ELEC_POWER & CONTROL CABLE DESIGN_DESIGN CRITERIA FOR CABLE
DP16004-YR07-90ZEN-140002
CONTENTS
1.0 GENERAL ................................................................................................................................. 3
2.0 DESIGN PARAMETERS .............................................................................................................. 3
3.0 MINIMUM PERMISSIBLE CROSS-SECTIONS ................................................................................ 4
4.0 CURRENT CARRYING CAPACITY ................................................................................................ 6
5.0 VOLTAGE DROPS ...................................................................................................................... 8
6.0 ATTACHMENTS ........................................................................................................................ 9
1.0 GENERAL
This report specifies permissible cross-sections of power cables for serving the MV and LV systems under
short-circuit conditions and normal operating conditions for 2 x 660 MW Obra-C Thermal Power
Extension Project.
The calculations in this report are performed in accordance with IS and other standards as mentioned in
ITB. For dimensioning of power cables the following conditions shall be considered:
- Short-circuit conditions
- Current carrying capacity under normal conditions
- Voltage Drop during normal operation and motor start-up
- The stating current for motor feeders shall be 6 times the full load current for AC motors and 2
times the full load current for DC motors
The longest duration of short-circuit fault for incoming and tie feeder cables is estimated to 1 second for
50kA and for outgoing feeder cables such as motors and transformers, 0.2 seconds which shall be verified
by short circuit calculation and protection relay setting study.
𝐼𝑋 𝑡
A = (Equation 3.1)
𝑘
Where,
t = duration in seconds
k = factor
𝑄𝑐 (𝐵+20) 𝜃𝑟 − 𝜃𝑖
𝑘= ln( 1 + ) (Equation 3.2)
𝑄20 𝐵+ 𝜃𝑖
Therefore minimum cross-sections shall be 630 mm2 for incoming and tie feeder cables and 240 mm2 for
outgoing feeder cables of 11kV switchgears.
The longest duration of short-circuit fault for incoming and tie feeder cables is estimated to 1 second for
40kA and for outgoing feeder cables such as motors and transformers, 0.2 seconds which shall be verified
by short circuit calculation and protection relay setting study.
Therefore minimum cross-sections shall be 630 mm2 for incoming and tie feeder cables and 240 mm2 for
outgoing feeder cables of 3.3kV switchgears.
The longest duration of short-circuit fault for incoming and tie feeder cables is estimated to 1 second for
50kA and for outgoing feeder cables such as motors and transformers, 0.25 seconds which shall be
verified by short circuit calculation and protection relay setting study.
Therefore minimum cross-sections shall be 630 mm2 for incoming and tie feeder cables and 300 mm2 for
outgoing feeder cables of 415V switchgears.
The cable size will be selected based on the current carrying capacity of cable.
N = I1/I2
Where,
(Derated current carrying capacity of cable X No. of runs > Load current)
5.1 Formula
Vd = k x (R cos θ + X sin θ) x Ir x L
= k x Z x Ir x L (Equation 5.1)
Where,
k : Constant
(Value equal to 2 for single phase and 1.732 for three phases)
For DC loads:
Vd = 2 x Ir x R x L (Equation 5.2)
Where,
The maximum permissible voltage drops for 11kV and 3.3kV system shall be considered for normal
operation as well as for start-up of 11kV motors and 3.3kV motors. Voltage drops for normal and starting
mode of 11kV motors will be limited to 3% and 15% respectively.
The maximum voltage drop under normal conditions shall not exceed 3%, and the total voltage drop up
to motor terminals at full voltage, during the motor starting period shall not exceed 15%.
The voltage drop limits for feeders other than motors shall be as mentioned below:
6.0 ATTACHMENTS
b) RATING FACTORS
i) Rating factors related to variation in ambient air temperature
Air temperature in Deg. C20 25 30 35 40 45 50 55
Normal PVC 1.32 1.25 1.16 1.09 1.00 0.90 0.80 0.80
Rating factors HRPVC 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.80
XLPE 1.20 1.16 1.11 1.06 1.00 0.95 0.88 0.81
iii) Rating factors related to variation in ground thermal resistivity of soil for 3 single core cables laid direct in ground. (Average value)
Thermal Res. in oC.Cm/W 100 120 150 200 250 300
Rating factors 1.20 1.10 1.00 0.90 0.81 0.74
iv) Rating factors related to variation in ground thermal resistivity of soil for multi core cables laid direct in ground. (Average value)
Thermal Res. in oC.Cm/W 100 120 150 200 250 300
Rating factors 1.16 1.08 1.00 0.90 0.82 0.76
vi) Rating factors related to variation in depth of laying for 3.3kv to 11kv cables
Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors — 1.00 0.99 0.98 0.96 0.95
vii) Rating factors related to variation in depth of laying for above 11kv cables
Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors — — 1.00 0.99 0.98 0.96
40
Basic assumption for current ratings & rating factors
No.
of WALL
300mm
S = dia of cable WALL
300mm
t = touching
racks
WALL
2d 300mm
41
S = axial spacing of cable
No. of cables/ No. of
circuits in groups Tier Multicore cables in Tier formation
Touching S=15CM S=30CM S=45CM S=60CM
2 1 0.80 0.84 0.87 0.90 0.91
3 1 0.68 0.74 0.79 0.83 0.86
4 2 0.60 0.66 0.73 0.77 0.79
5 2 0.55 0.61 0.68 0.71 0.73
6 2 0.51 0.57 0.63 0.67 0.69
7 3 0.48 0.54 0.59 0.63 0.64
8 3 0.46 0.51 0.56 0.60 0.61
9 3 0.44 0.48 0.53 0.57 0.58
10 4 0.42 0.47 0.52 0.55 0.56
11 4 0.41 0.46 0.50 0.54 0.55
12 4 0.40 0.45 0.49 0.53 0.54
No. co cables/ Multicore cable (Touching) Multicore cables (spacing of cable S/core cables in trefoil touching formation
circuits in group No of cables in racks equal to dia meter of cable spacing between circuits equal to twice
No of cables in racks the diameter of cable) No of cables in racks
1 3 4 1 2 3 4 1 2 3 4
1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2 0.84 0.80 0.78 0.76 0.98 0.95 0.94 0.93 0.98 0.95 0.94 0.93
3 0.80 0.76 0.74 0.72 0.96 0.93 0.92 0.90 0.96 0.93 0.92 0.90
4 0.76 0.71 0.70 0.68 0.93 0.90 0.89 0.87 — — — —
95 0.79 0.68 0.83 0.70 t t = Time duration required tobe calculated of short circuit in Sec.
