3ADW000198R0101 DCS800-A Technical Catalogue e A
3ADW000198R0101 DCS800-A Technical Catalogue e A
3ADW000198R0101 DCS800-A Technical Catalogue e A
Technical catalogue
DCS800 Drive Manuals
Language
Public. number E D I ES F CN
DCS800 Quick Guide 3ADW000191 x p p p p
DCS800 Tools & Documentation CD 3ADW000211 x
DCS800 Converter module
Flyer DCS800 3ADW000190 x x p x p p
Technical Catalogue DCS800 3ADW000192 x x x x p x
Hardware Manual DCS800 3ADW000194 x x p p p p
Firmware Manual DCS800 3ADW000193 x p p p p p
Installation according to EMC 3ADW000032 x
Technical Guide 3ADW000163 x
Service Manual DCS800 3ADW000195 x p
Planning and Start-up for12-Pulse converters 3ADW000196 p
CMA-2 Board 3ADW000136 p
Flyer Hard - Parallel 3ADW000153 p
Drive Tools
DriveWindow 2.x - User’s Manual 3BFE64560981 x
DriveOPC 2.x - User’s Manual 3BFE00073846 x
Optical DDCS Communication Link 3AFE63988235 x
DDCS Branching Units - User´s Manual 3BFE64285513 x
DCS800 Applications
PLC Programming with CoDeSys CoDeSys_V23 x x x
61131 DCS800 target +tool description - Application Program 3ADW000199 x
Winding with the DCS 800XXXXX 3ADW000058
Winder application description
Flyer magnetic application
Magnetic application description
Extension Modules
RAIO-01 Analogue IO Extension 3AFE64484567 x
RDIO-01 Digital IO Extension 3AFE64485733 x
AIMA R-slot extension 3AFE64661442 x
Serial Communication
Drive specific serial communication
NETA Remote diagnostic interface 3AFE64605062 x
Mechanics
The robust and strong
frame body of the cabi-
nets is made from steel
with a thickness of
2.5 mm and all metal
sheets are softline de-
sign to avoid accidents
AC80
A6 DCAxxx 2053-3003A_p5.dsf
A6 DCAxxx 1903-3003A_p5.dsf
A7 DCAxxx 2050-3300A_p4.dsf
Important!
CE mark requires the options EN61800-3 (IEC 1800-3) standard requires the options
EMC procedure/part list check EMC procedure/part list check
EMC filter or dedicated transformer (performed by EMC filter or dedicated transformer (performed by
the customer) the customer)
Cable marking A2 plus
DCA 63x DCS800-A DCS800-A DCA 650
I/O modules
max. 4
FIELD exciter
Advant
S800
DCS800
controller
Converter
AC 800M module
I/O
Incoming
supply
Grafiken_b_p11.dsf
F6
T1 Component list (options)
Excitation contactor K3
F3 Excitation line reactor L3
Excitation fuse F3
AC 800M Excitation autotransformer T3
Excitation unit DCF503B/504B U3
U3
Residual current detection T1
Motor fan starter contactor K6
G1 Motor fan starter thermal overload F60
Motor fan starter fuses F6
Advant controller AC 800M
A22 24 VDC power supply G1
T3
MIN. 500
(can be removed, if necessary)
644
120
120
Q1
2000
2000
220
15 600 15
90
260
25,5
600
90
MIN.100
498
600
644
51
DCS800-A-0020…0350 dimensions group and single drive
260
Cables for:
T1 control, field, 90
AC and DC connection
Q1
F2 F6
K1
T2 K6
.
.
Aux. supply voltage transformer T2
Aux. supply voltage fuses F2
K10
K16
K15
K8
T2
C2b DCAxxx 520-1000A_p2.dsf
T3
MIN. 500
(can be removed, if necessary)
644
120
120
Q1
2000
2000
220
15 800 15
90
260
25,5
600
90
MIN.100
698
600
644
51
Q1
C2b DCAxxx 520-1000A_p1.dsf
F2 F6
K1
T2 K6
Note 4: For more details (e.g. losses and weight) see
L1
F5 F4
tables on page 43 and 44
F60
Note 5: All enclosed converters are available as
U1
K8
230V group and single drives. Group drive require the op-
=
tion horizontal busbars.
< 15A
-
K10
K8
X1;X7
X6
L1 L2 L3
options or the excitation! Please choose the
single drive excitation from the options list.
