Cable Calculations For Water Treatment Plant
Cable Calculations For Water Treatment Plant
FOR
WATER TREATMENT
PLANT
Size
3
(35000 m /day)
Calculation of cables from Transformer (1600KVA) to
M.L.T.S.B:-
1600 0.8
I Load = 1944.75
3 0.38
I Cable =I Load x 1.3 ~ 2528.18 A
The cross section area of the cable will be selected (3X300+150) mm2,
cu, XLPE/STA/PVC, Multi – core.
The cable withstands 490 A "Laid in Ground".
2528.18
No. of parallel cables required = 5.1
490
Then, the cable is 6(3X300+150) mm2, cu, XLPE/STA/PVC, Multi – core.
Vm = 0.177 mV
Ib = 1944.75/6 A (Current such pass in one cable of six).
L = 40 mt
0.177 1944.75 / 6 40
Vmltsb 2.2 VOLT
1000
The voltage drop in this cable will be 2.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
2
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is 3(3X300+150) mm2, cu, XLPE/STA/PVC, Multi – core.
Vm = 0.177 mV
Ib = 911.6/3 A (Current such pass in one cable of three).
L = 40 mt
0.177 911.6 / 3 40
Vgen 2.1 VOLT
1000
The voltage drop in this cable will be 2.1 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
5
I Load= 9.5
3 0.38 0.8
I Cable =I Load x 1.3 ~ 12.34 A
The cross section area of the cable will be selected (4X6) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 56 A "Laid in Ground ".
12.3
No. of parallel cables required = 0.21
56
Then, the cable is (4X6) mm2, cu, XLPE/STA/PVC, multi – core.
Vm = 5.191 mV
Ib = 9.5 A
L = 40 mt
5.191 9.5 40
Vc 2 VOLT
1000
The voltage drop in this cable will be 4.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
The cable (4X6) mm2, cu, XLPE/STA/PVC, multi – core is O.K
3
Eng. Mohamed Shaban / 01008873106 -01110997707
Calculation of cables from M.L.T.S.B to Generator
Building S.B.:-
10
I Load= 19
3 0.38 0.8
Vm = 3.094 mV
Ib = 19 A
L = 40 mt
3.094 19 40
Vc 2.3 VOLT
1000
The voltage drop in this cable will be 4.5 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
5
I Load= 9.5
3 0.38 0.8
I Cable =I Load x 1.3 ~ 12.34 A
The cross section area of the cable will be selected (4X6) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 56 A "Laid in Ground ".
12.3
No. of parallel cables required = 0.21
56
4
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is (4X6) mm2, cu, XLPE/STA/PVC, multi – core.
Vm = 5.191 mV
Ib = 9.5 A
L = 230 mt
The voltage drop in this cable will be 13.5 V which is not acceptable as
the maximum permissible for the circuit is 9.5 V.
The cable (4X6) mm2, cu, XLPE/STA/PVC, multi – core is not suitable.
Vm = 3.094 mV
Ib = 9.5 A
L = 230 mt
The voltage drop in this cable will be 8.9 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
20
I Load= 38
3 0.38 0.8
I Cable =I Load x 1.3 ~ 49.3 A
The cross section area of the cable will be selected (4X16) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 96 A "Laid in Ground".
49.3
No. of parallel cables required = 0.51
96
5
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is (4X16) mm2, cu, XLPE/STA/PVC, multi – core.
Vm = 1.982mV
Ib = 38 A
L = 160 mt
1.982 38 160
Vc 12 VOLT
1000
The voltage drop in this cable will be 14.2 V which is not acceptable as
the maximum permissible for the circuit is 9.5 V.
The cable (4X16) mm2, cu, XLPE/STA/PVC, multi – core is not suitable
Vm = 1.276 mV
Ib = 38 A
L = 160 mt
1.276 38 160
Vc 7.7 VOLT
1000
The voltage drop in this cable will be 9.9 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
10
I Load= 19
3 0.38 0.8
I Cable =I Load x 1.3 ~ 24.7 A
The cross section area of the cable will be selected (4X10) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 74 A "Laid in Ground ".
24.7
No. of parallel cables required = 0.33
74
6
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is (4X10) mm2, cu, XLPE/STA/PVC, multi – core.