120 0.63 0.55 0.66 0.56 SELECTION CRITERIA OF H.V./MV CABLES FOR PRIMARY DISTRIBUTION
150 0.52 0.46 0.55 0.48 REQUIRED DATAS FOR EXAMPLE
185 0.42 0.37 0.44 0.40 1) Nominal System voltage at H.T. Side 11KV
240 0.34 0.30 0.35 0.30 2) Short circuit level for H.T. system 25KA
3) Fault withstand time for H.T. CBs 0.5 SEC
300 0.28 0.26 0.30 0.26
4) Formula for calculating H.T. cable size
400 0.24 0.22 0.24 0.22 With Aluiminium cond./XLPE insulated cable = Ish X t = 25 X0.5
500 0.23 0.20 0.23 0.20 0.094 = 0.94
630 0.20 0.18 0.21 0.18 = 188
Hence nearest higher size 240sqmm is required
800 0.19 - 0.20 -
With Copper cond./XLPE insulated cable = Ish X t = 25 X 0.5
1000 0.18 - 0.18 - 0.143 0.143
**Above voltage drops (volts/km/amps) shall be multiplied = 124
with rated current & length of Cable in K.M. to calculate total Hence nearest higher size 150sqmm is required
voltage drop in particular length and size of cables.
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approx). (Approx). Al Cu
25 1.20 0.727 1.54 0.931 0.164 0.14 100 90 120 130 115 155 2.35 3.58
35 0.868 0.524 1.11 0.671 0.156 0.16 120 105 145 155 140 185 3.29 5.00
50 0.641 0.387 0.820 0.495 0.147 0.17 140 125 170 185 160 220 4.70 7.15
70 0.443 0.268 0.567 0.343 0.139 0.20 175 155 215 225 195 275 6.58 10.01
95 0.320 0.193 0.410 0.248 0.132 0.21 205 180 260 265 235 340 8.93 13.59
120 0.253 0.153 0.325 0.197 0.126 0.23 235 205 305 300 265 390 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.124 0.25 260 230 345 335 295 440 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.120 0.26 295 260 395 380 330 510 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.116 0.29 340 300 470 435 380 600 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.112 0.32 385 335 540 490 425 680 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.109 0.35 440 380 630 550 480 790 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.105 0.39 495 430 730 610 530 910 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.102 0.43 560 480 840 680 580 1030 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.097 0.50 620 530 960 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.096 0.56 680 580 1070 790 670 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
34
Table -30 TECHNICAL DETAIL FOR HAVELLS 11/11KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY ( 11KVUE) Ref. Spec. : IS :7098PART -2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm (mm) Cond. Cond. wire (mm) mm (mm) Cond. Cond.
25 5.5 0.5 0.8 1.88 50 3000 3500 2.50 2.04 54 4300 4750
35 5.5 0.5 0.8 2.04 53 3200 3850 2.50 2.20 57 4700 5350
50 5.5 0.6 0.8 2.20 56 3700 4600 2.50 2.20 60 5100 6050
70 5.5 0.6 0.8 2.20 60 4100 5400 2.50 2.36 64 5800 7100
95 5.5 0.6 0.8 2.36 64 4800 6567 3.15 2.52 69 7300 9100
120 5.5 0.7 0.8 2.52 68 5400 7632 3.15 2.52 73 8000 10250
150 5.5 0.7 0.8 2.52 71 5900 8690 3.15 2.68 76 8600 11400
185 5.5 0.7 0.8 2.68 75 6500 9950 3.15 2.84 80 9400 12850
240 5.5 0.7 0.8 2.84 81 7600 12050 3.15 3.00 85 11000 15500
300 5.5 0.7 0.8 3.00 85 8600 14200 4.00 3.00 91 13000 18600
400 5.5 0.7 0.8 3.00 93 10000 17500 4.00 3.00 98 15000 22450
4 INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5 PVC FILLERS
6 INNER SHEATH : Extruded PVC
7
ARMOURING : Single layer of Galvanized Flat strip/ Round wires.
8
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cabe at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu
25 1.20 0.727 1.54 0.931 0.145 0.14 95 82 105 120 105 135 2.35 3.58
35 0.868 0.524 1.11 0.671 0.138 0.16 115 97 125 145 125 165 3.29 5.01
50 0.641 0.387 0.820 0.495 0.129 0.17 130 115 150 170 150 195 4.70 7.15
70 0.443 0.268 0.567 0.343 0.124 0.20 160 140 190 210 180 240 6.58 10.01
95 0.320 0.193 0.410 0.248 0.116 0.21 190 165 230 250 215 295 8.93 13.59
120 0.253 0.153 0.325 0.197 0.112 0.23 220 190 260 280 240 335 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.108 0.25 245 210 295 310 270 380 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.105 0.26 275 240 335 350 305 430 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.102 0.29 315 275 395 400 350 500 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.0999 0.32 355 310 450 445 390 570 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.0954 0.35 400 350 520 500 440 650 37.60 57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
35
Table -23 TECHNICAL DETAIL FOR HAVELLS 3.3 KV
SINGLE CORE, AL/COPPER COND., XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY ( 3.3KV-EARTHED/ UNEARTHED GRADE) Ref. Spec. : IS :7098PART -2
Physical Parameters
SIZE Nominal Nominal Diameter Minimum Thickness Approx. Approx.
cross- Sectional Insulation of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area(Sqmm) thickness (mm) (mm) Diameter With Al. With Cu
( mm) (mm) Cond. Cond.