Note 2: * Wiring see section Basic circuit
diagrams.
T2
A5 DCAxxx 1503-2003A_a_p2.dsf
U3
T3
not visible:
F60, AC 800M
A5 DCAxxx 1503-2003A_c_p4.dsf
MIN. 500
(can be removed, if necessary)
644
120
120
Q10
2000
2000
Q1
220
15 800 600 15
90
260
Cables for: Cables for:
25,5 control and AC connection field and DC connection
600
90 90
MIN.100
698 498
600
644
51 51
260
260
DCS800-A-(900)1200...2000 dimensions group and single drive
90 90
T1
Q10
A5 DCAxxx 1503-2003A_b_p1.dsf
Q1
F2 F3 F6
T2 T3 K6
L1
F5 F4 K3
Note 4: For more details (e.g. losses and weight) see
F60
tables on page 43 and 44
K8 230V Note 5: All enclosed converters are available as
U1 U3
group and single drives. Group drive require the op-
=
tion horizontal busbars.
DCF
Note 6: For easy connection of cables use additional
incoming cabinet DCA 635 (see section Incoming
DCA 635).
M
A5 DCAxxx 1503-2003A_c_p3.dsf
A6 DCAxxx 2053-3003A_p4.dsf
A6 DCAxxx 2053-3003A_p2.dsf
Single_line_DCAxxx-2050_5150_a.dsf
A6 DCAxxx 1903-3003A_p4.dsf
A6 DCAxxx 1903-3003A_p2.dsf
A6 DCAxxx 1903-3003A_a_p3.dsf
Overvoltage
Protection
Single_line_DCAxxx-2050_5150_a.dsf
A7 DCAxxx 2050-3300A_p4.dsf
A7 DCAxxx 2050-3300A_p2.dsf
A7 DCAxxx 2050-3300A_a_p3.dsf
Overvoltage
Protection
Single_line_DCAxxx-2050_5150_a.dsf
A7 DCAxxx 4000-5200A_p4.dsf
A7 DCAxxx 4000-5200A_p2.dsf
A7 DCAxxx 4000-5200A_a_p3.dsf
Overvoltage
Protection
Single_line_DCAxxx-2050_5150_a.dsf
AC
Auxiliary
control
DC
large_drv_principl_d.dsf
Paralleling master Paralleling slave
Configuration of 12-pulse parallel (12-pulse master and follower) in combination with hard
parallel (paralleling master and slave)
A7 Parallel.dsf
The marking is done for long conductors and short End panels
obvious conductors. End panels have to be chosen to make a complete cab-
• Class B1 inet. For a line-up only one pair of panels is needed.
In addition to the marking A2 cable marking pro- Horizontal AC busbars
vides the apparatus symbols. Busbars are used to feed the entire line-up from the
incoming supply section.
Tin plated copper busbars inside the cabinet are op-
tional.
• without AC busbars => single drive
• copper (tin plated possible), 1000 A AC => group drives
• copper (tin plated possible), 2000 A AC => group drives
• copper (tin plated possible), 3000 A AC => group drives
cable mark.dsf
Current rating depends on the power needed. Maxi-
mum current is 3000 A for horizontal AC-busbars. 4000
Standard Design is IP21
A incoming sections should be placed in the middle of
Air inlet 8 mm longitudinal slots, air outlet same as air
a line up, in order to distribute the AC-current to left
inlet plus a air ventilation hood on the top.
and right side.
Note1:
If a line up is splitted into several transportation seg-
ments an additional joining cabinet is needed per
M
segment (except the last segment) for connection.
Note2: DCS800 12p_par.dsf
DCS800 DCS800
1 C1 1 C1
M
DCS800 12p_ser.dsf
Unit type DC I
Power
Size
loss
525 V [A] [kW]
DCS800-F01-0020-05-C 16 0.58
DCS800-F02-0025-05-C 22 0.58
DCS800-F01-0045-05-C 40 0.65
DCS800-F02-0050-05-C 45 0.65
D1
DCS800-F01-0065-05-C 57 0.72
DCS800-F02-0075-05-C 67 0.72
DCS800-F01-0090-05-C 84 0.85
DCS800-F02-0100-05-C 92 0.85
DCS800-F01-0180-05-C 160 1.40
D3 D2
100%
t
A6 DCAxxx 2053-3003A_p5.dsf
Option three phase field exciters assembled in armature Single line diagram DCS800-A-1900 (D6)...5200
circuit enclosed converter DCS800-A0x-1900...5200 (D7) including field supply
Field supply (DCS800-S0x-0020...0350 converter modules,
230... 500 V AC + overvoltage protection)
Field exciters integrated in enclosed converters are avail-
able as packages. The packages includes all necessary
parts (e.g. overvoltage protection DCF 506, line reactor).