Vm = 3.094 mV
Ib = 19 A
L = 70 mt
3.094 19 70
Vc 4.1 VOLT
1000
The voltage drop in this cable will be 6.3 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
25
I Load= 47.5
3 0.38 0.8
I Cable =I Load x 1.3 ~ 61.75 A
The cross section area of the cable will be selected (4X25) mm2, cu,
Vm = 1.276 mV
Ib = 47.5 A
L = 120 mt
1.276 47.5 120
Vc 7.2 VOLT
1000
7
Eng. Mohamed Shaban / 01008873106 -01110997707
The voltage drop in this cable will be 9.4 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
25
I Load= 47.5
3 0.38 0.8
I Cable =I Load x 1.3 ~ 61.75 A
The cross section area of the cable will be selected (4X25) mm2, cu,
Vm = 1.276 mV
Ib = 47.5 A
L = 20 mt
1.276 47.5 20
Vc 1.2 VOLT
1000
The voltage drop in this cable will be 3.4 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation, the Bridge motor with Power equal 3 K.W.
3
I Load= 5.7
3 0.38 0.8
8
Eng. Mohamed Shaban / 01008873106 -01110997707
The cross section area of the cable will be selected (4X6) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 56 A "Laid in Ground ".
7.41
No. of parallel cables required = 0.13
56
Then, the cable is (4X6) mm2, cu, XLPE/STA/PVC, multi – core.
Vm = 5.191 mV
Ib = 5.7 A
L = 50 mt
5.191 5.7 50
Vc 1.5 VOLT
1000
The voltage drop in this cable will be 3.7 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation & approved technical offer, the motor with
power 200 K.W. (The starter is s.s)
200
I Load= 359.4
3 0.38 0.89 0.95
The cross section area of the cable will be selected (3X120+70) mm2,
cu, XLPE /PVC, Multi – core.
The cable withstands 245 A "Laid in Duct ".
467.22
No. of parallel cables required = 1.9
245
Then, the cable is 2(3X120+70) mm2, cu, XLPE /PVC, multi – core, for
each motor.
Vm = 0.337 mV
9
Eng. Mohamed Shaban / 01008873106 -01110997707
Ib = 359.4/2 A (Current such pass in one cable of two).
L = 30 mt
0.337 359.4 / 2 30
Vc 1.8 VOLT
1000
30
I Load= 57
3 0.38 0.8
Then, the cable is (4X25) mm2, cu, XLPE /PVC, multi – core.
0.55
I Load= 1.57
3 0.38 0.75 0.71
I Cable =I load x 1.3 ~ 2 A
The cross section area of the cable will be selected (4X2.5) mm2, cu,
XLPE /PVC, Multi – core.
The cable withstands 29 A "Laid in Duct ".
2
No. of parallel cables required = 0.07
29
01
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is (4X2.5) mm2, cu, XLPE /PVC, multi – core, for each
motor.
Calculation of cables from Aux. S.B to Dewatering
Pumps:-
3
I Load= 6.6
3 0.38 0.82 0.842
0.75
I Load= 1.9
3 0.38 0.77 0.762
267.6
I Load= 406.5
3 0.38
Vm = 0.282 mV
02
Eng. Mohamed Shaban / 01008873106 -01110997707
Ib = 406.5/2 A (Current such pass in one cable of two).
L = 130 mt
The voltage drop in this cable will be 9.6 V which is not acceptable as the
maximum permissible for the circuit is 9.5 V.
Vm = 0.241 mV
Ib = 406.5/2 A (Current such pass in one cable of two).
L = 130 mt
The voltage drop in this cable will be 8.5 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
30
I Load= 57.3
3 0.38 0.86 0.925
Il
I∆ = 33
3
I Cable = I∆ x 1.3 ~43 A
The cross section area of the cable will be selected (4X16) mm2, cu,
XLPE /PVC, Multi – core
The cable withstands 75 A "Laid in duct".
43
No. of parallel cables required = 0.57
75
03
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is 2(4X16) mm2, cu, XLPE /PVC, multi – core, for each
motor.
Vm = 1.982 mV
Ib = 33 A
L = 20 mt
1.982 33 20
Vc 1.3 VOLT
1000
The voltage drop in this cable will be 9.8 V which is not acceptable as the
maximum permissible for the circuit is 9.5 V.
The cable 2(4X16) mm2, cu, XLPE/PVC, multi – core is not suitable
Vm = 1.276 mV
Ib = 33 A
L = 20 mt
1.276 33 20
Vc 0.8 VOLT
1000
The voltage drop in this cable will be 9.3 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
75
I Load= 139.6
3 0.38 0.87 0.938
Il
I∆ = 80.6
3
04
Eng. Mohamed Shaban / 01008873106 -01110997707
The cable withstands 210 A "Laid in duct ".
104.78
No. of parallel cables required = 0.49
210
Then, the cable is 2(3X95+50) mm2, cu, XLPE/PVC, multi – core , for each
motor.
