Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

ACI STRUCTURAL JOURNAL TECHNICAL PAPER

Title No. 111-S18

Seismic Behavior of Synthetic Fiber-Reinforced Circular


Columns
by Laura Isabel Osorio, Patrick Paultre, Rami Eid, and Jean Proulx
Ductile behavior and high energy-dissipation ability are two essen- few published research studies (for example, Djumbong et
tial properties for a reinforced concrete column part of a struc- al.,2 Nguyen,3 Han et al.,4 and Chernov et al.5) have indicated
ture in a moderate to high seismic region. Concrete design codes positive field experiences with synthetic fiber-reinforced
ensure ductile behavior of columns by setting a requirement for a concrete (SNFRC), and show several advantages over SFRC.
minimum amount of transverse steel reinforcement. Studies have
For example, synthetic fibers melt during a fire, allowing the
shown, however, that use of fiber-reinforced concrete (FRC) can
steam pressure inside the concrete to dissipate through the
enhance the post-peak behavior and hence, the ductility and energy
dissipation ability of concrete columns subjected to axial force pathways left by the melted fibers, reducing the risk of severe
and bending moment. Therefore, the inclusion of macro fibers in spalling.4 This does not occur with SFRC. SNFRC elements
the concrete mixture, combined with a reduced amount of lateral placed in aggressive environments will have a better appear-
reinforcement, can be an alternative to the conventional lateral ance than those made of SFRC because the surface of
reinforcement required by the codes. Moreover, the higher resis- elements containing steel fibers will corrode with time.5
tance to crack growth and the excellent durability of FRC over Interest remains in examining structural applications of
nonfibrous concrete can result in a higher cost-effective value. In SNFRC. Such research will lead to analytical models and
this regard, tests on large-scale circular synthetic fiber-reinforced appropriate design procedures. A variety of SNFRC struc-
concrete (SNFRC) columns subjected to a combined constant axial tural applications could be developed once engineers are
load and reversed cyclic flexure simulating earthquake loading
familiar with the benefits and design procedures of SNFRC.
were carried out. The aim of this test program was to examine the
influence of adding synthetic fibers to the concrete mixture on the
behavior of normal-strength concrete (NSC) columns. The results RESEARCH SIGNIFICANCE
show that, in terms of ductility and energy dissipation, SNFRC Improving the seismic performance of structural elements
columns outperformed NSC columns. The results also show that the is an important issue. Concrete design codes ensure the ductile
larger the amount of lateral reinforcement the smaller the influence behavior of columns by setting minimum requirements for
of the fibers on the column’s behavior. Based on the test results, transverse steel reinforcement. Studies have shown, however,
the amount of confinement steel required by concrete design codes that FRC can enhance the post-peak behavior and, hence,
could be reduced when SNFRC is used. the ductility and energy-dissipation capacity of concrete
columns subjected to axial loading.6-12 The higher resistance
Keywords: circular columns; cyclic flexure; ductility; energy dissipation;
seismic behavior; synthetic fiber-reinforced concrete.
to crack growth and excellent durability of FRC over nonfi-
brous concrete can result in higher cost-effective value. This
INTRODUCTION paper presents tests on large-scale circular SNFRC columns
Technology advances in recent decades have allowed the subjected to a combined constant axial load and reversed
development and use of fibers as a component in concrete cyclic flexure simulating earthquake loading. The main objec-
mixtures. Fiber-reinforced concrete (FRC) is concrete with tive of the research program was to study the seismic behavior
randomly distributed discrete fibers. Incorporating fibers of circular SNFRC columns subjected to constant axial load,
in the concrete matrix offers several advantages, such as while relating the amount of transverse reinforcement and the
shrinkage reduction (cracking control), enhanced toughness volumetric synthetic fiber ratio to the gain in ductility, energy
and tensile strength, and improved strain characteristics dissipation, resistance, and reduction of damage.
when cracking occurs. Furthermore, FRC has been found to
be more impermeable; thus, corrosion of the reinforcement EXPERIMENTAL INVESTIGATION
and the required maintenance cost could be minimized. The Test specimens
main use of FRC is in nonstructural elements and non-prin- Six large-scale circular reinforced-concrete columns were
cipal structural elements such as slabs-on-grade, pools, and tested in this experimental research study under combined
ground slope stabilization. Its use in structural elements, constant axial load and reversed cyclic flexure. The column
while permitted in some codes, is still the subject of research. diameter was 305 mm (12 in.). The total height was 2610 mm
Despite a large variety of fibers developed for FRC (steel, (102.76 in.), including the massive I-shape rigid stub at the
glass, natural, and synthetic fibers), research studies on base. The height of the base stub was 500 mm (19.69 in.)
structural applications tended to focus on steel and synthetic ACI Structural Journal, V. 111, No. 1, January-February 2014.
fibers. Since 1988, ACI Committee 5441 has reported design MS No. 2012-055, doi:10.14359/51686517, was received February 15, 2012, and
reviewed under Institute publication policies. Copyright © 2014, American Concrete
considerations for steel fiber-reinforced concrete (SFRC) Institute. All rights reserved, including the making of copies unless permission is
obtained from the copyright proprietors. Pertinent discussion including author’s
limited to some structural applications. On the other hand, closure, if any, will be published ten months from this journal’s date if the discussion
is received within four months of the paper’s print publication.