Autotransformers for field supply assembled in an enclosed
converter are excluded. ➀
Incoming Supply Sections for Line-ups Cabinet Modifications for Incoming Supply
DCA 63x Sections DCA630, 631, 632
Incomings DCA 63x are described in options for con- CE mark
verters. These cabinets must only be selected if the drive Requires options for EMC regulation and cable mark-
system consists of group drives from 20 up to 2000 A since ing.
these converters are supplied by horizontal busbars.
- EMC procedure according to part list check
In the incoming supply section (DCA 63x) only bus- see section DCS800-A Mechanical options
bars are used. The connection to the AC supply can be - Marking of conductors
made by cables or busbars. The cable / busbar entry is see section DCS800-A Mechanical options
at the bottom of the incoming supply section. • Standard: (not sufficient for CE mark):
Cable or busbar connection for 1000A and 2000A is see section DCS800-A Mechanical options
standard. • Class A2 Plus: Special Marking according to EN60204-1
Cable connection for 3000A and 4000A is on request, see section DCS800-A Mechanical options
busbar connection is standard. • Class B1: Special Marking
The cabinets standard protection class is IP21. see section DCS800-A Mechanical options
Incoming Cabinet
(IP21)
AC-voltage measurement
[transformers > 660 V]
Insulation monitor
(A90, F90)
Horizontal AC busbars
Fuses (F2)
AC line connections
PE busbar
Cable entry
( gland plate)
Inc_630_b.dsf
= Options
single_line_standard.dsf
Incoming Cabinet
(IP21)
AC-voltage measurement
[transformers > 660 V]
Insulation monitor
(A90, F90)
Horizontal AC busbars
Fuses (F2)
AC line connections
PE busbar
Cable entry
( gland plate)
Inc_631_b.dsf
= Options
single_line_standard.dsf
Incoming Cabinet
(IP21)
AC-voltage measurement
[transformers > 660 V]
Insulation monitor
(A90, F90)
Horizontal AC busbars
Fuses (F2)
AC line connections
= Options
single_line_standard.dsf
Inc_635_b.dsf
single_line_standard.dsf
Options
Overvoltage protection
DCF 506 for 3ph - field
Auto- and insulating transformers 24V DC power supply (G1)
An autotransformer is used to have a Converter module (U1)
[DCS800-S0x]
suitable supply voltage level for a field
A10
exciter and to reduce voltage ripple. For
each 3-phase field exciter an autotransfor- Line reactor (L1)
A9
For dimensioning please contact ABB DC field connections
Automation Products GmbH, Ladenburg,
Germany.
Terminals auxiliary
Higher input voltages (> 600 V/690 V) supply voltage (X1:200)
require an insulating transformer. AF100 terminal
PE busbar
Cable entry
(gland plate)
EXC_620_e.dsf
= Options
Basic equipment
Degree of protection IP 21
Converter module U1
Line reactor L1
Transformer T2 only if required
Overvolt. protect. DCF 506
I/O board SDCS-IOB-2x
I/O board SDCS-IOB-3
Fuses auxiliary supply F2
Auxiliary relays K8, K15, K16
Isolation switch Q1
Main contactor K1
DCA62x_single_line.dsf
S800 I/O
first cluster
next cluster
or extension
AF 100 terminal
process cable
wiring
DCA650_b.dsf
The standard design of this control cabinet takes care The amount of process terminals is limited to 180
of the amount of control cables and EMC requirements Attention: The combination with the horizontal busbar
(shielded connection) which limits the amount of S800 option is not possible. So the cabinet must be located
I/O modules. at the end of the line-up.
+
24 V DC digital
process input Options
Process DI810/
Process power supply
process terminal TU810 On request.
This power supply is needed to supply all process
devices outside the cabinet. The rated power and
wiring_AC80encl_d.dsf rated voltage of the active process devices must be
Wiring extended socket considered.