Vm = 0.394 mV
Ib = 80.6 A
L = 10 mt
0.394 80.6 10
Vc 0.3 VOLT
1000
The voltage drop in this cable will be 8.8 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
3
I Load= 6.73
3 0.38 0.82 0.826
Vm = 7.731 mV
Ib = 6.73 A
L = 15 mt
05
Eng. Mohamed Shaban / 01008873106 -01110997707
7.731 6.73 15
Vc 0.7 VOLT
1000
3
I Load= 6.73
3 0.38 0.82 0.826
Vm = 7.731 mV
Ib = 6.73 A
L = 15 mt
7.731 6.73 15
Vc 0.7 VOLT
1000
06
Eng. Mohamed Shaban / 01008873106 -01110997707
Calculation of cables from Filter S.B to Sample Pump:-
0.75
I Load= 1.9
3 0.38 0.77 0.762
Vm = 7.731 mV
Ib = 1.9 A
L = 20 mt
7.731 1.9 20
Vc 0.3 VOLT
1000
The voltage drop in this cable will be 8.8 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
5
I Load= 10.6
3 0.38 0.83 0.857
07
Eng. Mohamed Shaban / 01008873106 -01110997707
The cross section area of the cable will be selected (4X6) mm2, cu,
XLPE/PVC, Multi – core.
The cable withstands 45 A "Laid in duct ".
13.9
No. of parallel cables required = 0.30
45
Then, the cable is (4X6) mm2, cu, XLPE/PVC, multi – core.
1.5
I Load= 2.8
3 0.38 0.8
I Cable =I Load x 1.3 ~ 3.7 A
The cross section area of the cable will be selected (4X6) mm2, cu, XLPE
/PVC, Multi – core
The cable withstands 45 A "Laid in duct".
3.7
No. of parallel cables required = 0.08
45
Then, the cable is (4X6) mm2, cu, XLPE /PVC, multi – core, for each disk.
Vm = 3.094 mV
Ib = 20.25 A
L = 20 mt
08
Eng. Mohamed Shaban / 01008873106 -01110997707
3.094 20.25 20
Vc 1.25 VOLT
1000
The voltage drop in this cable will be 9.7 V which is not acceptable as the
maximum permissible for the circuit is 9.5 V.
The cable (4X10) mm2, cu, XLPE/PVC, multi – core is not suitable.
Vm = 1.982 mV
Ib = 20.25 A
L = 20 mt
1.982 20.25 20
Vc 0.8 VOLT
1000
The voltage drop in this cable will be 9.3 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation the panel served loads equal 52.5 KVA.
09
Eng. Mohamed Shaban / 01008873106 -01110997707
52.5
I Load= 79.8
3 0.38
Vm = 0.520 mV
Ib = 79.8 A
L = 15 mt
0.520 79.8 15
Vc 0.6 VOLT
1000
The voltage drop in this cable will be 9.1 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
19.56
I Load= 29.73
3 0.38
Vm = 1.982mV
Ib = 29.73 A
L = 160 mt
The voltage drop in this cable will be 11.6 V which is not acceptable as
the maximum permissible for the circuit is 9.5 V.
The cable (4X16) mm2, cu, XLPE/STA/PVC, multi – core is not suitable
Vm = 1.276 mV
Ib = 29.73 A
L = 160 mt
The voltage drop in this cable will be 8.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
0.25
I Load= 0.79
3 0.38 0.74 0.65
Vm = 13.197 mV
Ib = 0.79 A
L = 30 mt
13.197 0.79 30
Vc 0.3 VOLT
1000
The voltage drop in this cable will be 8.5 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
2
I Load= 4
3 0.38 0.75
22
Eng. Mohamed Shaban / 01008873106 -01110997707
5.2
No. of parallel cables required = 0.14
36
Then, the cable is (4X4) mm2, cu, XLPE /PVC, multi – core.
Vm = 7.731 mV
Ib = 4 A
L = 10 mt
7.731 4 10
Vc 0.3 VOLT
1000
The voltage drop in this cable will be 8.5 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation, the panel served loads equal 52.3 K.V.A.
52.3
I Load= 79.5
3 0.38
23
Eng. Mohamed Shaban / 01008873106 -01110997707
The cross section area of the cable will be selected (3X70+35) mm2, cu,
XLPE/STA/PVC, Multi – core
The cable withstands 220 A " Laid in Ground ".
