A. Academic Buildings:: Card Readers: Designer Comments
A. Academic Buildings:: Card Readers: Designer Comments
A. Academic Buildings:: Card Readers: Designer Comments
A. Academic Buildings:
The main entrance door to academic buildings shall have a card access system.
B. Residential Buildings:
Main entrances to residential halls housing more than 20 people shall have a card access
system. Suite doors, and apartment unit entry doors, will have card access readers if
they have more than 20 people each.
D. Electrical Requirements:
1. In the Communications closet – 110v/120v AC nonswitched circuit.
2. At the door – 110v/120v AC nonswitched circuit for PS873X871-2 Power supply.
3. Door contact, card access reader and power transfer hinge to be connected to Reader
Interface Module through concealed wiring (i.e. conduit/EMT).
E. Data/networking Requirements:
1. Reader Interface Module installed above the door/ceiling and powered from from the
communications closet with 2 conductor,18 awg, NS, plenum rated cable (or enclosed
in conduit if hard ceiling)
2. Elon will provide campus Ethernet connection in Communication Closet in each
building. Installer to provide wiring from door device to Communication Closet.
2. Reader Interface Module connected to System Controller with 4 conductor, 18awg,
OAS, plenum rated, communitcations cable (or enclosed in conduit if hard ceiling)
Any deviations from these criteria are noted above in the comments section.
DESIGNER SIGNATURE_________________________
389977411.xls
ELON UNIVERSITY
DOOR HARDWARE CRITERIA
06/15/2018
Door Locks
Door Type DESCRIPTION Designer Comments
1 Schlage D73 Rd (Removable
Residence Hall (Bedroom) core not factory pinned (Lockable
AND by button from inside and key
Offices only from outside))
Athens Trim - Lever Handle
626 (brushed chrome finish)
2-3/4" Backset
Door Hardware
Device DESCRIPTION Designer Confirmation
1 Door Closures LCN - 4041 (4000 Series)
Note:
1. Keyway is (Elon To Provide)
2. Contractor provides all locks with interchangable cores.
( ZERO bitting only).
3. Elon provides pinning and key cutting.
4. Contractor submittal for hardware to be sent concurrently to AE and Elon
for review.
Any deviations from these criteria are noted above in the comments section.
.
Designer Signature
389977411.xls