25 2.5 1.40 1.24 18 350 500
35 2.5 1.40 1.24 19 400 600
50 2.5 1.40 1.40 21 500 800
70 2.5 1.60 1.40 23 650 1100
95 2.5 1.60 1.40 25 750 1350
120 2.5 1.60 1.40 26 850 1600
150 2.5 1.60 1.40 28 950 1900
185 2.5 1.60 1.40 29 1100 2250
240 2.5 1.60 1.56 32 1350 2850
300 2.5 1.60 1.56 34 1550 3400
400 2.8 2.00 1.56 39 2000 4500
500 2.8 2.00 1.56 42 2400 5500
630 3.0 2.00 1.72 47 3000 6900
800 3.3 2.00 1.88 52 3650 8600
1000 3.5 2.50 2.04 56 4500 10700
~ Tabulated approx. net weights of cables are only for guidelines for transportation / loading/ unloading purpose.
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approx). (Approx). Al Cu
25 1.20 0.727 1.54 0.931 0.133 0.25 100 91 110 130 115 145 2.35 3.58
35 0.868 0.524 1.11 0.671 0.126 0.29 120 110 135 155 140 175 3.29 5.00
50 0.641 0.387 0.820 0.495 0.122 0.33 140 125 165 185 165 215 4.70 7.15
70 0.443 0.268 0.567 0.343 0.116 0.38 175 155 210 225 200 270 6.58 10.00
95 0.320 0.193 0.410 0.248 0.111 0.44 205 185 255 265 235 330 8.93 13.59
120 0.253 0.153 0.325 0.197 0.106 0.49 235 210 295 300 265 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.103 0.53 260 230 335 335 300 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.100 0.58 295 260 390 380 335 495 17.39 26.45
240 0.125 0.0754 0.162 0.098 0.097 0.67 340 300 460 435 385 590 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.095 0.73 385 335 530 490 430 670 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.093 0.84 440 380 620 550 480 780 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.091 0.86 495 430 730 610 530 900 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.090 0.88 560 485 840 680 590 1020 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.088 0.94 620 530 960 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.086 0.99 670 570 1070 780 660 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
28
Table -24 TECHNICAL DETAIL FOR HAVELLS 3.3 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (3.3KV UE/E) Ref. Spec. : IS :7098PART -2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm ( mm) Cond. Cond. wire ( mm) mm ( mm) Cond. Cond.
25 2.2 0.3 0.8 1.40 28 1100 1550 1.60 1.56 30 1450 1900
35 2.2 0.3 0.8 1.56 31 1300 1950 1.60 1.56 33 1600 2250
50 2.2 0.4 0.8 1.56 33 1500 2450 2.00 1.56 35 2100 3050
70 2.2 0.4 0.8 1.56 36 1800 3100 2.00 1.56 38 2400 3700
95 2.2 0.4 0.8 1.72 39 2150 3900 2.00 1.72 42 2850 4600
120 2.2 0.5 0.8 1.72 42 2500 4750 2.00 1.88 45 3300 5550
150 2.2 0.5 0.8 1.88 44 2850 5650 2.50 2.04 48 4100 6900
185 2.2 0.5 0.8 2.04 48 3350 6800 2.50 2.04 51 4650 8100
240 2.2 0.6 0.8 2.20 52 4100 8550 2.50 2.20 56 5450 9900
300 2.2 0.6 0.8 2.20 56 4750 10350 2.50 2.36 60 6300 11900
400 2.2 0.7 0.8 2.36 62 5750 13200 3.15 2.68 67 8350 15800
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. pp.. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu
25 1.20 0.727 1.54 0.931 0.098 0.25 94 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.094 0.29 115 95 120 145 120 155 3.29 5.00
50 0.641 0.387 0.820 0.495 0.086 0.33 135 110 145 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.084 0.38 165 140 185 210 175 235 6.58 10.01
95 0.320 0.193 0.410 0.248 0.081 0.44 195 165 225 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.078 0.49 220 185 255 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.076 0.53 245 210 295 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.075 0.58 280 235 340 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.073 0.67 320 270 400 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.072 0.73 360 305 460 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.071 0.84 410 350 535 520 440 670 37.60 57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
29
Table -18 TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, AL WIRE/STRIP ARMOURED CABLES
Cable Code : A2XFaY/ 2XFaY, A2XWaY/ 2XWaY Ref. Spec. : IS :7098PART -1
Physical Parameters
SIZE Minimum Nominal ARMOURING WITH FLAT STRIP ( A2XFaY/2XFaY) ARMOURING WITH ROUND WIRES ( A2XWaY/ 2XWaY)
Cross- No of Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in Thickness of Thickness Thickness of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) Strip outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) A2XFaY 2XFaY (mm) (mm) (mm) A2XWaY 2XWaY
4 — 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 10 90 130
6 1 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 11 130 170
10 1 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 12 160 222
16 6 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 13 200 300
25 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 14 300 455
35 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 15 350 567
50 6 6 1.3 N/A N/A N/A N/A N/A 1.40 1.24 17 420 730
70 12 12 1.4 N/A N/A N/A N/A N/A 1.40 1.24 19 520 954
95 15 15 1.4 0.80 1.40 21 600 1195 1.60 1.40 22 650 1235