103.35
No. of parallel cables required = 0.46
220
Vm = 0.520 mV
Ib = 79.5
L = 220 mt
The voltage drop in this cable will be 11.2 V which is not acceptable as
the maximum permissible for the circuit is 9.5 V.
The cable (3X70+35) mm2, cu, XLPE/STA/PVC, multi – core is not suitable
Vm = 0.337 mV
Ib = 79.5
L = 220 mt
3
I Load= 6.95
3 0.38 0.81 0.81
24
Eng. Mohamed Shaban / 01008873106 -01110997707
I Cable =I load x 1.3 ~ 9 A
The cross section area of the cable will be selected (4X6) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 56 A "Laid in Ground ".
9
No. of parallel cables required = 0.16
56
Then, the cable is (4X6) mm2, cu, XLPE/STA/PVC, multi – core
Vm = 5.191 mV
Ib = 6.95 A
L = 20 mt
5.191 9.5 40
Vc 0.7 VOLT
1000
The voltage drop in this cable will be 8.7 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
25
Eng. Mohamed Shaban / 01008873106 -01110997707
Then, the cable is (4X2.5) mm2, cu, XLPE /PVC, multi – core, for each
motor.
Vm = 13.197 mV
Ib = 1.9 A
L = 30 mt
13.197 1.9 30
Vc 0.75 VOLT
1000
The voltage drop in this cable will be 8.75 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
20.96
I Load= 31.85
3 0.38
I Cable =I Load x 1.3 ~ 41.4 A
The cross section area of the cable will be selected (4X16) mm2, cu,
XLPE/PVC, Multi – core.
The cable withstands 75 A "Laid in duct".
41.4
No. of parallel cables required = 0.55
75
Then, the cable is (4X16) mm2, cu, XLPE/PVC, multi – core.
Vm = 1.982 mV
Ib = 31.85 A
L = 30 mt
1.982 31.85 30
Vc 1.8 VOLT
1000
The voltage drop in this cable will be 9.8 V which is not acceptable as the
maximum permissible for the circuit is 9.5 V.
26
Eng. Mohamed Shaban / 01008873106 -01110997707
The cable (4X16) mm2, cu, XLPE/PVC, multi – core is not suitable
Vm = 1.276 mV
Ib = 31.85 A
L = 40 mt
1.276 31.85 30
Vc 1.2 VOLT
1000
The voltage drop in this cable will be 9.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
3
I Load= 6.73
3 0.38 0.82 0.826
Vm = 5.191 mV
Ib = 6.73 A
L = 5 mt
5.191 6.73 5
Vc 0.17 VOLT
1000
27
Eng. Mohamed Shaban / 01008873106 -01110997707
The voltage drop in this cable will be 9.37 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
2.2
I Load= 4.93
3 0.38 0.82 0.826
Vm = 5.191 mV
Ib = 4.93 A
L = 10 mt
The voltage drop in this cable will be 9.45 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation the panel served loads equal 25.73 KVA.
25.73
I Load= 39.1
3 0.38
28
Eng. Mohamed Shaban / 01008873106 -01110997707
I Cable =I Load x 1.3 ~ 50.8 A
The cross section area of the cable will be selected (4X25) mm2, cu,
XLPE/STA/PVC, Multi – core.
The cable withstands 127 A "Laid in Ground".
39.1
No. of parallel cables required = 0.3
127
Then, the cable is (4X25) mm2, cu, XLPE/STA/PVC, multi – core.
Vm = 1.276mV
Ib = 39.1 A
L = 190 mt
The voltage drop in this cable will be 11.6 V which is not acceptable as
the maximum permissible for the circuit is 9.5 V.
The cable (4X25) mm2, cu, XLPE/STA/PVC, multi – core is not suitable
Vm = 0.955 mV
Ib = 39.1 A
L = 190 mt
0.955 39.1 190
Vc 7 VOLT
1000
The voltage drop in this cable will be 9.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
1.5
I Load= 3.67
3 0.38 0.79 0.785
29
Eng. Mohamed Shaban / 01008873106 -01110997707
I Cable =I Load x 1.3 ~ 4.7 A
The cross section area of the cable will be selected (4X6) mm2, cu,
XLPE /PVC, Multi – core.
The cable withstands 45 A "Laid in Duct ".
4.7
No. of parallel cables required = 0.1
45
Then, the cable is (4X6) mm2, cu, XLPE /PVC, multi – core, is for each
motor.
