Professional Documents
Culture Documents
Seismic Behavior of Synthetic Fiber-Reinforced Circular Columns
Seismic Behavior of Synthetic Fiber-Reinforced Circular Columns
Canadian Standard A23.3-04,13 the New Zealand code NZS ture agent were used for the SNFRC. As mentioned previ-
3101:1995,14 and the American code ACI 318M-11.15 NZS ously, the SNFRC for the first column placed (C30S100FP1
3101:1995 and A23.3-04 take into account the axial load with w/c = 0.50) presented workability problems; thus, a
applied to the column for calculating transverse reinforce- high-range water-reducing admixture was added to make
ment. Hence, for all specimens, 25% of Ag fc′ was assumed, the mixture workable. A high slump (130 mm [5.12 in.])
where Ag is the gross area of column section. At this level was then obtained for Specimen C30S100FP1 resulting in
of loading, the column is close to the balanced failure with reduced concrete strength. Those problems were fixed for
an expected under-reinforced flexural failure (that is, longi- the other two SNFRC specimens. Slump was 95, 90, and
tudinal steel yields before concrete crushes). Although not 105 mm (3.74, 3.54, and 4.13 in.) for the NSC Specimens
typical for bridge columns for which values close to 0.1Ag fc′ C30S100FP0, C30S75FP0, and C30S42FP0, respectively;
are usually found, the higher value of axial load used in this and 90 and 100 mm (3.54 and 3.94 in.) for the SNFRC Spec-
research program brings out the effect of confinement more imens C30S75FP1 and C30S42FP1, respectively. Further
clearly, as it is strongly dependent on the level of axial load. information on mixture composition for both types of
Table 1 shows the design results; the selected spacings of 42, concrete can be found in Osorio.16 The specimens were taken
75, and 100 mm (1.65, 2.95, and 3.94 in.) are in bold. These off the formwork the day after casting, covered with wet
values correspond to the maximum spacing required in the burlap, and wrapped in polythene sheets. The columns and
Canadian Standard A23.3-04,13 ductile seismic performance, stub faces were frequently watered to obtain moist curing.
and moderate ductile performance, respectively. All control cylinders and prisms were cured under the same
conditions as the column specimens to estimate the column
Material properties concrete material characteristics as accurately as possible.
Concrete—Premixed normalweight concrete was used to Table 2 summarizes the material properties measured at
vertically cast the NSC and SNFRC specimens. The water- 28 days and on the day of testing. The concrete compres-
binder ratio was 0.50 for all NSC specimens. Because the sive strength at day of testing, which ranged from 30.8 to
concrete strength was lower than expected for Specimen 38.3 MPa (4.51 to 5.55 ksi), was determined from standard
C30S100FP1 (first SNFRC column casted), however, compressive tests on at least three 150 x 300 mm (6 x 12 in.)
the water-binder ratio was reduced to 0.45 for Specimens cylinders. The post-peak strain at 50% of maximum stress,
C30S75FP1 and C30S42FP1. Air-entraining and water‑ εc50u, was determined from the complete stress-strain curves
reducing admixtures were used for the NSC, while an air- obtained from the standard compressive tests, and shown in
entrained admixture and a high-range water-reducing admix- Fig. 3. This strain ranged from 0.0043 to 0.0055. The secant
modulus of elasticity Ec ranged from 16,576 to 22,992 MPa
(2404 to 3335 ksi). The cracking strength of the concrete fr,
obtained from standard modulus of rupture tests on at least
three 100 x 100 x 400 mm (3.94 x 3.94 x 15.75 in.) prisms
for each specimen, ranged from 4.64 to 5.60 MPa (0.67 to
0.81 ksi). As can be seen from Fig. 3, significant increase
in toughness is obtained from SNFRC compared with NSC.
Reinforcement—Two different types of reinforcing bars
were used: 10M (100 mm2 [0.155 in.2]), and 20M (300 mm2
[0.465 in.2]) Grade 400 bars. Complete stress-strain curves
were obtained from test coupons on each of the steel types
used. The averages of at least three steel coupons for each
steel type are shown in Table 3 where fy is the yield stress, εsh
is the strain at the commencement of strain hardening, and εsu
is the ultimate strain corresponding to the ultimate stress fsu.
Synthetic fibers—The synthetic structural fiber used in this
research is extruded from a polypropylene and polyethylene
blend. Given the incompatibility of these two polymers, this
results in self-fibrillating fibers; that is, after introduction of
Fig. 2—Experimental setup. (Note: 1 kN = 0.2248 kip.) the fibers into the concrete mixer, each fiber is transformed
into one unit with several fibrils at its ends. Because of their
low initial surface area and high aspect ratio (74), these
macro-fibers do not tend to ball, allowing for good disper-
sion in the initial phase of the mixing process. Furthermore,
their three-dimensional twisted shape not only facilitates
fiber fabrication and storing in bundles before cutting, it also
enhances fiber dispersibility in the concrete matrix. Once the Fig. 3—Stress-strain curves for NSC and SNFRC measured
fibers are well distributed, and after a few minutes of agita- at 28 days.
tion, they start to fibrillate, and their surface area in contact
with the concrete matrix increases. This yields higher bond Instrumentation and testing procedure
capability to concrete compared with conventional smooth Instrumentation—Each specimen was equipped with elec-
and deformed monofilament fibers. Table 4 presents the trical strain gauges to measure strains in the reinforcing steel,
fiber physical and mechanical properties. The fibers have and with linear potentiometers to calculate the curvature of
high resistance to the alkaline environment of concrete and two sections in the potential plastic-hinge region. Linear
good ultraviolet resistance. Additional details about these variable displacement transducers (LVDTs) were also used
fibers are provided by Trottier and Mahonney.17-19 to measure crack opening and slippage of longitudinal bars.