120 15 18 1.5 0.80 1.40 23 700 1450 1.60 1.40 24 750 1494
150 15 18 1.7 0.80 1.40 24 800 1730 1.60 1.40 25 850 1780
185 30 30 1.9 0.80 1.40 26 950 2100 1.60 1.40 28 1000 2147
240 30 34 2.0 0.80 1.40 30 1200 2690 1.60 1.40 30 1250 2738
300 30 34 2.1 0.80 1.56 32 1400 3270 1.60 1.56 33 1500 3360
400 53 53 2.4 0.80 1.56 36 1750 4230 2.00 1.56 38 1900 4380
500 53 53 2.6 0.80 1.56 39 2150 5250 2.00 1.56 41 2350 5450
630 53 53 2.8 0.80 1.72 44 2700 6610 2.00 1.72 46 2900 6806
800 53 53 3.1 0.80 1.72 48 3350 8320 2.00 1.88 51 3600 8560
1000 53 53 3.3 0.80 1.88 54 4100 10300 2.50 2.04 56 4600 10800
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.90 0.152 0.22 — — — 48 47 45 0.376 0.572
6 4.61 3.08 5.90 3.94 0.144 0.26 45 45 40 60 59 57 0.56 0.858
10 3.08 1.83 3.94 2.34 0.133 0.31 59 62 53 80 78 77 0.94 1.43
16 1.91 1.15 2.44 1.47 0.122 0.40 76 80 73 104 102 106 1.50 2.29
25 1.20 0.727 1.54 0.931 0.116 0.40 99 90 115 130 115 145 2.35 3.58
35 0.868 0.524 1.11 0.671 0.110 0.47 117 110 140 155 140 175 3.29 5.01
50 0.641 0.387 0.820 0.495 0.103 0.50 138 125 170 185 165 215 4.70 7.15
70 0.443 0.268 0.567 0.343 0.099 0.55 168 155 210 225 200 270 6.58 10.01
95 0.320 0.193 0.411 0.248 0.097 0.64 204 185 255 265 235 330 8.93 13.59
120 0.253 0.153 0.325 0.197 0.093 0.67 230 210 300 300 265 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.091 0.67 265 230 342 335 300 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.090 0.67 295 260 385 380 335 495 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.086 0.72 340 300 450 435 385 590 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.085 0.75 390 335 519 490 430 670 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.085 0.75 450 380 605 550 480 780 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.083 0.77 500 430 700 610 530 900 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.082 0.81 555 485 809 680 590 1020 59.22 90.09
800 0.0367 0.0221 0.0530 0.0319 0.081 0.88 625 530 935 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.081 0.88 690 570 1065 780 660 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
23
Table -19 TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORES, AL/COPPER COND.,
XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : A2xFY/2xFY, A2XWY/ 2XWY Ref. Spec. : IS :7098 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY) ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Al Cu (mm) (mm) (mm) (mm) (mm) A2XFY 2XFY (mm) (mm) (mm) A2XWY 2XWY
4 — 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 15 500 550
6 1 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 16 550 600
10 1 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 650 770
16 6 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.40 19 700 900
25 6 6 0.9 0.30 0.80 1.40 20 650 950 1.60 1.40 21 850 1150
35 6 6 0.9 0.30 0.80 1.40 21 750 1200 1.60 1.40 23 950 1400
50 6 6 1.0 0.30 0.80 1.40 23 900 1500 1.60 1.40 25 1100 1700
70 12 12 1.1 0.30 0.80 1.56 26 1100 1950 1.60 1.56 28 1400 2250
95 15 15 1.1 0.40 0.80 1.56 29 1350 2500 2.00 1.56 31 1850 3000
120 15 18 1.2 0.40 0.80 1.56 31 1600 3100 2.00 1.56 34 2150 3600
150 15 18 1.4 0.40 0.80 1.72 34 1900 3750 2.00 1.72 37 2450 4300
185 30 30 1.6 0.50 0.80 1.72 37 2250 4500 2.00 1.88 40 2900 5200
240 30 34 1.7 0.50 0.80 1.88 42 2800 5800 2.50 2.04 45 3850 6800
300 30 34 1.8 0.60 0.80 2.04 45 3300 7000 2.50 2.20 49 4450 8200
400 53 53 2.0 0.60 0.80 2.36 50 4100 9050 2.50 2.36 52 5350 10300
500 53 53 2.2 0.70 0.80 2.52 55 5000 11000 3.15 2.68 60 7100 13300
630 53 53 2.4 0.70 0.80 2.68 63 6100 14000 3.15 2.84 66 8500 16300
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec. duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 --- 4.61 --- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.1
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 461 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
24
Table -20 TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : A2XFY/2XFY, A2XWY/ 2XWY Ref. Spec. : IS :7098 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY) ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Al Cu (mm) (mm) strip (mm) (mm) (mm) A2XFY 2XFY (mm) (mm) (mm) A2XWY 2XWY
4 — 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 600 670
6 1 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 650 770
10 1 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 20 750 930
16 6 6 0.7 0.30 0.8 1.24 19 600 900 1.60 1.40 20 800 1100
25 6 6 0.9 0.30 0.8 1.40 21 800 1200 1.60 1.40 23 1000 1450
35 6 6 0.9 0.30 0.8 1.40 23 950 1500 1.60 1.40 25 1200 1850
50 6 6 1.0 0.30 0.8 1.40 26 1100 2000 1.60 1.56 29 1450 2300
70 12 12 1.1 0.40 0.8 1.56 29 1450 2700 2.00 1.56 32 2000 3300
95 15 15 1.1 0.40 0.8 1.56 32 1750 3500 2.00 1.56 35 2350 4100
120 15 18 1.2 0.40 0.8 1.56 35 2100 4200 2.00 1.72 39 2750 4900
150 15 18 1.4 0.50 0.8 1.72 42 2500 5200 2.00 1.88 43 3250 6000
