Professional Documents
Culture Documents
Current Diff Protections
Current Diff Protections
PERLINDUNGAN PENGHANTARAN
(SETAKAT 132kV)
Unit Perlindungan
Seksyen Latihan Penghantaran
Institut Latihan Sultan Ahmad Shah (ILSAS)
Current Differential
Protection
• TOSHIBA
Unit Perlindungan, Seksyen Latihan Penghantaran - 2007
Institut Latihan TNB - ILSAS
Current Differential
• Teknologi
Digital, ‘Fiber Optic’ digunakan sbg
medium perhubungan
Current Differential
Komunikasi Di Antara CD
• Dua cara CD berkomunikasi, Direct Fiber
dan melalui G.703
Komunikasi Di Antara CD
• Utk jarak jauh pengubah Optic ke Elektrik,
G.703 melalui Multiplex digunakan.
%bias-K2
Trip zone Trip2
/Idiff/=/Ia+Ib+Ic/
Trip1=>
/Idiff/>k1*/Ibias/+Is1
Trip1 Trip2=>
%bias-K1 /Idiff/>k2*/Ibias/+
Is1 [k2-k1]Is2+Is1.
Is2 Ibias
/Ibias/=0.5[/Ia/+/Ib/+/Ic/]
Current Differential
• LFCB- using novel software ‘poll &
answer’ technique.
• Dual slop, %bias/restrain characteristic
– for low level fault (flt. level raise)
– to overcome ct saturation .
LFCB
LFCB
SIEMENS NUMERICAL
CURRENT COMPARISON
PROTECTION
7SD511 RELAY
Current Comparison
• 7SD51* - Siemens
• Current input are digitized & filtered
• Instantaneous Current are compared
with the STORED inst.value measured
2 period earlier.
• The polarity of current changes are
transmitted & monitored both end.
Current Differential
• GRL 100 - Toshiba
• LFCB 102 / 103 - Areva
• REL 561/551 - ABB
Current Comparison
• 7SD512/513 - Siemens
• THANK YOU