ACI Structural Journal/January-February 2014 189


Fig. 1—Reinforcing cage and instrumentation details. (Note: Dimensions in mm; 1 mm = 0.0394 in.)
(Fig. 1), sufficient to anchor the six 20 mm (0.79 in.) diam- fined compressive concrete strength fc′, in MPa. The second
eter longitudinal bars. The 180 mm (7.09 in.) high column term, S_, indicates the pitch of the spiral in mm. The third term,
head was built as a square section to facilitate installation of FP_, indicates the volumetric percentage of synthetic fibers.
the horizontal hydraulic actuator. The application point of the For example, C30S75FP1 refers to a column with fc′ = 30 MPa
lateral force was located at 2000 mm (78.74 in.) from the top of (4.35 ksi), having a spiral with a center-to-center spacing of
the base stub. The specimens could represent a 4.0 m (157.48 75 mm (2.95 in.) and a volumetric synthetic fiber ratio of 1%.
in.) high column in a typical building assuming that the point
of contraflexure is located at approximately mid-column Test variables
height, or a 1/3-scale bridge column with the point of contra- As stated previously, this research program studied
flexure located at approximately 1/3 of the height. This corre- the effects of discrete fibers added to the concrete matrix
sponds to a height-width ratio ranging from 6 to 13, which on cyclic flexural behavior of circular concrete columns.
was chosen to avoid shear-critical columns as this research It also intended to determine if this fiber content allowed
program concentrates on flexural behavior. The concrete an increase in the spacing of transverse reinforcement.
columns and stubs were cast vertically in a single placement. Therefore, the specimen test variables were: 1) the volu-
Proper placement of the concrete was ensured with the use of metric fiber percentage in the concrete mixture nf; and 2)
a concrete vibrator. Figure 2 shows the experimental setup. the spacing of the transverse steel reinforcement s. Values
Column identification uses a nomenclature composed of of 0 and 1% were fixed for nf. Values of s were determined
three terms. The first term, C_, indicates the specified uncon- from a seismic design using three concrete design codes: the

190 ACI Structural Journal/January-February 2014


Table 1—Design results for spacing of transverse reinforcement
CSA A23.3-046 NZS 3101:19957 ACI 318M-058
Clause s, mm (in.) Clause s, mm (in.) Clause s, mm (in.)
21.4.4.2(a) 213 (8.39) 276 (10.87) 21.4.4.1 178 (7.01)
Ductile 8.5.4.3(a)
21.4.4.3 75 (2.95) 75 (2.95) 21.4.4.2 75 (2.95)
21.7.2.2.5(a) 284 (11.18) 8.4.7.1(a)(i) 389 (15.31) — —
Moderate ductility
21.7.2.2.3 150 (5.91) 8.4.7.1(a)(ii) 100 (3.94) — —
7.6.4 42 (1.65) — —
Minimum provisions 10.9.3 108 (4.25)
10.9.4 108 (4.25) — —

Canadian Standard A23.3-04,13 the New Zealand code NZS ture agent were used for the SNFRC. As mentioned previ-
3101:1995,14 and the American code ACI 318M-11.15 NZS ously, the SNFRC for the first column placed (C30S100FP1
3101:1995 and A23.3-04 take into account the axial load with w/c = 0.50) presented workability problems; thus, a
applied to the column for calculating transverse reinforce- high-range water-reducing admixture was added to make
ment. Hence, for all specimens, 25% of Ag fc′ was assumed, the mixture workable. A high slump (130 mm [5.12 in.])
where Ag is the gross area of column section. At this level was then obtained for Specimen C30S100FP1 resulting in
of loading, the column is close to the balanced failure with reduced concrete strength. Those problems were fixed for
an expected under-reinforced flexural failure (that is, longi- the other two SNFRC specimens. Slump was 95, 90, and
tudinal steel yields before concrete crushes). Although not 105 mm (3.74, 3.54, and 4.13 in.) for the NSC Specimens
typical for bridge columns for which values close to 0.1Ag fc′ C30S100FP0, C30S75FP0, and C30S42FP0, respectively;
are usually found, the higher value of axial load used in this and 90 and 100 mm (3.54 and 3.94 in.) for the SNFRC Spec-
research program brings out the effect of confinement more imens C30S75FP1 and C30S42FP1, respectively. Further
clearly, as it is strongly dependent on the level of axial load. information on mixture composition for both types of
Table 1 shows the design results; the selected spacings of 42, concrete can be found in Osorio.16 The specimens were taken
75, and 100 mm (1.65, 2.95, and 3.94 in.) are in bold. These off the formwork the day after casting, covered with wet
values correspond to the maximum spacing required in the burlap, and wrapped in polythene sheets. The columns and
Canadian Standard A23.3-04,13 ductile seismic performance, stub faces were frequently watered to obtain moist curing.
and moderate ductile performance, respectively. All control cylinders and prisms were cured under the same
conditions as the column specimens to estimate the column
Material properties concrete material characteristics as accurately as possible.
Concrete—Premixed normalweight concrete was used to Table 2 summarizes the material properties measured at
vertically cast the NSC and SNFRC specimens. The water- 28 days and on the day of testing. The concrete compres-
binder ratio was 0.50 for all NSC specimens. Because the sive strength at day of testing, which ranged from 30.8 to
concrete strength was lower than expected for Specimen 38.3 MPa (4.51 to 5.55 ksi), was determined from standard
C30S100FP1 (first SNFRC column casted), however, compressive tests on at least three 150 x 300 mm (6 x 12 in.)
the water-binder ratio was reduced to 0.45 for Specimens cylinders. The post-peak strain at 50% of maximum stress,
C30S75FP1 and C30S42FP1. Air-entraining and water‑ εc50u, was determined from the complete stress-strain curves
reducing admixtures were used for the NSC, while an air- obtained from the standard compressive tests, and shown in
entrained admixture and a high-range water-reducing admix- Fig. 3. This strain ranged from 0.0043 to 0.0055. The secant
modulus of elasticity Ec ranged from 16,576 to 22,992 MPa
(2404 to 3335 ksi). The cracking strength of the concrete fr,
obtained from standard modulus of rupture tests on at least
three 100 x 100 x 400 mm (3.94 x 3.94 x 15.75 in.) prisms
for each specimen, ranged from 4.64 to 5.60 MPa (0.67 to
0.81 ksi). As can be seen from Fig. 3, significant increase
in toughness is obtained from SNFRC compared with NSC.
Reinforcement—Two different types of reinforcing bars
were used: 10M (100 mm2 [0.155 in.2]), and 20M (300 mm2
[0.465 in.2]) Grade 400 bars. Complete stress-strain curves
were obtained from test coupons on each of the steel types
used. The averages of at least three steel coupons for each
steel type are shown in Table 3 where fy is the yield stress, εsh
is the strain at the commencement of strain hardening, and εsu
is the ultimate strain corresponding to the ultimate stress fsu.
Synthetic fibers—The synthetic structural fiber used in this
research is extruded from a polypropylene and polyethylene
blend. Given the incompatibility of these two polymers, this
results in self-fibrillating fibers; that is, after introduction of
Fig. 2—Experimental setup. (Note: 1 kN = 0.2248 kip.) the fibers into the concrete mixer, each fiber is transformed