185 30 30 1.6 0.50 0.8 1.88 44 3000 6300 2.50 2.04 48 4200 7500
240 30 34 1.7 0.60 0.8 2.04 49 3750 8200 2.50 2.20 53 5100 9500
300 30 34 1.8 0.60 0.8 2.20 54 4500 10000 2.50 2.36 58 6000 11300
400 53 53 2.0 0.70 0.8 2.52 60 5600 13000 3.15 2.68 65 7950 15200
500 53 53 2.2 0.70 0.8 2.68 66 6900 16000 3.15 2.84 72 9500 18500
630 53 53 2.4 0.70 0.8 2.84 74 8550 20000 4.00 3.00 81 12600 23700
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec. duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 --- 4.61 --- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 460 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
25
Table -21 TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE AND HALF CORES,
AL/CUCOPPER COND.,
XPLE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : 3.5 Core - A2XFY / 2XFY, A2XWY / 2XWY Ref. Spec. : IS :7098PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY)ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable (Kg/KM)
area Conductor Insulation) inner Sh. of Armr. outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(mm)
( sqmm) Al Cu (mm) Strip (mm) (mm) (mm) A2XFY 2XFY (mm) (mm) (mm) A2XWY 2XWY
3X25+16 6/6 6/6 0.90/0.70 0.30 0.80 1.40 23 900 1400 1.60 1.40 25 1100 1700
3X35+16 6/6 6/6 0.90/0.70 0.30 0.80 1.40 25 1000 1800 1.60 1.40 27 1300 2000
3X50+25 6/6 6/6 1.00/0.90 0.30 0.80 1.40 28 1200 2300 1.60 1.56 30 1600 2700
3X70+35 12/6 12/6 1.10/0.90 0.40 0.80 1.56 32 1600 3200 2.00 1.56 35 2200 3700
3X95+50 15/6 15/6 1.10/1.00 0.40 0.80 1.56 35 2000 4100 2.00 1.56 38 2600 4600
3X120+70 15/12 18/12 1.20/1.10 0.40 0.80 1.72 39 2400 5100 2.00 1.72 42 3100 5700
3X150+70 15/12 18/12 1.40/1.10 0.50 0.80 1.72 43 2800 6000 2.00 1.88 46 3600 6800
3X185+95 30/15 30/15 1.60/1.10 0.50 0.80 1.88 47 3400 7400 2.50 2.04 51 4700 8700
3X240+120 30/15 34/18 1.70/1.20 0.60 0.80 2.04 53 4300 9500 2.50 2.20 56 5700 10500
3X300+150 30/15 34/18 1.80/1.40 0.60 0.80 2.20 57 5000 11500 2.50 2.36 60 6700 13000
3X400+185 53/30 53/30 2.00/1.60 0.70 0.80 2.52 66 6400 14500 3.15 2.68 71 9000 17000
3X500+240 53/30 53/34 2.20/1.70 0.70 0.80 2.68 74 7900 18000 3.15 2.84 79 11000 21500
3X630+300 53/30 53/34 2.40/1.80 0.70 0.80 3.00 82 9900 23000 4.00 3.00 88 14500 28000
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App..Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
3X25+16 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
3X35+16 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
3X50+25 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
3X70+35 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
3X95+50 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
3X120+70 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
3X150+70 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
3X185+95 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
3X240+120 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 402 410 350 510 22.56 34.32
3X300+150 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.20 42.90
3X400+185 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
3X500+240 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
3X630+300 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
26
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Power Cable Sizing Rev. P1
1 4 2 4 3 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 25
ELECTRICAL CONSUMER Length POWER CABLE SPECIFICATION CURRENT CARRYING CAPACITY VOLTAGE DROP
Laying
From Current Margin Impedance Derating Factors Running Starting
Unit No. Type of Rated Power Rated Derated (D: Duct bank SIZING OK ?
S.N. Load ID KKS Code To KKS Code Rated Power Phase Efficiency Actual (5% for MV, Size Type REMARKS
(10/20/90) (Switchgear Name) feeder Voltage Factor Ir Is Cable ID Resistance Reactance Current Current T: Tray, TR: Trench (YES/NO)
10% for LV)
G: Directly Buried)
(kW)/(kVA) (V) (A) (A) (m) (m) (sqmm) (line) (ohm/km) (ohm/km) (A) ft FdxFhxFc fT (A) (V) (%) (V) (%)
1 B_0001 10 10BBA01 11kV Unit switchgear 1A FD fan (A) Later MO 1750.00 11000 3 0.95 0.83 128.14 768.82 261 275 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 10.62 0.097 48.1 0.437 T 0
2 B_0019 10 10BBA01 11kV Unit switchgear 1A PA fan (A) Later MO 2930.00 11000 3 0.95 0.87 204.67 1228.05 285 300 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 18.49 0.168 83.8 0.762 T 0
3 B_0039 10 10BBA01 11kV Unit switchgear 1A ID fan (A) Later MO 8460.00 11000 3 0.95 0.85 604.88 3629.26 666 700 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 42.54 0.387 192.6 1.751 T 0
Outgoing to Boiler
5 Later 10 10BBA01 11kV Unit switchgear 1A 10BFB01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 114 120 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 4.42 0.040 0.0 0.000 T 0
service trf
Outgoing to Turbine
6 Later 10 10BBA01 11kV Unit switchgear 1A 10BFA01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
service trf
