optimum RHVDC is given by: REFERENCES
[1] Y. Yu, S. Grijalva, J. J. Thomas, L. Xiong, P. Ju, and Y. Min
L a3
R HVDCopt  3 (31) “Oscillation energy analysis of inter-area low-frequency oscillations in
LtCt power systems,” IEEE Trans. Power Systems, vol. 31, no. 2, pp. 1195–
1203, March 2016.
which is achieved at nopt  a . This frequency can be [2] D. Cai, P. Regulski, M. Osborne, and V. Terzija “Wide area inter-area
oscillation monitoring using fast nonlinear estimation algorithm,” IEEE
translated back into the original frequency context using (22) Trans. Smart Grid, vol. 4, no. 3, pp. 1721–1731, Sep. 2013.
as: [3] Y. Chompoobutrgool, and L. Vanfretti “Identification of power system
dominant inter-area oscillation paths,” IEEE Trans. Power Systems, vol.
nopt a 28, no. 3, pp. 2798–2807, Aug. 2013.
opt   (32)
LtCt LtCt [4] Y. Pipelzadeh, B. Chaudhuri, and T. C. Green “Control coordination
within a VSC HVDC link for power oscillation damping: A robust
To clarify more, the following steps are carried out to apply decentralized approach using homotopy,” IEEE Trans. Control Systems
the above proof for the open-loop Bode plot of Fig. 12 to Technology, vol. 21, no. 4, pp. 1270–1279, July 2013.
[5] R. Preece, J. V. Milanović, A. M. Almutairi, and O. Marjanovic
select the optimum gain. The flow chart of these steps is also “Damping of inter-area oscillations in mixed AC/DC networks using
shown in Fig. 13. WAMS based supplementary controller,” IEEE Trans. Power Systems,
Step 1: initial choice of RHVDC is set to  (open-loop). vol. 28, no. 2, pp. 1160–1169, May 2013.
[6] P. Kundur, Power System Stability and Control, New York: McGraw-
Step 2: excite the system using the current source at a range Hill, 1994, p. 1200.
of different frequencies and measure the voltage v. Use this to [7] M. Raza, E. Prieto-Araujo and O. Gomis-Bellmunt, “Small-signal
build up a Bode magnitude plot with the transfer function stability analysis of offshore AC network having multiple VSC-HVDC
systems,” IEEE Trans. Power Delivery, to be published. DOI:
H(s)=v(s)/i(s). 10.1109/TPWRD.2017.2725982.
Step 3: identify the resonant and anti-resonant frequencies, [8] N. Pathak, T. S. Bhatti, and V. Verma “Discrete data AGC of
p and z for the system. hydrothermal systems under varying turbine time constants along with
the power system loading conditions,” IEEE Trans. Industry
Step 4: select RHVDC as the magnitude of the system Applications, vol. 53, no. 5, pp. 4998–5013, Sep. 2017.
response at the frequency OPT= PZ . [9] P. Satapathy, S. Dhar, and P. K. Dash “Stability improvement of PV-
BESS diesel generator-based microgrid with a new modified harmony
If the first step is taken, then the response to current search-based hybrid firefly algorithm,” IET Renew. Power Gener, vol.
disturbance in Fig. 12 evolves according to: 11, pp. 566–577, Feb. 2017.
v(s)=( Z1-1+Z2-1)-1i(s) (33) [10] H. A. Mohammadpour, and E. Santi “Optimal adaptive sub-synchronous
resonance damping controller for a series-compensated doubly-fed
this means that the Bode magnitude plot we produce (step 2) is induction generator-based wind farm,” IET Renew. Power Gener, vol. 9,
the frequency response of the following transfer function: pp. 669–681, Feb. 2015.
[11] F. S. AL-Ismail, M. A. Hassan, and M. A. Abido “RTDS
L 3ŝ(1  ŝ 2 )
G op (ŝ)  (34) implementation of STATCOM-based power system stabilizers,”
L t C t (1  (ŝ / a 2 ) 2 ) Canadian Journal of electrical and computer engineering, vol. 37, no. 1,
pp. 48–56, Winter 2014.
Hence p=a2 and z=1 and so PZ =a (step 3). Now [12] C. Lu, Y. D. Han, J. B. He, X. C. Wu, P. Li, L. C. Li, J. T. Wu, J. H. Shi
and J. Hu, "Wide-area coordinated and adaptive damping control of
selecting RHVDC to be the magnitude of the response of this multiple HVDC links in China southern power grid," in Proc.2010
transfer function at this frequency (step 4) shows that: CIGRE, pp. 1-7.
[13] B. J. Pierre, F. Bernal, D.A. Schoenwald, and D. J. Trudnowski “Open-
L 3a 1  a 2 L 3a 3 loop testing results for the pacific DC intertie wide area damping
R HVDC   (35) controller,” in Proc.2017 IEEE PowerTech.
Lt Ct 1 1/ a 2 Lt Ct [14] M. Hadjikypris, and V. Terzija, “Active power modulation assisting
as required. controller scheme implemented on a VSC-HVDC link establishing
effective damping of low frequency power oscillations,” in Proc.2014
IEEE International Energy Conference.
Make the circuit [15] Power System Stability and Control, 3rd ed., CRC Press, 2006, Chapter.
Build up the Bode
open-loop; 9.
magnitude plot of :
RHVDC=∞ H(s)=v(s)/i(s)
[16] O. Samuelsson, “Power system damping structural aspects of controlling
active power,” Ph.D. dissertation, Dept. Idus. Elec. Eng and Automation,
Lund University., Lund, Sweden, 1997.
Resonant (ωp ) and anti-resonant (ωz ) [17] C. Ivanov, O. Samuelsson, K. Gerasimov, “Selection of PSS gain based
frequencies identification on impedance matching,” in Proc.2005 ELMA.
[18] B. C. Lesieutre, E. Scholtz, and G. C. Verghese, “Impedance matching
controllers to extinguish electromechanical waves in power networks,”
Selecting optimum RHVDC as equal to: in Proc.2002 IEEE Intl Conf. on Control Applications, pp. 25-30.
|H(s)|  pz [19] M. R. Safari Tirtashi, O. Samuelsson and J. Svensson, “Impedance
n
matching for VSC-HVDC and energy storage damping controllers,”
Fig. 13. Flow chart of the proposed approach to determine the optimum IEEE Trans. Power Delivery, to be published. DOI:
RHVDC. 10.1109/TPWRD.2017.2719578.