ACI Structural Journal/January-February 2014 191


Table 2—Concrete characteristics on test day
Specimen fc′, 28 days, MPa (ksi) fc′, MPa (ksi) εc′ Ec, MPa (ksi) εc50u fr, MPa (ksi) Test day
C30S100FP0 32.6 (4.72) 34.3 (4.97) 0.00232 22.277 (3.224) 0.0045 5.60 (0.81) 85
C30S100FP1 27.6 (4.00) 30.8 (4.47) 0.00263 19.281* (2.796) 0.0051 4.58 (0.66) 120
C30S75FP0 34.4 (4.99) 36.0 (5.22) 0.00236 22.992 (3.335) 0.0043 5.38 (0.78) 128
C30S75FP1 36.3 (5.26) 38.0 (5.51) 0.00264 21.693 (3.146) 0.0054 5.24 (0.76) 83
C30S42FP0 29.4 (4.26) 31.1 (4.51) 0.00227 21.292 (3.088) 0.0045 4.64 (0.67) 119
C30S42FP1 36.3 (5.26) 38.3 (5.5) 0.00265 21.402 (3.104) 0.0055 5.42 (0.79) 84
*
Measured at 28 days.

Table 3—Steel characteristics


Steel type fy, MPa (ksi) εsh εsu fsu, MPa (ksi)
20M 438 (63.5) 0.00792 0.1108 702 (101.8)

No. 10M (spiral)


s = 75 and 100 mm 445 (64.5) 0.01370 0.1378 625 (90.6)
(3.94 and 2.95 in.)

No. 10M (spiral)


445 (64.5) 0.01303 0.1339 626 (90.8)
s = 42 mm (1.65 in.)

Table 4—Physical and mechanical properties of


synthetic fibers
Specific gravity 0.92
Tensile strength 600 to 650 MPa (87 to 94 ksi)
Modulus of elasticity 5.0 GPa (725 ksi)
Fiber length 50 mm (1.97 in.)
Aspect ratio 74

into one unit with several fibrils at its ends. Because of their
low initial surface area and high aspect ratio (74), these
macro-fibers do not tend to ball, allowing for good disper-
sion in the initial phase of the mixing process. Furthermore,
their three-dimensional twisted shape not only facilitates
fiber fabrication and storing in bundles before cutting, it also
enhances fiber dispersibility in the concrete matrix. Once the Fig. 3—Stress-strain curves for NSC and SNFRC measured
fibers are well distributed, and after a few minutes of agita- at 28 days.
tion, they start to fibrillate, and their surface area in contact
with the concrete matrix increases. This yields higher bond Instrumentation and testing procedure
capability to concrete compared with conventional smooth Instrumentation—Each specimen was equipped with elec-
and deformed monofilament fibers. Table 4 presents the trical strain gauges to measure strains in the reinforcing steel,
fiber physical and mechanical properties. The fibers have and with linear potentiometers to calculate the curvature of
high resistance to the alkaline environment of concrete and two sections in the potential plastic-hinge region. Linear
good ultraviolet resistance. Additional details about these variable displacement transducers (LVDTs) were also used
fibers are provided by Trottier and Mahonney.17-19 to measure crack opening and slippage of longitudinal bars.
Each column had a total of 30 strain gauges distributed as
Reinforcing cages follows: six placed on the spiral, three on each side at no
Figure 1 provides the details of the reinforcing cages. more than 300 mm (12 in.) from the stub top (Fig. 1(b));
An average volumetric longitudinal steel-reinforcement eight strain gauges placed on two longitudinal bars at posi-
ratio of 2.50% was provided in each specimen as six 20M tions 1 to 8 as shown in Fig. 1(b); and four strain gauges
Grade 400R deformed bars. The spiral reinforcement was were glued to two other longitudinal bars used as backups.
10M Grade 400W deformed bars. The spirals were equally Two sets of four potentiometers were installed along the
spaced along the total height. As mentioned previously, the theoretical plastic hinge region, which, for the specimens
column top where the lateral load was applied had a square tested, was estimated as 348 mm (13.7 in.) using the equa-
section reinforced with square ties to prevent concrete tion proposed by Priestley et al.20 Lp = 0.8l + 0.022db fy (MPa)
crushing. The stub was designed to prevent excessive (= 0.08l + 0.15db fy [ksi]), where l is column height, db is the
cracking and to provide proper anchorage for the longitudinal longitudinal bar diameter, and fy is the yield strength of the
bars of the column. longitudinal steel reinforcement. One set was supported by

