0 INTRODUCTION
The design only considers losses by friction. The others can be neglected because it is too
small. The loss by friction could be determined by using Hazen Williams formula.
hf = 10.69 LQ1.852
C1.852 D4.87
Residual head pressure at the end of node could be determined by using Bernoulli equation:
The safe water pressure tested on existing main pipe, 150mmØ pipe is 12.5m.
(Based on original drawing: WRL 1/1)
Qave = ___15.000___
24 x 60 x 60
= 1.7361 x 10-4 m3/s
Q to domestic = Qpeak
= (1.7361 x 10-4) x 2.5
= 4.3402 x 10-4 m3/s
= 4.35 x 10-4 m
= 2.54 x 10-4 m