Outgoing to ESP
7 E_0284 10 10BBA01 11kV Unit switchgear 1A 10BFF01 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
8 E_0286 10 10BBA01 11kV Unit switchgear 1A 10BFF03 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
9 E_0288 10 10BBA01 11kV Unit switchgear 1A 10BFF05 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
10 Later 10 10BBA01 11kV Unit switchgear 1A Outgoing to UAT 1A 10BBS01 TR 10000.00 11000 3 1.00 1.00 577.35 0.00 57 60 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 2.95 0.027 0.0 0.000 T 0
Outgoing to cooling
11 Later 10 10BBA01 11kV Unit switchgear 1A 10BFT01 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 11.78 0.107 0.0 0.000 T 0
tower trf
Outgoing to cooling
12 Later 10 10BBA01 11kV Unit switchgear 1A 10BFT03 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 11.78 0.107 0.0 0.000 T 0
tower trf
Outgoing to ESP
13 E_0285 10 10BBA02 11kV Unit switchgear 1B 10BFF02 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
14 E_0287 10 10BBA02 11kV Unit switchgear 1B 10BFF04 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
15 E_0289 10 10BBA02 11kV Unit switchgear 1B 10BFF06 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
16 Later 10 10BBA02 11kV Unit switchgear 1B Outgoing to UAT 1B 10BBS02 TR 10000.00 11000 3 1.00 1.00 577.35 0.00 57 60 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 2.95 0.027 0.0 0.000 T 0
17 B_0002 10 10BBA02 11kV Unit switchgear 1B FD fan (B) Later MO 1750.00 11000 3 0.95 0.83 128.14 768.82 261 275 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 10.62 0.097 48.1 0.437 T 0
18 B_0020 10 10BBA02 11kV Unit switchgear 1B PA fan (B) Later MO 2930.00 11000 3 0.95 0.87 204.67 1228.05 285 300 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 18.49 0.168 83.8 0.762 T 0
19 B_0040 10 10BBA02 11kV Unit switchgear 1B ID fan (B) Later MO 8460.00 11000 3 0.95 0.85 604.88 3629.26 666 700 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 42.54 0.387 192.6 1.751 T 0
Outgoing to cooling
21 Later 10 10BBA02 11kV Unit switchgear 1B 10BFT02 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 11.78 0.107 0.0 0.000 T 0
tower trf
Outgoing to Boiler
22 Later 10 10BBA02 11kV Unit switchgear 1B 10BFB02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 114 120 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 4.42 0.040 0.0 0.000 T 0
service trf
Outgoing to Turbine
23 Later 10 10BBA02 11kV Unit switchgear 1B 10BFA02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
service trf
24 B_0680 20 20BBA01 11kV Unit switchgear 2A FD fan (A) Later MO 1750.00 11000 3 0.95 0.83 128.14 768.82 261 275 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 10.62 0.097 48.1 0.437 T 0
25 B_0698 20 20BBA01 11kV Unit switchgear 2A PA fan (A) Later MO 2930.00 11000 3 0.95 0.87 204.67 1228.05 285 300 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 18.49 0.168 83.8 0.762 T 0
26 B_0718 20 20BBA01 11kV Unit switchgear 2A ID fan (A) Later MO 8460.00 11000 3 0.95 0.85 604.88 3629.26 666 700 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 42.54 0.387 192.6 1.751 T 0
Outgoing to Boiler
28 Later 20 20BBA01 11kV Unit switchgear 2A 20BFB01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 114 120 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 4.42 0.040 0.0 0.000 T 0
service trf
Outgoing to Turbine
29 Later 20 20BBA01 11kV Unit switchgear 2A 20BFA01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
service trf
Outgoing to ESP
30 E_0290 20 20BBA01 11kV Unit switchgear 2A 20BFF01 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
31 E_0292 20 20BBA01 11kV Unit switchgear 2A 20BFF03 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
32 E_0294 20 20BBA01 11kV Unit switchgear 2A 20BFF05 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
33 Later 20 20BBA01 11kV Unit switchgear 2A Outgoing to UAT 2A 20BBS01 TR 10000.00 11000 3 1.00 1.00 577.35 0.00 57 60 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 2.95 0.027 0.0 0.000 T 0
Outgoing to cooling
34 Later 20 20BBA01 11kV Unit switchgear 2A 20BFT01 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 11.78 0.107 0.0 0.000 T 0
tower trf
Outgoing to cooling
35 Later 20 20BBA01 11kV Unit switchgear 2A 20BFT03 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 11.78 0.107 0.0 0.000 T 0
tower trf
Outgoing to ESP
36 E_0291 20 20BBA02 11kV Unit switchgear 2B 20BFF02 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
Outgoing to ESP
37 E_0293 20 20BBA02 11kV Unit switchgear 2B 20BFF04 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
1 of 6
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Power Cable Sizing Rev. P1
ELECTRICAL CONSUMER Length POWER CABLE SPECIFICATION CURRENT CARRYING CAPACITY VOLTAGE DROP
Laying
From Current Margin Impedance Derating Factors Running Starting
Unit No. Type of Rated Power Rated Derated (D: Duct bank SIZING OK ?