192 ACI Structural Journal/January-February 2014


metallic rings measuring the average concrete displacement
over a gauge length of 400 mm (15.75 in.), and another set
was supported by two steel rods passing through the concrete
core (placed before concrete placement), measuring average
concrete displacement over a gauge length of 210 mm
(8.27 in.) (Fig. 1(d)). Moreover, four LVDTs were supported
by a metallic ring and placed 25 mm (1 in.) from the stub
top to measure crack opening and longitudinal-bar slippage.
All measurement devices were connected to an acquisition
system, which was also connected to the testing software
used to control the hydraulic actuators.
Test procedure—At the beginning of the test, the axial
load was applied manually until reaching the target value of
0.25Ag fc′. The test was then divided into two stages: lateral
cyclic loading under force control during the first cycle at
a rate of 0.375 kN/s (84.3 lb/s), and lateral cyclic loading
under displacement control from the second cycle to the end
of the test at a rate of 0.30 mm/s (0.012 in./s) (Fig. 4). Fig. 4—Loading history.
During the first stage of the test, the horizontal force was (first cycle of 3.0Δy) without any sign of detachment of the
applied under force control to a maximum of 75% of the concrete cover on one side of the column. The delayed
theoretical horizontal load Hy, causing the first yielding of the crushing of concrete is due mainly to the greater toughness
longitudinal bars. The main goal of this cycle was to crack the of SNFRC compared with NSC, as evidenced by the average
section. After completing this cycle, the second cycle started strain at 50% of peak stress εc50u = 0.0053 for SNFRC, and
under displacement control to reach the yielding displace- εc50u = 0.0044 for NSC. Also, the plane of weakness formed
ment defined as the point at which the longitudinal bars first by the transverse reinforcement spiral is less preeminent for
yielded in tension (this criterion was taken specifically for this the specimen with the 100 mm (3.94 in.) spiral pitch than
column section because it represents the global yielding of the other specimens with smaller spacing between turns of
the section given by its shape and steel-reinforcement place- the spirals. Generally, specimen failure was predominantly
ment). Once the yielding displacement was reached on each by rupture of longitudinal bars in tension. It should be noted,
side of the column, an average of these values was calculated however, that these bars experienced buckling in previous
and defined as the experimental yielding displacement, Δyexp. cycles, which may have decreased their ultimate tension
This concluded the first stage of the test. By the second stage, strain. No spiral failure was observed. Results in the form
still under displacement control, the second cycle of 1.0Δy of load-displacement and moment-curvature relationships
was repeated using the experimental yielding displacement. are presented in Fig. 5 and 6, respectively. No correction
Thereafter, each cycle at 1.5, 2, 3,... times Δyexp was repeated due to the P-Δ effect was necessary because the setup was
twice until column failure. The test ended when at least one configured to ensure this effect was negligible. As can be
of the following events occurred: 1) the column was unable to seen from Fig. 5, the specimens with fibers show signifi-
sustain axial load, characterized by a 10% loss of the applied cant improvement in terms of ductility (approximately 30%
axial load; 2) a drop of more than 50% of the maximum flex- increase in ductility for specimens with 100 mm and 75 mm
ural capacity was experienced; or 3) longitudinal bar rupture [3.94 and 2.95 in.] spiral pitch), energy dissipation measured
(by buckling or tension) or spiral rupture, inducing a large as the area under the hysteretic curves (225% increase for
drop in flexural capacity. Due to safety reasons, the test was the specimen with 100 mm [3.94 in.] spiral pitch and 68%
ended in some cases without fulfilling the previous criteria, for the specimen with the 75 mm [2.95 in.] spiral pitch),
but with at least one criterion nearly achieved. and capacity to keep the strength after a number of cycles
at large ductility demand. This is particularly visible for
TEST RESULTS specimens with a 100 and 75 mm (3.94 and 2.95 in.) spiral
General behavior pitch. The average curvature in Fig. 6 was calculated from
During the initial part of loading, cracks in the cover the set of four potentiometers with average gauge lengths of
were slightly smaller in columns with fibers, compared with 210 mm (8.27 in.) (refer to Section C-C in Fig. 1(d)). Four
those without fibers. The minimum compressive strain at important events are also pointed out on each curve: cover
the extreme fiber of the reinforced concrete circular cross spalling for NSC or concrete crushing for SNFRC, yielding
section corresponding to the first sign of cover crushing of the longitudinal bars, the first spiral yielding, and the loss
was 0.0040 and 0.0043 for Specimens C30S100FP0 and of capacity, either due to a loss in flexural capacity or to
C30S100FP1, respectively. The average values were 0.0043 bar rupture. The point defining cover spalling or concrete
for NSC column specimens, and 0.0047 for SNFRC column crushing corresponds to the first visible detachment of the
specimens. Significant crushing accompanied with visible concrete cover, even if portions remained hanging from the
detachment of the concrete cover occurred between the column. The figures show that addition of synthetic fibers
fourth (first cycle of 1.5Δy) and sixth cycles (first cycle of to the concrete mixture enhances the behavior of the RC
2.0Δy). Only Column C30S100FP1 reached the eighth cycle

ACI Structural Journal/January-February 2014 193


Fig. 5—Lateral load versus tip displacement. (Note: 1 MPa = 145 psi.)
columns; however, this enhancement decreases with the Ductility and energy dissipation
reduction of the spiral spacing. Generally, the seismic behavior of columns is assessed
Figure 7 shows the appearance of all specimens after testing. according to ductility and energy-based indicators. Ductility
SNFRC specimens evidenced less damage than the NSC spec- means the ability of a structure to undergo large amplitude
imens. Cover spalling was prevented by fiber presence, with cyclic deformations in the inelastic range without substantial
the damage state corresponding to concrete crushing in the reduction in strength.21 Therefore, the ductility parameters
plastic-hinge region. Figure 8 shows the diagrams of the most used herein, formulated in terms of displacement and curva-
damaged region for each column, where cover spalling for ture, allow this expression in nondimensional terms. Ener-
NSC specimens or concrete crushing for SNFRC specimens gy-based indicators are related to energy-dissipation capacity
and the fractured zone are indicated. As can be seen from Fig. and damage. Before calculating these indicators, the average
7 and 8, the damage zone in the NSC columns is approxi- envelope curve was estimated from the cyclic response of
mately 1.5 to 2.5 times the column diameter, while for SNFRC each specimen, using the formulation shown in Fig. 9.22
columns, it is approximately equal to the column diameter. From the load-displacement envelope, a bilinear diagram
In all specimens, however, regions just above the stub were is derived because all indicators are defined using this type
not damaged, although they were subjected to the maximum of response.21,23 The ascending part of the curve is defined as
moment. This behavior is generally attributed to confinement a straight line from the origin passing through the envelope
to the sections provided by the base stub in its immediate curve at a load of 0.75Hmax′ or at the yielding load (which-
vicinity. The maximum spacing between turns of the spiral of ever is less), and it is then extended until the intersection
1/6 of the core diameter permitted by the Canadian Standard with Hmax′. Herein, Hmax′ is defined as the maximum hori-
seems overly conservative, as no buckling of the longitudinal zontal load carried by the column after the yielding point,
reinforcement occurred. It should be noted that the ACI code which indicates the beginning of the post-peak behavior of
does not have such a limit on the spacing of the spiral pitch. the columns. The second part of the ideal curve is defined as
a straight line from the new point already found (ΔyI, Hmax′)

