Relay Setting For Transformer Primary and Secondary

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 2

Dwaraganathan's easy guide for 51 & 50 setting

23-TR-2304-01 Trafo
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
43.74 100 5.33
2.5
418.4 600 5.33

23-TR-7220 Trafo
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
17.5 100 6.5
1
1333 1600 6.5

RLSS-26
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
2.8 100 5.26
0.16
213 600 5.26

23-TR-0004 Trafo
Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
14 100 4.3
0.8
1067 1250 4.3

6E-TR- 0002 Trafo


Secondary FLC in A from
MVA Primary FLC in A from ETAP CT Primary in A Impedance in Z%
ETAP
11.1 100 3.9
0.63
840 1250 3.9
Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.55 10.26 0.09 0.82 33
0.87 0.14 3.45

Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.22 3.36 0.04 0.27 33
1.04 0.17 0.433

Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.04 0.66 0.01 0.05 33
0.44 0.07 0.433

Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.18 4.07 0.03 0.33 33
1.07 0.17 0.433

Voltage
OC (51) OC (50) Earth (51) Earth (50)
in kV
0.13 3.53 0.02 0.28 33
0.77 0.13 0.433