Compact sockets
Shielding busbar
Compact sockets have smaller size, but process terminals
Shielding busbar is an option and used for small
are recommended.
shielded control and process cables.
The cable shielding of the control and process ca-
power power + AC 800M bles must be connected.
+
supply supply
process internal
24 V DC
Shielding of very thick cables should be connected
at the cable entry.
Note: see Installation manual
+ doc.no 3ADW000091.
24 V DC digital
process input Small cable can also be connected at a shielding
busbar located in parallel to the terminals.
DI810/
process TU830
Other mechanical options
see chapter 3
• Horizontal busbars
wiring_AC80encl_d.dsf
• EMC bottom plate
Wiring compact socket • Cable marking A2 plus
Environmental conditions
System connection Environmental limit values
Voltage, 3-phase: 230 to 1000 V acc. to IEC 60038 Permissible cooling air temperat.
Voltage deviation: ±10% continuous; ±15% short-time * - at converter module air inlet: 0 to +55°C
Rated frequency: 50 Hz or 60 Hz with rated DC current: 0 to +40°C
Static frequency deviation: 50 Hz ±2 %; 60 Hz ±2 % w. different DC current +30 to +55°C
Dynamic: frequency range: 50 Hz: ±5 Hz; 60 Hz: ± 5 Hz - Options: 0 to +40°C
df/dt: 17 % / s Relative humidity (at 5...+40°C): 5 to 95%, no condensation
* = 0.5 to 30 cycles. Relative humidity (at 0...+5°C): 5 to 50%, no condensation
Please note: Special consideration must be taken for voltage deviation in regenera- Change of the ambient temp.: < 0.5°C / minute
tive mode.
Storage temperature: -40 to +55°C
Degree of protection
Transport temperature: -40 to +70°C
Converter module and
options (line chokes, fuse Pollution degree (IEC 60664-1, IEC 2
holder, field supply unit, etc.): IP 00 60439-1):
Site elevation
Enclosed converters: IP 20/21/31/41
<1000 m above M.S.L.: 100%, without current reduction
Paint finish
>1000 m above M.S.L.: with current reduction
Converter module: RAL 9002
Enclosed converter: light grey RAL 7035 North American Standards
In North America the system components fulfil the requirements of the
Sound pressure level table below.
Size Sound pressure level LP (1 m distance) Vibration Rated supply Standards
voltage Converter module Enclosed converter
as module enclosed conv. as module
D1 55 dBA ?? dBA to 600 V UL 508 C UL/CSA types: on
Power Conversion Equipment request
D2 55 dBA ?? dBA
CSA C 22.2 No. 14-95
D3 60 dBA ?? dBA 0.5 g, 5...55 Hz Industrial Control Equipment,
D4 66...70 dBA, 77 dBA Industrial Products
depending on fan Available for converter modules
D5 73 dBA 78 dBA including field exciter units.
1 mm, 2...9 Hz Types with UL mark:
D6 75 dBA 73 dBA
0.3 g, 9...200 Hz • see UL Listing www.ul.com /
D7 82 dBA 80 dBA certificate no. E196914
• or on request
>600 V to EN / IEC xxxxx see table above. EN / IEC types: on
1000 V Available for converter modules request (for details
including field exciter units. see table above)
Regulatory compliance
The converter module and enclosed converter components are designed for use in industrial environments. In EEA countries, the components fulfil the
requirements of the EU directives, see table below.
