Soal Nomor 1

Program MATLAB
%Problem : SHORT CIRCUIT
% The Fault Current, bus voltage and line current is use
% the lgfault, llfault, and dlgfault functions
% Impedansi Urutan
zdata0=[0 1 0.00000 0.05000
0 2 0.00000 0.05000
0 5 0.00000 0.14000
1 2 inf inf
2 3 0.00000 0.10000
2 6 0.00000 0.20000
3 4 0.00000 0.20000
4 6 0.00000 0.10000
4 5 0.00000 0.05000];

zdata1=[0 1 0.00000 0.02000


0 5 0.00000 0.20000
1 2 0.00000 0.20000
2 3 0.00000 0.03000
2 6 0.00000 0.07000
3 4 0.00000 0.07000
4 6 0.00000 0.03000
4 5 0.00000 0.05000];

% Jenis Gangguan
zdata2 = zdata1
Zbus0 = zbuild(zdata0)
Zbus1 = zbuild(zdata1)
Zbus2 = Zbus1;
%disp('(a) Symmetrical three-phase fault')
%symfault(zdata1, Zbus1)
disp('(b) Line-to-ground fault' )
lgfault(zdata0, Zbus0, zdata1, Zbus1, zdata2, Zbus2)
%disp('(c) Line-to-line fault')
%llfault(zdata1, Zbus1, zdata2, Zbus2)
%disp('(d) double line-to-ground fault')
%dlgfault(zdata0, Zbus0, zdata1, Zbus1, zdata2, Zbus2)

Hasil Run Hubung singkat L-G bus 2


zdata2 =

0 1.0000 0 0.0200
0 5.0000 0 0.2000
1.0000 2.0000 0 0.2000
2.0000 3.0000 0 0.0300
2.0000 6.0000 0 0.0700
3.0000 4.0000 0 0.0700
4.0000 6.0000 0 0.0300
4.0000 5.0000 0 0.0500

Zbus0 =

0.0000 + 0.0500i -0.0000 + 0.0000i -0.0000 + 0.0000i -0.0000 + 0.0000i -0.0000 + 0.0000i
-0.0000 + 0.0000i
-0.0000 + 0.0000i 0.0000 + 0.0436i 0.0000 + 0.0372i 0.0000 + 0.0244i 0.0000 + 0.0179i
0.0000 + 0.0308i
-0.0000 + 0.0000i 0.0000 + 0.0372i 0.0000 + 0.1077i 0.0000 + 0.0487i 0.0000 + 0.0359i
0.0000 + 0.0449i
-0.0000 + 0.0000i 0.0000 + 0.0244i 0.0000 + 0.0487i 0.0000 + 0.0974i 0.0000 + 0.0718i
0.0000 + 0.0731i
-0.0000 + 0.0000i 0.0000 + 0.0179i 0.0000 + 0.0359i 0.0000 + 0.0718i 0.0000 + 0.0897i
0.0000 + 0.0538i
-0.0000 + 0.0000i 0.0000 + 0.0308i 0.0000 + 0.0449i 0.0000 + 0.0731i 0.0000 + 0.0538i
0.0000 + 0.1256i
Zbus1 =

0.0000 + 0.0192i 0.0000 + 0.0115i 0.0000 + 0.0110i 0.0000 + 0.0096i 0.0000 + 0.0077i
0.0000 + 0.0102i
0.0000 + 0.0115i 0.0000 + 0.1269i 0.0000 + 0.1206i 0.0000 + 0.1058i 0.0000 + 0.0846i
0.0000 + 0.1121i
0.0000 + 0.0110i 0.0000 + 0.1206i 0.0000 + 0.1393i 0.0000 + 0.1130i 0.0000 + 0.0904i
0.0000 + 0.1153i
0.0000 + 0.0096i 0.0000 + 0.1058i 0.0000 + 0.1130i 0.0000 + 0.1298i 0.0000 + 0.1038i
0.0000 + 0.1226i
0.0000 + 0.0077i 0.0000 + 0.0846i 0.0000 + 0.0904i 0.0000 + 0.1038i 0.0000 + 0.1231i
0.0000 + 0.0981i
0.0000 + 0.0102i 0.0000 + 0.1121i 0.0000 + 0.1153i 0.0000 + 0.1226i 0.0000 + 0.0981i
0.0000 + 0.1405i

(b) Line-to-ground fault

Line-to-ground fault analysis


Enter Faulted Bus No. -> 2

Enter Fault Impedance Zf = R + j*X in complex form (for bolted fault enter 0). Zf = 0

Single line to-ground fault at bus No. 2


Total fault current = 10.0862 per unit

Bus Voltages during the fault in per unit

Bus -------Voltage Magnitude-------


No. Phase a Phase b Phase c
1 0.9224 0.9812 0.9812
2 0.0000 0.8935 0.8935
3 0.0642 0.8934 0.8934
4 0.2069 0.8951 0.8951
5 0.3707 0.9089 0.9089
6 0.1427 0.8952 0.8952

Line currents for fault at bus No. 2

From To -----Line Current Magnitude----


Bus Bus Phase a Phase b Phase c

Soal nomor 2