Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

V 120 STANDARD RESISTANCE & REACTANCE (Extracted From Kab

cos phi 1 2 CORE CONDUCTOR 0.6/1 KV (Copper Conductor, XLPE Ins


P 1126 PVC SHEATHED)

IL DC 9.383333333 Cross DC AC
L mcc 0.175 l 100% 2 Section ResistanceResistance
V D %  I  R DC   
L MV 0.196 1000 VDC N No. mm2 at 20oC at 90oC
(ohm/km) (ohm/km)
VD MCC 1.059144E-05
VD MV
1 2C #2.5 7.41 9.449
rumus 2 2 2C #4 4.61 5.878
VD MCC 1.720903333 3 2C #6 3.08 3.927
VD MV 1.927411733 4 2C #10 1.83 2.334
5 2C #16 1.15 1.467
6 2C #25 0.727 0.927
7 2C #35 0.524 0.669
8 2C #50 0.387 0.494
9 2C #70 0.268 0.342
10 2C #95 0.193 0.247
11 2C #120 0.153 0.196
12 2C #150 0.124 0.16
13 2C #185 0.0991 0.128
14 2C #240 0.0754 0.099
15 2C #300 0.0601 0.08
CTANCE (Extracted From Kabel Metal Indo)
(Copper Conductor, XLPE Insulated, Galvanized Steel Wire Armor,

Reactance Maximum Maximum


at 50 Hz Rated CurrRated CurrInductance
in Air in Ground
(ohm/km) (Ampere) (Ampere) ( mH / km )

0.092086 40 46 0.293
0.086429 53 60 0.275
0.082657 67 75 0.263
0.077943 92 101 0.248
0.0748 122 131 0.238
0.075429 162 169 0.24
0.073229 199 204 0.233
0.072914 240 241 0.232
0.071971 302 295 0.229
0.0704 369 353 0.224
0.070086 427 400 0.223
0.0704 486 447 0.224
0.070714 558 503 0.225
0.070086 655 579 0.223
0.069457 743 646 0.221