194 ACI Structural Journal/January-February 2014


Fig. 6—Experimental moment-curvature responses.
to a second point (Δ2, H2′) at the failure displacement Δ2, ∆2
which is taken at a load equal to 80% of Hmax′, ensuring that δu = (3)
l
the area under the ideal curve is the same as the one under
the envelope curve. The displacement of these two points at
the bilinear curve are the idealized yielding displacement ΔyI, where l = 2000 mm (78.74 in.) is the column height. This
and the idealized ultimate displacement Δ2 (Fig. 10). This parameter is plotted on the top horizontal axes in Fig. 5.
procedure is repeated with the moment-curvature response For flexural cyclic loading, the energy dissipated during
to obtain the idealized yielding curvature ϕyI and the ideal- one cycle i, Ei, is described by the hatched area in Fig. 9.
ized ultimate curvature ϕ2. The total dissipated energy during the test Ehyst, until 80% of
The idealized structural ductility is defined as conventional failure or bar rupture is reached is

n
∆ Ehyst = ∑ Ei (4)
µ ∆I = 2 (1) i =1
∆ yI

where n is the number of cycles to failure. For comparison
and the idealized sectional ductility is defined as purposes, the dissipated energy is normalized as follows

ϕ2 1 n
µ ϕI = (2) EN = ∑ Ei (5)
ϕ yI ′ ∆ yI
H max i =1

The maximum interstory drift ratio δu is another param- where Hmax′ is the maximum equivalent lateral load, which
eter used to measure the maximum displacement at failure includes the applied horizontal load, and the equivalent hori-
in relation to the element height zontal load due to the P-Δ effect, if applicable.

ACI Structural Journal/January-February 2014 195


Fig. 7—Photographs of damaged regions and plastic hinge zones for all specimens.

196 ACI Structural Journal/January-February 2014


The work index Iw, proposed by Gosain, Brown and Jirsa,24
helps in comparing loading severity on the performance of
the elements with the same loading history. It is defined as

1 n
Iw = ∑ Hi ∆ i (6)
′ ∆ yI
H max i =1

A damage index DEW, which combines the cyclic dissi-


pated energy and the elastic energy is defined as25

2
1 n  K  ∆ 
DEW = ∑ Ei  i   i  (7)
′ ∆ yI
H max i = 1  K yI   ∆ yI 

where Ki and Δi are defined in Fig. 9.


Table 5 gives the values of all indexes μΔI, μϕI, EN, IW, and
DEW for all specimens. Furthermore, important variables,
such as the measured concrete compressive strength fc′; the
section diameter D; the core diameter Dc; the spiral spacing
s; the volumetric spiral ratio ρs; Hmax′; ΔyI; and ϕyI, defined
previously, are summarized in Table 5 for each column.

ANALYSIS OF RESULTS
Figure 11 compares the moment-curvature response of
specimen pairs with the same concrete strength and spiral
spacing, one without fibers, and the other with 1% fibers.
According to Fig. 11, for the same spiral spacing, adding
fibers into the concrete matrix can improve the post-peak Fig. 8—Sketches of most damaged regions of specimens.
response of the column. Fiber addition is less effective when (Note: Dimensions in mm [in.].)
the spiral spacing decreases, as can be seen in Fig. 12. For Furthermore, analysis of Specimens C30S100FP1
large spiral spacing (75 mm [2.95 in.]), increasing the spiral and C30S75FP0 responses reveals comparable behav-
spacing while adding fibers to the concrete matrix improves iors. Ductility and energy indexes show that Specimen
the post-peak behavior, as can be seen in Fig. 12(a). In C30S100FP1 performs better than C30S75FP0. For
the case of spiral spacing giving very good confinement, example, the structural and sectional ductility are 9 and
increasing the spiral spacing while adding fibers to the 39% higher, respectively, for Specimen C30S100FP1 than
concrete matrix does not result in any gain, as can be seen for C30S75FP0. Specimen C30S100FP1 dissipates 40%
in Fig. 12(b). Moreover, the loss in rigidity is smaller for more energy than C30S75FP0. Comparing the response
fibrous specimens compared with those without fibers, but of C30S75FP1 with C30S42FP0 reveals that Specimen
with the same amount of transverse steel reinforcement. It C30S42FP0 performs better than C30S75FP1. The pres-
should be noted that an increase in the maximum shear force ence of fibers in the concrete matrix with a spiral spacing of
as well as the maximum bending moment is obtained for 75 mm (2.95 in.) is not sufficient to obtain behavior compa-
fibrous specimens compared with those that are nonfibrous. rable with Specimen C30S42FP0.
In terms of ductility, the SNFRC specimens evidenced an Additionally, three confinement indexes were calculated.
increase of up to 30% in sectional and structural ductility The indexes were developed to correlate the displacement
capacity compared with their NSC counterparts (Table 5). capacity of a column with the effectiveness of confine-
This improvement is also observed in the interstory drift ment. The confinement index Ic has been recommended
ratio. In terms of energy dissipation, the fibrous specimens by ACI-ASCE Committee 441,26 and is defined as ρs fyh/fc′.
with s = 100, 75, and 42 mm (3.94, 2.95, and 1.65 in.) had The effective confinement index Ie′, proposed by Cusson
an increase of 125, 68, and 0%, respectively, in terms of the and Paultre,27 relates the effective yield strength to the
parameter EN, compared with their corresponding nonfibrous geometrical distribution and the amount of confinement
specimens. Moreover, for IW, which indicates the specimen steel. Ie′ is calculated as fle′/fc′, where fle′ is the effective
loading severity, an increase of 108, 61, and 4% was also confinement pressure applied by the tie to the concrete
observed for the SNFRC specimens with s = 100, 75, and core when confined concrete reaches its maximum stress.
42 mm (3.94, 2.95, and 1.65 in.), respectively, compared Further discussion about this index can be found in Cusson
with their corresponding nonfibrous specimens. The DEW and Paultre.27,28 According to Paultre et al.,29 the index Ik,
index follows the same tendency. This agrees with the fact which accounts for the effectiveness of confinement and
that fiber influence in the response is less effective as the the axial load, is the key to understanding the behavior
spiral spacing decreases. of NSC and high-strength concrete (HSC) columns under