European union directive Manufacturer‘s assurance Harmonized standards
Converter module Enclosed converter
Machinery Directive
98/37/EEC Declaration of Incorporation EN 60204-1 EN 60204-1
93/68/EEC [IEC 60204-1] [IEC 60204-1]
Low Voltage Directive
73/23/EEC Declaration of Conformity EN 60146-1-1 EN 60204-1
93/68/EEC [IEC 60146-1-1] [IEC 60204-1]
EN 61800-5-1 EN 61800-5-1
(EN 50178 [IEC --]) EN 60439-1
see additional [IEC 60439-1]
IEC 60664
EMC Directive
89/336/EEC Declaration of Conformity EN 61800-3 ① EN 61800-3 ①
93/68/EEC (Provided that all installation instructions concern- [IEC 61800-3] [IEC 61800-3]
ing cable selection, cabling and EMC filters or
dedicated transformer are followed.) ① in accordance with ① in accordance with 3ADW
3ADW 000 032 000 032/3ADW 000 091
DCS800-A0x-5200-10PD ➁
DCS800-A0x-6600-10PD ➁ 6200 4655 6982 4465 6697 4370 8740 <45.60
DCS800-A0x-8000-10PD ➁ 7600 5415 8122 5320 7980 5225 10450 <46.80 525 V [A] [kW]
1200 V ON REQUEST DCS800-A21-0020-05-D 16 0.58
DCS800-A0x-2600-12-D ➁ 2600 1900 2850 1830 2745 1850 2775 <21.20 DCS800-A22-0025-05-D 22 0.58
DCS800-A0x-3300-12-D ➁ 3300 2390 3885 2310 3465 2310 4620 <22.80 D7 DCS800-A21-0045-05-D 40 0.65
DCS800-A0x-4000-12-D ➁ 3800 A at 7% uk 4000 A at 14% uk <24.50 DCS800-A22-0050-05-D 45 0.65
D1
DCS800-A21-0065-05-D 57 0.72
Table 1: DCS800-A types DCS800-A22-0075-05-D 67 0.72
DCS800-A21-0090-05-D 84 0.85
* Ratings are valid for IP 21; for IP 31 and IP 41 the current derating DCS800-A22-0100-05-D 92 0.85
x=1 ⇒ 2-Q converter is calculated by DriveSize ➀ = Air circuit breaker on request DCS800-A21-0180-05-D 160 1.40
D2
x=2 ⇒ 4-Q converter ➁ = Air circuit breaker not available ➂ = Reduced current due to DCS800-A22-0200-05-D 180 1.40
P ⇒ hard parallel (two conv. mod. in parallel) standard air circuit breaker. Larger air circuit breakers are available DCS800-A21-0315-05-D 285 1.89
DCS800-A22-0350-05-D 300 1.89
D3
Voltage class: (example: DCS800-A0x-0025-04y-D) on request ➃ with air exit IP20 ⇒ plus 100 A ➄ FEX425 internal DCS800-A21-0405-05-D 340 2.40
04 ⇒ 400V 05 ⇒ 500/525V 06 ⇒ 600V 07 ⇒ 690V field exciter as option; three-phase or single phase, separate DCS800-A22-0450-05-D 380 2.40
supply max. 500 V AC DCS800-A21-0610-05-D 520 3.00
08 ⇒ 800V 10 ⇒ 990V 12 ⇒ 1200V
D4
Notes:
All dimensions are in mm
Please add for each end panel 15 mm and for a door (without buttons) 20 mm
DCA 63x DCS800-A DCS800-A
➀ Height is including detachable hood (120 mm)
➁ with circuit breaker or contactor
➂ without circuit breaker or contactor
➃ DCS800-A with AC supply voltage 3 x 800 V...1200 V or current ≥3300 A
are generally without circuit breaker.
➄ Max length of a shipping split is 3.40 m. If the line-up width is longer Incoming
than 3.40 m busbar joining cabinets are required.
➅ at 600 V (6) and 690 V (7) only available as 2-Q converter
➆ z: Weight for busbars: 1000 A/2000 A=35kg/m; 3000 A=70kg/m
➇ The air circuit breaker stands out of the line-up's front.
