Professional Documents
Culture Documents
Transducer Details
Transducer Details
7 PF Transducer Unipolar, Three Phase Rated Input Voltage: 110VAC Rated Input
Current: 1A PF Range: 0.5 Lead-1-0.5 Lag Transducer Output: 4mA...12.. 20mA
Aux Sup. 240V+/-20% 1Ph 50 Hz Insulation level: 2KV RMS for 1 Min Accuacy:
0.5%, Max Continuous Input Voltage 137.5VAC ,Shot time input voltage: 165V
for 10Sec , Max continous input current: 2A Short time input current: 15A for 10
Sec.Projection Mounting & wiring details shall be submitted alongwith the offer.
8 DC Voltage Transducer input : 0-300 VDC Output: 4-20 mA Dual output, Aux
supply: 220VAC Test voltage: 4KV 50 Hz for 1 min Accuracy : 0.5% or Better.
Projection Mounting & wiring details shall be submitted alongwith the offer.
9 DC Voltage Transducer Input:0-60 mV DC output: 4-20mA Dual output, Aux
Supply: 220VAC Test Voltage: 4KV 50 Hz for 1 Min Accuracy: 0,5% or
Better.Projection Mounting & wiring details shall be submitted alongwith the offer.
10 DC Voltage Transducer Input: 0-40 VDC Output : 4-20 mA Dual output, Aux.
Supply : 230VAC Test voltage: 4KV 50 Hz for 1 min Accuracy : 0.5% or Better.
Projection Mounting & wiring details shall be submitted alongwith the offer.