ACI Structural Journal/January-February 2014 197


Table 5—Summary of test results
fc′, Dc, ϕyI,
MPa D, mm mm s, mm ρs, Hmax′, ΔyI, mm rad/m
Specimen (ksi) (in.) (in.) (in.) % kN (kip) (in.) (rad/in.) μΔI μϕI EN IW DEW Ic Ie′ Ik
34.3 304 250 100 59.7 30.0 0.0196
C30S100FP0 1.53 4.9 23.2 31.6 26.8 96.3 0.20 9 0.90
(4.97) (11.97) (9.84) (3.94) (13.42) (1.18) (0.7717)
30.8 302 252 100 59.5 32.3 0.0151
C30S100FP1 1.52 6.3 30.2 71.4 55.8 319.6 0.22 10 1.11
(4.47) (11.89) (9.92) (3.94) (13.38) (1.27) (0.5945)
36.0 303 253 75 61.8 28.9 0.0215
C30S75FP0 2.01 5.8 21.8 50.6 39.2 196.4 0.25 12 1.13
(5.22) (11.93) (9.96) (2.95) (13.89) (1.14) (0.8465)
38.0 304 253 75 63.8 30.7 0.0230
C30S75FP1 2.01 7.7 25.3 84.8 63.2 456.6 0.24 12 1.02
(5.51) (11.97) (9.96) (2.95) (14.34) (1.21) (0.9055)
31.1 302 240 42 56.2 30.0 0.0135
C30S42FP0 3.78 10.0 49.2 155.0 108.7 1069.5 0.54 29 2.58
(4.51) (11.89) (9.45) (1.65) (12.63) (1.18) (0.5315)
38.3 304 248 42 62.4 30.4 0.0139
C30S42FP1 3.67 10.3 51.0 149.9 112.6 1182.3 0.43 22 1.58
(5.55) (11.97) (9.76) (1.65) (14.03) (1.20) (0.5472)

Fig. 10—Ideal curve definitions.


for the former specimens reduced their indexes compared
with the latter specimen. Yet the values when comparing
Fig. 9—Envelope curve calculation and energy dissipation. Specimens C30S100FP0 and C30S100FP1, for example, do
not reflect the visible increase in ductility obtained for Spec-
cyclic loading and developing predictive behavioral models. imen C30S100FP1 by the presence of fibers in the concrete
Ik is calculated as ρs fh′/(fc′kp), where kp is the ratio of the matrix. Similarly, when comparing Specimens C30S100FP1
applied axial load to the axial capacity in compression of and C30S75FP0, the values of the indexes are slightly higher
the column measured as 0.85(Ag – Asl)fc′ + Asl fy, and fh′ is for Specimen C30S75FP0, even though the results from
tensile stress in the transverse reinforcement when confined testing, and all ductility and energy-based parameters, show
concrete reaches its maximum stress. fh′ can be determined a better performance for Specimen C30S100FP1. This indi-
according to Légeron and Paultre23 but for simplification, cates the need to develop a new index expression that takes
can be taken as fyh up to 500 MPa (72.5 ksi) as recommended into account the presence of fibers in the concrete matrix.
by the CSA standard.13 Table 5 shows the results of Ic, Ie′,
and Ik for all specimens tested. When comparing specimens CONCLUSIONS
with same concrete mixture, that is, NSC or SNFRC, Table The test results presented in this paper show the structural
5 shows that the specimens behave in a more ductile manner applicability and benefits that can be obtained with SNFRC
at higher values of confinement index (except for index Ik of compared with NSC. The flexural behavior of columns under
Specimen C30S75FP1, which can be attributed to its rela- constant axial load was highly influenced by the amount
tively high concrete strength of 38 MPa [5.51 ksi] compared of confinement steel reinforcement. The test results show
with 30.8 MPa [4.47 ksi] for C30S100FP1). Note that the that SNFRC specimens with a volumetric fiber ratio of 1%
axial load level applied to all specimens is similar. There- evidenced greater ductility, energy-dissipation capacities,
fore, the trend of the index Ik is similar to that of the indexes and strength enhancement at large ductility than similar NSC
Ic and Ie′ for all specimens. For the NSC specimens, the specimens. These properties are all significant in seismic
indexes clearly reflect the displacement capacity obtained design, leading very often to steel congestion in reinforced
from the test. The same result is observed with the SNFRC concrete columns. Therefore, a reduction in transverse steel
specimens, if analyzed separately. Note that the indexes are reinforcement when using SNFRC within a certain range
a function of the concrete strength, which was 23% higher of transverse reinforcement spacing is a great advantage in
for Specimens C30S75FP1 and C30S42FP1 compared with seismic design. Thus, the confinement provided due to fiber
that of Specimen C30S100FP1. The higher concrete strength action can replace part of the confinement due to the action of