Thus 78 mm have to be added to the total depth of the line-up. Grafiken_b_p10.dsf
DCS800-A0x
K16
X7:9 X7:10
X7:11 X7:12 DO3
DO1
X7:13 (K10)
X7:14 Q1
X2:4 Fan
F60 Klixon
X2:5
Main
switch
Pressure
switch at
D2...D7 converter
D7
K15
T2
230V 11 690V
1 12 10 660V
K15 K16 K6 K8 K1
9 600V
F5 8 575V
2 7 525V F2
E-STOP ELECTR. 115V 6 500V
DISCONNECT 13 5 450V
4 415V
3 400V
2 380V
1 1 3 5
14 K1
2 4 6
1 3
L1
K8
2 4
CH 0
Control board (CON-4)
D1...D4
M
DO8 ~
CH 2
Power supply
SDCS-COM-8
depending on the unit type
(POW-4 / PIN-4) (D1...D7)
CH 3
Converter Field
module exciter
COM DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 depending on converter type included
the wiring and the components
Q1, K1, L1 are different
SDCS-IOB-3 X4: 3x AO A10 A9 SDCS-IOB-23
DCS800-A Basic circuit diagrams
X7:1/X7:2
X5:1...10
C1 D1
_
+
K6 K16
K6 K3 K1
K8 (K10)
K8 K1 K15
if there are intermediate terminals the polarities are shown for motoring
T M
+
T
_
dcs8-A ans.dsf
45
46
voltage
supply
Main supply
DCS800-A0x
K16
2 4 6
F60
X7:9 X7:10 1 3 5
X7:11 X7:12 DO3 2 4 6
DO1
X7:13 (K10)
K6
1 3 5
X7:14 Q1
D2...D7 converter
8
D7 365V
K15 350V 7
T2 265V 6
230V 11 690V 250V 5
10 660V 90V 4
K15 K16 K6 K8 K1 1 12
9 600V 60V 3
F5 8 575V 30V 2
2 7 525V 1
F2
E-STOP ELECTR. 115V 6 500V
DISCONNECT 13 5 450V
4 415V
3 400V
2 380V
other 24V
230 V AC
Basic diagram with electrical options
24 V DC
Interface to 1 3
FCI, ext. UPS L1 L3
K8
AC 800 2 4
SDCS-COM-8
depending on the unit type
(POW-4 / PIN-4) (D1...D7) DCS800 Field exciter unit
PC (FEX425 internal)
CH 3
Converter Field
module exciter
X33 COM DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 depending on converter type included
the wiring and the components
Q1, K1, L1 are different
SDCS-IOB-3 X4: 3x AO A10 A9 SDCS-IOB-2x
SDCS-IOB-23
1.5/5mA current source
±10V voltage source
X7:1/X7:2
X5:1...10
C1 D1 X1: 5 3
_ _
+ +
K6 K16
K6 K3 K1
K8 (K10)
K8 K1 K15
PANEL
DCS800PAN
if there are intermediate terminals the polarities are shown for motoring
T M
+
T
option optionional wiring
_
dcs8-A ans.dsf
Type code table for DCS800-A0x drives cabinets Type code table for DCS800-A2x 3-phase field exciters in a
separate cabinet
DCS800 - A02 - 0680 - 05 - D B N DCS800 - A22 - 0100 - 05 - D B N
Cabinet type
D = ABB Drive cabinet
DE = EMC protected ABB Drive cabinet
Cabling
B = Bottom entry / exit
T = Top entry / exit
AC-connection
N = No horizontal busbars / single drive
1 = 1000 A horizontal busbars / group drive
2 = 2000 A horizontal busbars / group drive
Type code table for a DCS800-F0x 3-phase field exciter in the
armature cabinet 1900 A (D6)...5200 A (D7)
DCx_type_code_c.dsf
3 = 3000 A horizontal busbars / group drive
DCS800 - F01
- - 0075 - 05
Module type
related to modul current IP00 e.g. 0075 = 75 A
DC DRIVES INCOMING
Section type Rated AC voltage [V]
30 = incoming with options 4 = 230...400V
DCx_type_code_c.dsf
31 = incoming insulation switch 5 = 415...500V
32 = incoming circuit breaker
35 = incoming without options
Module type
Rated AC current for incoming
Rated AC voltage [V]
4 = 230...400V
5 = 415...500V
6 = 525...600V
7 = 660...690V
Type code table for DCF 50xB 2-phase field exciters (up to 50 A)
Frequency [Hz] in the armature cabinet
5 = 50 Hz
6 = 60 Hz
DC F 50 3 B 0050 - C
Cabinet type
D = ABB Drive cabinet
DE = EMC protected ABB Drive cabinet
DC DRIVES FIELD EXCITER
AC-connection
1 = 1000 A horizontal busbars
2 = 2000 A horizontal busbars
Bridge type
DCx_type_code_c.dsf
3 = 1-Q half contolled
3 = 3000 A horizontal busbars
4 = 4 -Q full controlled
Module type
0007 = 7 A
0017 = 17 A } only DCF 504B DCx_type_code_c.dsf
0033 = 33 A
DCS800-A Components
DCS800-R Rebuild Kit ▅ Proven long life components are re-used, such
Digital control-kit for existing as power stacks, (main) contactors, cabinets and
powerstacks cabling / busbars, cooling systems
▅ Use of up-to-date communication facilities
20 … 20,000 ADC ▅ Increase of production and quality
0 … 1,160 VDC ▅ Very cost-effective solution
230 … 1,200 VAC ▅ Open Rebuild Kits for nearly all existing DC drives