URS / 01 Date : 11/04/04

USER REQUIREMENT SPECIFICATIONS

Air Filtration
Room Air ( Area ) Exhaust
Sr. Sys. Room Volume ACH Room Filtration Temp. Primary Microvee Terminal Eq. Occup.
Description RH Air
No. No. No. CFM HEPA Load Nos.
(ft3) Class AHU AHU AFM
Room
01 R.M. HOLD 728 30 364
95% 98% 99.997%
Terminal
02 AIR LOCK - 1 530 40 353 25 oC to to to < 40 % 2 hp 1 -
Sys - I HEPA
1 5m 3m 0.3m
( A.C. ) 03 MANUFACTURING 1817 40 1211

3075 1929

05 FILLING / POLISHING / SORTING 2725 40 1817 95% 98% 99.997%


Terminal
25 oC to to to < 40 % 7.5 hp 2 100
Sys - II HEPA
2 06 AIR LOCK - 2 636 30 318 5m 3m 0.3m
( A.C. )
3361 2135

04 QUARANTINE 1557 40 1038 95% 98% 99.997%


Terminal
25 oC to to to @ 60 % - 2 -
Sys - III HEPA
3 07 QUARANTINE 874 40 583 5m 3m 0.3m
( A.C. )
2431 1621

09 BLISTER 2076 40 1384 95% 98% 99.997%


Terminal
25 oC to to to < 40 % 10 kva 4 100
Sys - IV HEPA
4 10 POUCH 1557 40 1038 5m 3m 0.3m
( A.C. )
3634 2422

08 CORRIDOR 2876 40 1918 95% 98% 99.997%


Terminal No
25 oC to to to 8 kva 8 -
Sys - V HEPA Control
5 11 PACKING 5580 40 3720 5m 3m 0.3m
( A.C. )
8457 5638

SHEET 1 OF 1