198 ACI Structural Journal/January-February 2014


Fig. 12—Comparison of normalized moment-curvature rela-
tionships for specimens with different spiral spacing.
ACKNOWLEDGMENTS
The authors would like to acknowledge the financial support of the
Natural Sciences and Engineering Research Council of Canada (NSERC)
and the Quebec Fonds pour la Recherche sur la Nature et les Technologies
(FQRNT). The authors would also like to acknowledge the collaboration of
Professor N. Roy; and J. Desmarais Claude Aubé and L. Thibodeau, tech-
nicians in the Department of Civil Engineering at the Université de Sher-
brooke, for their role in the test preparation and during the tests.
Fig. 11—Comparison of normalized moment-curvature rela-
tionships for specimens with same spiral spacing. NOTATION
Ag = gross section of concrete
the transverse reinforcement, thereby reducing the minimum D = section diameter of column
Dc = core diameter measured out-to-out of spiral
amount required by design codes. Furthermore, according to DEW = damage index
the damage level reached by all specimens, synthetic fibers Ec = secant modulus of elasticity of plain concrete
prevent early spalling of concrete cover due to the plane of Ehyst = total energy dissipated
Ei = energy dissipated in one cycle
weakness defined by the transverse reinforcement. In addition, EN = normalized dissipated energy
a significant reduction in the damaged zone around the plastic fc′ = maximum compressive strength of concrete measured on 150 x
hinge is achieved with the use of SNFRC. More work is being 300 mm cylinders
fle′ = effective confinement pressure at peak stress
carried out to relate the reduction of transverse reinforcement f r = concrete modulus of rupture
to the amount of synthetic fibers used in the concrete mixture. fsu = ultimate strength of longitudinal reinforcement steel
fy = yield strength of longitudinal reinforcement steel
fyh = yield strength of transverse reinforcement steel
AUTHOR BIOS H = applied horizontal load
Laura Isabel Osorio is a Structural Engineer at Dessau Inc., Montreal, H′ = applied horizontal load, H, plus equivalent horizontal load due
QC, Canada. She received her BSc in civil engineering from the University to P-Δ effect
of Medellín, Medellín, Antioquia, Colombia, and her MSc from the Univer- Ic = confinement index
sity of Sherbrooke, Sherbrooke, QC, Canada. Ie′ = effective confinement index
Ik = confinement index
Patrick Paultre, FACI, holds a Canada Research Chair in Seismic Engi- I w = work index
neering and dynamics of structures at the University of Sherbrooke. He is a K i = stiffness in i-th cycle corresponding to maximum displacement
member of Joint ACI-ASCE Committee 441, Reinforced Concrete Columns. KyI = stiffness corresponding to idealized yield displacement
kp = relation between factored axial load and nominal axial resis-
Rami Eid is a Senior Lecturer and the Head of the Civil Engineering Depart- tance at zero eccentricity
ment at Shamoon College of Engineering, Beer Sheva, Israel. He received l = distance from top of base to application point of lateral load
his PhD in civil/structural engineering from the Technion – Israel Institute s = center-to-center spiral spacing
of Technology, Haifa, Israel. He is a member of Joint ACI-ASCE Committee Δ = horizontal tip displacement of cantilever column measured at
441, Reinforced Concrete Columns. His research interests include struc- load application point
tural behavior and analytical modeling of reinforced concrete elements. Δ′ = horizontal tip displacement of cantilever column
Δ2 = idealized ultimate displacement
Jean Proulx is a Professor of structural engineering and Head of the Δi = maximum horizontal displacement at i-th cycle at load applica-
Department of Civil Engineering at the University of Sherbrooke. He tion point
received his BSc in civil engineering from Laval University, Quebec City, Δyexp = experimental yielding displacement
QC, Canada, and his MSc and PhD from the University of Sherbrooke. ΔyI = idealized yielding displacement
δu = interstory drift ratio