Each column had a total of 30 strain gauges distributed as
Reinforcing cages follows: six placed on the spiral, three on each side at no
Figure 1 provides the details of the reinforcing cages. more than 300 mm (12 in.) from the stub top (Fig. 1(b));
An average volumetric longitudinal steel-reinforcement eight strain gauges placed on two longitudinal bars at posi-
ratio of 2.50% was provided in each specimen as six 20M tions 1 to 8 as shown in Fig. 1(b); and four strain gauges
Grade 400R deformed bars. The spiral reinforcement was were glued to two other longitudinal bars used as backups.
10M Grade 400W deformed bars. The spirals were equally Two sets of four potentiometers were installed along the
spaced along the total height. As mentioned previously, the theoretical plastic hinge region, which, for the specimens
column top where the lateral load was applied had a square tested, was estimated as 348 mm (13.7 in.) using the equa-
section reinforced with square ties to prevent concrete tion proposed by Priestley et al.20 Lp = 0.8l + 0.022db fy (MPa)
crushing. The stub was designed to prevent excessive (= 0.08l + 0.15db fy [ksi]), where l is column height, db is the
cracking and to provide proper anchorage for the longitudinal longitudinal bar diameter, and fy is the yield strength of the
bars of the column. longitudinal steel reinforcement. One set was supported by
n
∆ Ehyst = ∑ Ei (4)
µ ∆I = 2 (1) i =1
∆ yI
where n is the number of cycles to failure. For comparison
and the idealized sectional ductility is defined as purposes, the dissipated energy is normalized as follows
ϕ2 1 n
µ ϕI = (2) EN = ∑ Ei (5)
ϕ yI ′ ∆ yI
H max i =1
The maximum interstory drift ratio δu is another param- where Hmax′ is the maximum equivalent lateral load, which
eter used to measure the maximum displacement at failure includes the applied horizontal load, and the equivalent hori-
in relation to the element height zontal load due to the P-Δ effect, if applicable.
1 n
Iw = ∑ Hi ∆ i (6)
′ ∆ yI
H max i =1
2
1 n K ∆
DEW = ∑ Ei i i (7)
′ ∆ yI
H max i = 1 K yI ∆ yI
ANALYSIS OF RESULTS
Figure 11 compares the moment-curvature response of
specimen pairs with the same concrete strength and spiral
spacing, one without fibers, and the other with 1% fibers.
According to Fig. 11, for the same spiral spacing, adding
fibers into the concrete matrix can improve the post-peak Fig. 8—Sketches of most damaged regions of specimens.
response of the column. Fiber addition is less effective when (Note: Dimensions in mm [in.].)
the spiral spacing decreases, as can be seen in Fig. 12. For Furthermore, analysis of Specimens C30S100FP1
large spiral spacing (75 mm [2.95 in.]), increasing the spiral and C30S75FP0 responses reveals comparable behav-
spacing while adding fibers to the concrete matrix improves iors. Ductility and energy indexes show that Specimen
the post-peak behavior, as can be seen in Fig. 12(a). In C30S100FP1 performs better than C30S75FP0. For
the case of spiral spacing giving very good confinement, example, the structural and sectional ductility are 9 and
increasing the spiral spacing while adding fibers to the 39% higher, respectively, for Specimen C30S100FP1 than
concrete matrix does not result in any gain, as can be seen for C30S75FP0. Specimen C30S100FP1 dissipates 40%
in Fig. 12(b). Moreover, the loss in rigidity is smaller for more energy than C30S75FP0. Comparing the response
fibrous specimens compared with those without fibers, but of C30S75FP1 with C30S42FP0 reveals that Specimen
with the same amount of transverse steel reinforcement. It C30S42FP0 performs better than C30S75FP1. The pres-
should be noted that an increase in the maximum shear force ence of fibers in the concrete matrix with a spiral spacing of
as well as the maximum bending moment is obtained for 75 mm (2.95 in.) is not sufficient to obtain behavior compa-
fibrous specimens compared with those that are nonfibrous. rable with Specimen C30S42FP0.
In terms of ductility, the SNFRC specimens evidenced an Additionally, three confinement indexes were calculated.
increase of up to 30% in sectional and structural ductility The indexes were developed to correlate the displacement
capacity compared with their NSC counterparts (Table 5). capacity of a column with the effectiveness of confine-
This improvement is also observed in the interstory drift ment. The confinement index Ic has been recommended
ratio. In terms of energy dissipation, the fibrous specimens by ACI-ASCE Committee 441,26 and is defined as ρs fyh/fc′.
with s = 100, 75, and 42 mm (3.94, 2.95, and 1.65 in.) had The effective confinement index Ie′, proposed by Cusson
an increase of 125, 68, and 0%, respectively, in terms of the and Paultre,27 relates the effective yield strength to the
parameter EN, compared with their corresponding nonfibrous geometrical distribution and the amount of confinement
specimens. Moreover, for IW, which indicates the specimen steel. Ie′ is calculated as fle′/fc′, where fle′ is the effective
loading severity, an increase of 108, 61, and 4% was also confinement pressure applied by the tie to the concrete
observed for the SNFRC specimens with s = 100, 75, and core when confined concrete reaches its maximum stress.
42 mm (3.94, 2.95, and 1.65 in.), respectively, compared Further discussion about this index can be found in Cusson
with their corresponding nonfibrous specimens. The DEW and Paultre.27,28 According to Paultre et al.,29 the index Ik,
index follows the same tendency. This agrees with the fact which accounts for the effectiveness of confinement and
that fiber influence in the response is less effective as the the axial load, is the key to understanding the behavior
spiral spacing decreases. of NSC and high-strength concrete (HSC) columns under