BARC Specification of Differential Relay For Indent
BARC Specification of Differential Relay For Indent
Advance CT Input, Screw Terminal, I/O module 14 inputs + 6 outputs 24-250V DC and
Communication module 2-wire RS 485 network interface. one of the suitable relay may be
SEPAM series.
Specifications of Differential Relays for Transformers:
Information to bidders:
1. Any deviation in technical specifications shall not be acceptable and
such offers will be rejected.
2. Only those venders/ Manufactures quote those have complete Testing
facility at manufacture ‘s premises.
3. Technical catalogue should be submitted with their quotation.
4. Details of similar supplies shall be submitted with their quotation.
5. Datasheet to be filled by the bidder during submitting their offer, without
filled datasheet offer will be rejected.
DATA SHEET FOR DIFFERENTIAL PROTECTION RELAY
Confirmation /Comments
Sr.No. Parameter Details /Data to Furnished by
Bidder (YES/NO)
Relay should have at least following protection
functions:
• Phase over current
• Earth fault / Sensitive earth fault
• Breaker Failure
• Negative sequence / unbalance
• Thermal overload
1 Protections • Restricted Earth Fault
• Differential Protection
• Over fluxing(V/Hz)
• Under voltage (L-L or L-N)
• Over voltage (L-L or L-N)
• Over frequency
• Under frequency
Differential:
Restraint on energization
Current threshold - 1 to 10 %
Time Delay - 0 to 300 s
Choice of restraint - Conventional & Self-adapting.
Over fluxing (V/Hz):
Set Point 1.03 to 2 pu
Definite time Setting -0.1 to 20000 s
IDMT Setting - 0.1 to 1250 s
Over Current:
Definite time Setting 0.05 to 24 In, Time delay 0.05 s
to 300 s
IDMT Setting 0.05 to 2.4 In, Time Delay 0.1 to 12.5
sec
Settings of
protection Earth Fault:
2 Definite time Setting 0.01 to 15 In0 (min. 0.1 A)
functions
Time Delay 0.05 s to 300 s
IDMT Setting 0.01 to 1 In0 (min. 0.1 A), Time Delay
0.1 to 12.5 sec
Breaker Failure:
Presence of current - 0.2 to 2 In
Operating time 0.05 s to 3 s
Negative Sequence/Unbalance:
Definite time setting - 0.1 to 5 Ib/10% to 500% Time
Delay-0.1 to 300 s
IDMT Setting 0.1 to 1 Ib/ 10% to 100% Time Delay
0.1 to 1s
Under Voltage:
Set point 5 to 100 % of Unp
Time Delay - 0.05 to 300 s
Over Voltage:
Set Point - 50 to 150 % of Unp
Time Delay - 0.05 to 300 s
Frequency:
Over Frequency - Set point 50 to 55 Hz and time
delay 0.1 to 300 s
Under Frequency-Set point 40 to 50 Hz and time
delay 0.1 to 300 s
Thermal Overload:
Time constant Heating T1: 1 to 600 min
Cooling T2: 5 to 600 mn
Alarm and tripping set points
0 to 300 % of rated thermal capacity
Maximum equipment temperature 60 to 200 °C (140
°F to 392 °F)
Tripping curve The relay shall have following IDMT curves:
for phase over SIT, LTI, VIT, EIT, UIT (1), RI
3
current and IEC: SIT/A, LTI/B, VIT/B, EIT/C
Earth Fault IEEE: MI (D), VI (E), EI (F)
The relay shall have following measurement facilities:
• Phase current I1, I2, I3 RMS
Measured residual current I0, calculated I0Σ
Demand current I1, I2, I3
Peak demand current IM1, IM2, IM3
• Voltage U21, U32, U13, V1, V2, V3
4 Metering Residual voltage V0
• Frequency
• Active power P, P1, P2, P3
Reactive power Q, Q1, Q2, Q3
Apparent power S, S1, S2, S3
Peak demand power PM, QM
• Power factor
• Tripping current Trip I1, Trip I2, Trip I3
Phase fault and earth fault trip counters
• Unbalance ratio / negative sequence current
• Harmonic distortion (THD), current and voltage
Ithd, Uthd
Phase displacement
Disturbance recording
Network and Remaining operating time before overload tripping
5 machine Waiting time after overload tripping
diagnostics
Running hours counter / operating time
• Differential current Idiff1, Idiff2, Idiff3
• Through current It1, It2, It3
• CT / VT supervision
• Trip circuit supervision
• Auxiliary power supply monitoring
• Cumulative breaking current
• Watchdog function (The protection functions are
inhibited, the output relays are forced to drop out and
the "Watchdog" output indicates relay protection
functions are not working).
Relay shall have auxiliary input supply range 24 - 250
V DC.
If the auxiliary supply drifts, 2 alarms may be
triggered:
6 Power Supply
• High set point alarm, adjustable from 105 % to 150
% of rated supply (maximum 275 V).
• Low set point alarm, adjustable from 60 % to 95 %
of rated supply (minimum 20 V).
Relay shall have at least 14 digital inputs and 10
Digital Input digital output.
7
and Output There shall be provision increase the number of DI or
DO by adding/removing the I/O module at site.
Exposure to cold
Exposure to dry heat
Climatic
8 Continuous exposure to damp heat
withstand
Salt mist
Influence of corrosion/2-gas test
Emission Tests
Electromagnetic Immunity tests - Radiated disturbances
9
compatibility Immunity to fast transients
Immunity tests - Conducted disturbances
Enclosure safety tests
10 Safety
Electrical safety tests
Relay shall have Modbus RTU communication
protocol on RS485 port.
Relay should have facility to change the
11 Communication
communication protocol to IEC 61850 at site (if
required in future), without disturbing/upgrading the
firmware of relay.
Display Relay shall have LCD with graphical screen with
12
characteristics facility to draw SLD.
13 LEDs Relay shall have at least 9 LEDs.
Programmable software will be supplied along with
14 Software
relays.