ACI Structural Journal/January-February 2014 199


εc′ = axial strain in plain concrete corresponding to fc′ 12. Yoon, J. K.; Billington, S. L.; and Rouse, J. M., “Precast Segmental
εc50u = axial strain in plain concrete corresponding to 0.5fc′ after peak Bridge Piers with Unbonded Post-tensioning and Ductile, Fiber Reinforced
εsh = strain corresponding to beginning of steel hardening Concrete for Seismic Applications,” Proceedings of the 7th National
εsu = ultimate strain corresponding to ultimate stress fsu of steel Conference of Earthquake Engineering (NCEE), Boston, MA, 2002, 10 pp.
εy = yield strain in steel (CD-ROM)
ϕ2 = idealized ultimate curvature 13. CSA A23.3-04, “Design of Concrete Structures,” Canadian Stan-
ϕyI = idealized yielding curvature dards Association, Toronto, ON, Canada, 2004, 258 pp.
μΔI = structural ductility 14. NZS 3101, “Code of Practice for the Design of Concrete Structures,”
μϕI = sectional ductility Standard Association of New Zealand, Wellington, New Zealand, 1995,
n f = fiber volumetric ratio 256 pp.
ρl = area ratio of longitudinal reinforcement 15. ACI Committee 318, “Building Code Requirements for Structural
ρs = volumetric ratio of spiral reinforcement Concrete (ACI 318M-11) and Commentary ,” American Concrete Institute,
Farmington Hills, MI, 2011, 503 pp.
16. Osorio, L. I., “Behavior of Synthetic Fiber-Reinforced Concrete
REFERENCES Circular Columns under Cyclic Flexure and Constant Axial Load,” Mémoire
1. ACI Committee 544, “Design Consideration for Steel Fiber-Rein- de maîtrise, Département de génie civil, Université de Sherbrooke, Quebec,
forced Concrete (ACI 544.4R-88) (Reapproved 1999),” American Concrete QC, Canada, 2008, 100 pp.
Institute, Farmington Hills, MI, 1988, 17 pp. 17. Trottier, J.-F., and Mahoney, M., “Innovative Synthetic Fibers,”
2. Djumbong, A.; Cusson, D.; and Paultre, P., “Experimental Study of Concrete International, V. 23, No. 6, June 2001, pp. 23-28.
Influence of Synthetic Fibres on Behavior of Cylindrical High-Strength 18. Trottier, J.-F., and Mahoney, M., “Fiber Reinforced Building Mate-
Concrete Columns,” 37th Annual Conference of the Canadian Society of rial,” U.S. Patent issued on July 23, 2002, http: //www.patentstorm.us/
Civil Engineering, QC, Canada, June 10-13, 2008, 10 pp. patents/6423134.html.
3. Nguyen, H., “Shear Behavior of Polypropylene Fiber Reinforced 19. Trottier, J.-F.; Burke, S.; Macklin, M. B.; and Rieder, K.-A.,
Concrete Beams,” MASc, Department of Civil Engineering, University of “Three-Dimensional Twisted Fibers and Processes for Making Same,”
Sherbrooke, Sherbrooke, QC, Canada, 2006, 98 pp. (in French) U.S. Patent issued on January 22, 2002, http://www.patentstorm.us/
4. Han, C.; Hwang, Y.; Yang, S.; and Gowripalan, N., “Performance patents/6340522.html.
of Spalling Resistance of High Performance Concrete with Polypropylene 20. Priestly, M. J. N.; Seible, F.; and Calvi, G. M., Seismic Design and
Fiber Contents and Lateral Confinement,” Cement and Concrete Research, Retrofit of Bridges, John Wiley and Sons, Inc., New York, 1996, 686 pp.
V. 35, 2005, pp. 1747-1753. 21. Park, R., “Evaluation of Ductility of Structures and Structural Assem-
5. Chernov, V.; Zlotnikov, H.; and Shandalov, M., “Structural Synthetic blages from Laboratory Testing,” Bulletin of the New Zealand National
Fiber-Reinforced Concrete-Experience with Marine Applications,” Society for the Earthquake Engineering, V. 22, No. 3, 1989, pp. 155-166.
Concrete International, V. 28, No. 8, Aug. 2006, pp. 56-61. 22. Sheikh, S., and Khoury, S., “Confined Concrete Columns with Stub,”
6. Aoude, H.; Cook, W. D.; and Mitchell, D., “Behavior of Columns ACI Structural Journal, V. 90, No. 4, July-Aug. 1993, pp. 415-431.
Constructed with Fibers and Self-Consolidating Concrete,” ACI Structural 23. Légeron, F., and Paultre, P., “Uniaxial Confinement Model for
Journal, V. 106, No. 3, May-June 2009, pp. 349-357. Normal- and High-Strength Concrete Columns,” Journal of Structural
7. Aviram, A.; Stojadinovic, B.; and Parra-Montesinos, G., “Seismic Engineering, ASCE, V. 129, No. 2, 2003, pp. 241-252.
Behavior of High-Performance Fiber Reinforced Concrete Bridge Piers,” 24. Gosain, K. N.; Brown, H. R.; and Jirsa, J. O., “Shear Requirements
Proceedings of the 9th U.S. National and 10th Canadian Conference on for Load Reversals on RC Members,” Journal of the Structural Division,
Earthquake Engineering, Toronto, ON, Canada, 2010, 10 pp. (CD-ROM) ASCE, V. 103, No. 7, 1977, pp. 1461-1476.
8. Harajli, M. H., and Rteil, A. M., “Effect of Confinement Using 25. Ehsani, M. R., and Wright, J. K., “Confinement Steel Requirements
Fiber-Reinforced Polymer or Fiber-Reinforced Concrete on Seismic for Connections in Ductile Frames,” Journal of the Structural Division,
Performance of Gravity Load-Designed Columns,” ACI Structural Journal, ASCE, V. 116, No. 3, 1990, pp. 751-767.
V. 101, No. 1, Jan.-Feb. 2004, pp. 47-56. 26. Join ACI-ASCE Committee 441, “High-Strength Concrete Columns
9. Massicotte, B.; Mossor, B.; Filliatrault, A.; and Tremblay, S., (ACI 441R-96),” American Concrete Institute, Farmington Hills, MI, 1996,
“Compressive Strength and Ductility of Steel Fiber Reinforced Concrete 13 pp.
Columns,” Structural Applications of Fiber-Reinforced Concrete, SP-182, 27. Cusson, D., and Paultre, P., “High-Strength Concrete Columns
N. Banthia, C. MacDonald, and P. Tatnall, eds., American Concrete Insti- Confined by Rectangular Ties,” Structural Journal, ASCE, V. 120, No. 3,
tute, Farmington Hills, MI, 1998, pp. 163-180. 1994, pp. 783-804.
10. Parra-Montesinos, G. J., “High-Performance Fiber-Reinforced 28. Cusson, D., and Paultre, P., “Stress-Strain Model for Confined High-
Cement Composites: An Alternative for Seismic Design of Structures,” ACI Strength Concrete,” Journal of Structural Engineering, ASCE, V. 121, No.
Structural Journal, V. 102, No. 5, Sept.-Oct. 2005, pp. 668-675. 3, 1995, pp. 468-477.
11. Paultre, P.; Eid, R.; Langlois, Y.; and Lévesque, Y., “Compressive 29. Paultre, P.; Eid, R.; Robles, H. I.; and Bouaanani, N., “Seismic
Behavior of Steel Fiber-Reinforced High-Strength Concrete Columns,” Performance of Circular High-Strength Concrete Columns,” ACI Structural
Journal of Structural Engineering, ASCE, V. 136, No. 10, 2010, pp. Journal, V. 106, No. 4, July-Aug. 2009, pp. 395-404.
1225-1235.

200 ACI Structural Journal/January-February 2014

You might also like