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. Citation information: DOI 10.1109/TPWRS.2018.2815153, IEEE
Transactions on Power Systems

[20] CIGRE Task Force 38-02-08, “Long Term Dynamics Phase II, Final Richard Pates received the M.Eng degree in
Report,” CIGRE publication, March 1995. 2009, and the Ph.D. degree in 2014, both from the
[21] T. Smed, and G. Andersson, “Utilizing HVDC to damp power University of Cambridge (U.K.). Since completing
oscillations,” IEEE Trans. Power Delivery, vol. 8, no. 2, pp 620-627, his Ph.D. he has moved to Lund University, where
Apr. 1993. he is currently a Postdoc at the Department of
[22] P. Agnihotri, A. M. Kulkarni, A. M. Gole, B. A. Archer, and T. Weekes Automatic Control. His principal research
“A robust wide-area measurement-based damping controller for interests lie in decentralized design methods for
networks with embedded multiterminal and multiinfeed HVDC links,” control systems in networks, with applications in
IEEE Trans. Power Systems, vol. 32, no. 5, pp. 3884–3892, Sep. 2017. large scale electrical power systems.
[23] P. Agnihotri, A. M. Kulkarni, and A. M. Gole, “Robust Global Control
Strategies for Improvement of Angular Stability using FACTS and
HVDC Devices,” Int J. of Emerging Electric Power Systems, vol. 14, pp
95-104, Jan. 2013.
[24] K. R. Padiyar, FACTS Controllers in Power Transmission and
Distribution, New Age International Publishers, 2007, p. 532.
[25] M. B. S. Romdhane, M. W. Naouar, I. S. Belkhodja, and E. Monmasson
“Robust active damping methods for LCL filter-based grid-connected
converters,” IEEE Trans. Power Electronics, vol. 32, no. 9, pp. 6739–
6750, Sep. 2017.
[26] M. H. Hedayati, A. Acharya, and V. John “Common-mode and
differential-mode active damping for PWM rectifiers,” IEEE Trans.
Power Electronics, vol. 29, no. 6, pp. 3188–3200, June 2014.
[27] F. Liu, B. Wu, N. R. Zargari, and M. Pande “An active damping method
using inductor-current feedback control for high-power PWM current-
source rectifier,” IEEE Trans. Power Electronics, vol. 26, no. 9, pp.
2580–2587, Sep. 2011.
[28] DIgSILENT PowerFactory Version 14. URL.
<http://www.digsilent.de/>.
[29] L. Pottonen, R. Hirvonen, K. Jaaskelainen and M. Jaaskelainen,
“Network Interaction Tests of the Fenno-Skan HVDC Link,” in
Proc.1991 Intl Conf. on AC and DC Power Transmission, pp. 285-289.

VI. BIOGRAPHIES

M. Reza Safari Tirtashi was born in Behshahr,


Iran in 1986. He received his B.S. in Electrical
Engineering from Mazandaran University, Iran, in
2008, and his M.S. in Electrical Engineering from
Zanjan University, Iran, in 2011. He is currently a
PhD student at the division of Industrial Electrical
Engineering and Automation, Lund University. His
research interests include power system stability and
dynamics, power system restoration and VSC-HVDC
transmission systems.

Olof Samuelsson is Professor of Electric Power


Systems at the division of Industrial Electrical
Engineering and Automation, Lund University,
where he also received his M.Sc. in 1989 and Ph.D.
in 1997. His research covers transmission issues such
as dynamics (damping, inertia), stability and large
disturbances (including geomagnetically induced
currents), as well as distribution issues such as
microgrids, integration of distributed generation and
resilience to large disturbances.

Jörgen Svensson is an associate professor at the


division of Industrial Electrical Engineering and
Automation, Lund University, where he also
received his M.Sc. in 1992 and Ph.D. in 2006. His
research covers electric power system issues such as
microgrids, wind power and HVDC grids. He has
also an industrial background from constructing
offshore wind power plants.

0885-8950 (c) 2018 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.

You might also like