Interlocking: Close Command CB Upstream

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

INTERLOCKING

Close Command CB Upstream

ES Siemens Open Position

CB Siemens Close Position
& CB Upstream Possible to Close

CB Siemens Service Position

Close Command CB Incoming 
Siemens

CB Upstream Open Position
& CB Incoming Siemens Possible to Close

Permissive Earthing incoming 
Siemens

CB Upstream Open Position ES Incoming Siemens Possible to Open or 
& Close

MATRIX TRIPPING

Protection CB Upstream CB Downstream


Differential Protection Operate Trip Trip
Mechanical Transformer Operate Trip Trip
Wiring List Connection

From To
ID Cable Size Cable
Device Terminal No Device Terminal No
X1: 22 ?
Siemens 
X1: 23 Upstream  ?
4 x 4mm Incoming  CT for Differential
X1: 24 side ?
Panel
X1: 25 ?
X2: 1 ?
Siemens 
X2: 3 Upstream  ?
4 x 4mm Incoming  VT for AVR
X2: 5 side ?
Panel
X2: 7 ?
X4: 781 ? Permissive Close CB 
X5: 859 ? Upstream
X3: 23 ? Permissive Close CB 
X3: 24 ? Downstream
X3: 29 ? Permissive Close E/S 
Siemens 
X3: 30 Upstream  ? Downstream
12 x 2,5mm Incoming 
X3: 15 side ?
Panel Intertripping from Upstream
X3: 19 ?
Spare Spare
Spare Spare
Spare Spare
Spare Spare