S.N. Load ID KKS Code To KKS Code Rated Power Phase Efficiency Actual (5% for MV, Size Type REMARKS
(10/20/90) (Switchgear Name) feeder Voltage Factor Ir Is Cable ID Resistance Reactance Current Current T: Tray, TR: Trench (YES/NO)
10% for LV)
G: Directly Buried)
(kW)/(kVA) (V) (A) (A) (m) (m) (sqmm) (line) (ohm/km) (ohm/km) (A) ft FdxFhxFc fT (A) (V) (%) (V) (%)
Outgoing to ESP
38 E_0295 20 20BBA02 11kV Unit switchgear 2B 20BFF06 TR 2500.00 11000 3 1.00 0.90 144.34 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 30.27 0.275 0.0 0.000 T 0
service trf
39 Later 20 20BBA02 11kV Unit switchgear 2B Outgoing to UAT 2B 20BBS02 TR 10000.00 11000 3 1.00 1.00 577.35 0.00 57 60 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 2.95 0.027 0.0 0.000 T 0
40 B_0681 20 20BBA02 11kV Unit switchgear 2B FD fan (B) Later MO 1750.00 11000 3 0.95 0.83 128.14 768.82 261 275 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 10.62 0.097 48.1 0.437 T 0
41 B_0699 20 20BBA02 11kV Unit switchgear 2B PA fan (B) Later MO 2930.00 11000 3 0.95 0.87 204.67 1228.05 285 300 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 18.49 0.168 83.8 0.762 T 0
42 B_0719 20 20BBA02 11kV Unit switchgear 2B ID fan (B) Later MO 8460.00 11000 3 0.95 0.85 604.88 3629.26 666 700 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 42.54 0.387 192.6 1.751 T 0
Outgoing to cooling
44 Later 20 20BBA02 11kV Unit switchgear 2B 20BFT02 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 11.78 0.107 0.0 0.000 T 0
tower trf
Outgoing to Boiler
45 Later 20 20BBA02 11kV Unit switchgear 2B 20BFB02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 114 120 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 4.42 0.040 0.0 0.000 T 0
service trf
Outgoing to Turbine
46 Later 20 20BBA02 11kV Unit switchgear 2B 20BFA02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
service trf
47 Later 90 90BCA01 11kV Station switchgear 1 Outgoing to SST 90BFD01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
Outgoing to admin
48 Later 90 90BCA01 11kV Station switchgear 1 90BFS01 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 16.49 0.150 0.0 0.000 T 0
service trf
Outgoing to HVAC
49 Later 90 90BCA01 11kV Station switchgear 1 90BFW01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
service trf
Outgoing to demin
50 Later 90 90BCA01 11kV Station switchgear 1 90BFU01 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 18.41 0.167 0.0 0.000 T 0
water service trf
51 Later 90 90BCA01 11kV Station switchgear 1 Outgoing to SAT 90BCS01 TR 12000.00 11000 3 1.00 1.00 692.82 0.00 57 60 Later 1Cx630 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 3.53 0.032 0.0 0.000 T 0
Outgoing to CHP
53 E_0298 90 90BCA01 11kV Station switchgear 1 90BCE01 NM 15000.00 11000 3 1.00 1.00 866.03 0.00 857 900 Later 1Cx630 x2 XLPE Al 0.065 0.102 840 0.90 0.70 0.63 529 39.76 0.361 0.0 0.000 T 0
swgr
Outgoing to AHP
54 E_0296 90 90BCA01 11kV Station switchgear 1 90BCD01 NM 15000.00 11000 3 1.00 1.00 866.03 0.00 476 500 Later 1Cx630 x2 XLPE Al 0.065 0.102 840 0.90 0.70 0.63 529 22.09 0.201 0.0 0.000 T 0
swgr
Outgoing to bunker
55 E_0312 90 90BCA01 11kV Station switchgear 1 90BFK03 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 47 50 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.84 0.017 0.0 0.000 T 0
trf
Outgoing to colony
56 O_0001 90 90BCA02 11kV Station switchgear 2 Later NM 10000.00 11000 3 1.00 1.00 577.35 0.00 952 1000 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 49.09 0.446 0.0 0.000 T 0
supply
59 Later 90 90BCA02 11kV Station switchgear 2 Outgoing to SST 90BFD03 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
Outgoing to
60 Later 90 90BCA02 11kV Station switchgear 2 90BFX01 TR 1250.00 11000 3 1.00 1.00 72.17 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.55 0.50 196 9.20 0.084 0.0 0.000 D 0
switchyard service trf
Outgoing to water
61 Later 90 90BCA02 11kV Station switchgear 2 90BCJ01 NM 15000.00 11000 3 1.00 1.00 866.03 0.00 2380 2500 Later 1Cx630 x3 XLPE Al 0.065 0.102 840 0.90 0.55 0.50 416 73.64 0.669 0.0 0.000 G 0
system swgr
Outgoing to water
62 Later 90 90BCA03 11kV Station switchgear 3 90BCJ01 NM 15000.00 11000 3 1.00 1.00 866.03 0.00 2380 2500 Later 1Cx630 x3 XLPE Al 0.065 0.102 840 0.90 0.55 0.50 416 73.64 0.669 0.0 0.000 G 0
system swgr
Outgoing to raw
63 Later 90 90BCA03 11kV Station switchgear 3 water treatment 90BFQ02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 619 650 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 23.93 0.218 0.0 0.000 T 0
service trf
64 Later 90 90BCA03 11kV Station switchgear 3 Outgoing to SST 90BFD04 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
Outgoing to
65 Later 90 90BCA03 11kV Station switchgear 3 90BFX02 TR 1250.00 11000 3 1.00 1.00 72.17 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.55 0.50 196 9.20 0.084 0.0 0.000 D 0
switchyard service trf
Outgoing to colony
66 O_0002 90 90BCA03 11kV Station switchgear 3 Later NM 10000.00 11000 3 1.00 1.00 577.35 0.00 952 1000 Later 1Cx300 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 49.09 0.446 0.0 0.000 T 0
supply
68 Later 90 90BCA04 11kV Station switchgear 4 Outgoing to SAT 90BCS02 TR 12000.00 11000 3 1.00 1.00 692.82 0.00 57 60 Later 1Cx630 x2 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 3.53 0.032 0.0 0.000 T 0
69 Later 90 90BCA04 11kV Station switchgear 4 Outgoing to SST 90BFD02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
Outgoing to admin
70 Later 90 90BCA04 11kV Station switchgear 4 90BFS02 TR 1600.00 11000 3 1.00 1.00 92.38 0.00 666 700 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 16.49 0.150 0.0 0.000 T 0
service trf
Outgoing to HVAC
71 Later 90 90BCA04 11kV Station switchgear 4 90BFW02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 38 40 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.47 0.013 0.0 0.000 T 0
service trf
Outgoing to demin
72 Later 90 90BCA04 11kV Station switchgear 4 90BFU02 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 476 500 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 18.41 0.167 0.0 0.000 T 0
water service trf
Outgoing to CHP
73 E_0297 90 90BCA04 11kV Station switchgear 4 90BCE01 NM 15000.00 11000 3 1.00 1.00 866.03 0.00 857 900 Later 1Cx630 x2 XLPE Al 0.065 0.102 840 0.90 0.70 0.63 529 39.76 0.361 0.0 0.000 T 0
swgr
Outgoing to AHP
74 E_0299 90 90BCA04 11kV Station switchgear 4 90BCD01 NM 15000.00 11000 3 1.00 1.00 866.03 0.00 476 500 Later 1Cx630 x2 XLPE Al 0.065 0.102 840 0.90 0.70 0.63 529 22.09 0.201 0.0 0.000 T 0
swgr
2 of 6
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Power Cable Sizing Rev. P1
ELECTRICAL CONSUMER Length POWER CABLE SPECIFICATION CURRENT CARRYING CAPACITY VOLTAGE DROP
Laying
From Current Margin Impedance Derating Factors Running Starting
Unit No. Type of Rated Power Rated Derated (D: Duct bank SIZING OK ?