Vm = 5.191 mV
Ib = 3.67 A
L = 10 mt
5.191 3.67 10
Vc 0.2 VOLT
1000
The voltage drop in this cable will be 9.4 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
3
I Load= 6.73
3 0.38 0.81 0.81
2.2
I Load= 5.1
3 0.38 0.81 0.81
5
I Load= 10.12
3 0.38 0.75
Vm = 3.094 mV
Ib = 10.12 A
L = 10 mt
3.094 10.12 10
Vc 0.3 VOLT
1000
30
Eng. Mohamed Shaban / 01008873106 -01110997707
The voltage drop in this cable will be 9.5 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation the panel served loads equal 39.8 KVA.
39.8
I Load= 60.46
3 0.38
Vm = 1.276mV
Ib = 60.46 A
L = 100 mt
The voltage drop in this cable will be 9.9 V which is not acceptable as the
maximum permissible for the circuit is 9.5 V.
The cable (4X25) mm2, cu, XLPE/STA/PVC, multi – core is not suitable
Vm = 0.955 mV
Ib = 60.46 A
L = 100 mt
0.955 60.46 100
Vc 5.7 VOLT
1000
32
Eng. Mohamed Shaban / 01008873106 -01110997707
The voltage drop in this cable will be 7.9 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation, the motor power of Pre & Post Booster
Pump equal 3 K.W. (The starter is D.O.L)
3
I Load= 6.73
3 0.38 0.82 0.826
Vm = 7.731 mV
Ib = 6.73 A
L = 10 mt
7.731 6.73 10
Vc 0.5 VOLT
1000
The voltage drop in this cable will be 8.4 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation , the Motor power of Pump equal 2.2 K.W
(The starter is D.O.L)
2.2
I Load= 5.09
3 0.38 0.81 0.81
33
Eng. Mohamed Shaban / 01008873106 -01110997707
The cross section area of the cable will be selected (4X4) mm2, cu,
XLPE /PVC, Multi – core.
The cable withstands 36 A "Laid in Duct ".
6.6
No. of parallel cables required = 0.18
36
Then, the cable is (4X4) mm2, cu, XLPE /PVC, multi – core for each motor.
Vm = 7.731 mV
Ib = 5.09 A
L = 10 mt
7.731 5.09 10
Vc 0.4 VOLT
1000
The voltage drop in this cable will be 8.3 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
According to power calculation, the motor Power is 0.25 K.W. (the starter
is D.O.L).
0.25
I Load= 0.79
3 0.38 0.74 0.65
Vm = 13.197 mV
34
Eng. Mohamed Shaban / 01008873106 -01110997707
Ib = 0.79 A
L = 30 mt
13.197 0.79 30
Vc 0.3 VOLT
1000
VCT = VCHLORINE +VC = 7.9+ 0.3= 8.2 V
The voltage drop in this cable will be 8.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
4
I Load= 8.8
3 0.38 0.82 0.842
Vm = 7.731 mV
Ib = 8.8 A
L = 10 mt
7.731 8.8 10
Vc 0.7 VOLT
1000
The voltage drop in this cable will be 8.6 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
35
Eng. Mohamed Shaban / 01008873106 -01110997707
According to power calculation, the motor power of Mixer equal 1.5 KW
(The starter is D.O.L)
1.5
I Load= 3.67
3 0.38 0.79 0.785
I Cable =I load x 1.3 ~ 4.7 A
The cross section area of the cable will be selected (4X4) mm2, cu,
XLPE /PVC, Multi – core.
The cable withstands 36 A "Laid in Duct ".
4.7
No. of parallel cables required = 0.13
36
Then, the cable is (4X4) mm2, cu, XLPE /PVC, multi – core for each motor.
Vm = 7.731 mV
Ib = 3.67 A
L = 10 mt
7.731 3.67 10
Vc 0.3 VOLT
1000
The voltage drop in this cable will be 8.2 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
0.75
I Load= 1.9
3 0.38 0.77 0.762
Vm = 13.197 mV
Ib = 1.9 A
L = 30 mt
13.197 1.9 30
Vc 0.75 VOLT
1000
The voltage drop in this cable will be 8.65 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
37
Eng. Mohamed Shaban / 01008873106 -01110997707
The cable withstands 60 A "Laid in Duct".
19.76
No. of parallel cables required = 0.3
60
Then, the cable is (4X10) mm2, cu, XLPE/PVC, multi – core.
Vm = 3.094 mV
Ib = 15.2 A
L = 20 mt
3.094 15.2 20
Vc 0.94 VOLT
1000
The voltage drop in this cable will be 8.84 V which is acceptable as the
maximum permissible for the circuit is 9.5 V.
-------------------------------------------------------------------------------------------------------
38
Eng. Mohamed Shaban / 01008873106 -01110997707