S.N. Load ID KKS Code To KKS Code Rated Power Phase Efficiency Actual (5% for MV, Size Type REMARKS
(10/20/90) (Switchgear Name) feeder Voltage Factor Ir Is Cable ID Resistance Reactance Current Current T: Tray, TR: Trench (YES/NO)
10% for LV)
G: Directly Buried)
(kW)/(kVA) (V) (A) (A) (m) (m) (sqmm) (line) (ohm/km) (ohm/km) (A) ft FdxFhxFc fT (A) (V) (%) (V) (%)
Outgoing to bunker
75 E_0313 90 90BCA04 11kV Station switchgear 4 90BFK04 TR 2500.00 11000 3 1.00 1.00 144.34 0.00 47 50 Later 3Cx240 x1 XLPE Al 0.162 0.102 395 0.90 0.70 0.63 249 1.84 0.017 0.0 0.000 T 0
trf
Outgoing feeder to
76 Later 90 90BCA02 11kV Station switchgear 2 11kV FGD Later NM 3200.00 11000 3 1.00 1.00 184.75 0.00 761 800 Later 1Cx630 x1 XLPE Al 0.130 0.112 840 0.90 0.70 0.63 529 30.25 0.275 0.0 0.000 T 0
switchgear
Outgoing feeder to
77 Later 90 90BCA03 11kV Station switchgear 3 11kV FGD Later NM 3200.00 11000 3 1.00 1.00 184.75 0.00 761 800 Later 1Cx630 x1 XLPE Al 0.130 0.112 840 0.90 0.70 0.63 529 30.25 0.275 0.0 0.000 T 0
switchgear
78 B_0059 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-A Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
79 B_0060 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-B Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
80 B_0061 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-C Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
81 B_0062 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-D Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
82 T_0025 10 10BBB01 3.3 kV Unit switchgear 1 Motor for CEP-1 Later MO 1200.00 3300 3 0.90 0.85 301.88 1811.29 142 150 Later 3Cx240 x2 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.28 0.190 24.3 0.736 T 0
83 T_0026 10 10BBB01 3.3 kV Unit switchgear 1 Motor for CEP-2 Later MO 1200.00 3300 3 0.90 0.85 301.88 1811.29 142 150 Later 3Cx240 x2 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.28 0.190 24.3 0.736 T 0
84 T_0027 10 10BBB01 3.3 kV Unit switchgear 1 Motor for CEP-3 Later MO 1200.00 3300 3 0.90 0.85 301.88 1811.29 142 150 Later 3Cx240 x2 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.28 0.190 24.3 0.736 T 0
86 M_0007 10 90BCB01 3.3 kV Station switchgear ACWP-A Later MO 350.00 3300 3 0.90 0.85 88.05 528.29 380 400 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 9.77 0.296 37.8 1.145 T 0
87 M_0025 20 90BCB01 3.3 kV Station switchgear ACWP-B Later MO 350.00 3300 3 0.90 0.85 88.05 528.29 380 400 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 9.77 0.296 37.8 1.145 T 0
88 B_0063 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-E Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
89 B_0064 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-F Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
90 B_0065 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-G Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
91 B_0066 10 10BBB01 3.3 kV Unit switchgear 1 Pulverizer motor-H Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
Boiler recirculation
92 B_0171 10 10BBB01 3.3 kV Unit switchgear 1 Later MO 360.00 3300 3 0.90 0.85 90.56 543.39 95 100 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 2.51 0.076 9.7 0.294 T 0
pump motor
95 B_0738 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-A Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
96 B_0739 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-B Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
97 B_0740 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-C Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
98 B_0741 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-D Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
99 T_0040 20 20BBB01 3.3 kV Unit switchgear 2 Motor for CEP-1 Later MO 1200.00 3300 3 0.90 0.85 301.88 1811.29 142 150 Later 3Cx240 x2 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.28 0.190 24.3 0.736 T 0
100 T_0041 20 20BBB01 3.3 kV Unit switchgear 2 Motor for CEP-2 Later MO 1200.00 3300 3 0.90 0.85 301.88 1811.29 142 150 Later 3Cx240 x2 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.28 0.190 24.3 0.736 T 0
101 T_0042 20 20BBB01 3.3 kV Unit switchgear 2 Motor for CEP-3 Later MO 1200.00 3300 3 0.90 0.85 301.88 1811.29 142 150 Later 3Cx240 x2 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.28 0.190 24.3 0.736 T 0
103 B_0742 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-E Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
104 B_0743 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-F Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
105 B_0744 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-G Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
106 B_0745 20 20BBB01 3.3 kV Unit switchgear 2 Pulverizer motor-H Later MO 625.00 3300 3 0.93 0.72 179.63 1077.79 238 250 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 11.83 0.358 48.2 1.460 T 0
Boiler recirculation
107 B_0851 20 20BBB01 3.3 kV Unit switchgear 2 Later MO 360.00 3300 3 0.90 0.85 90.56 543.39 95 100 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 2.51 0.076 9.7 0.294 T 0
pump motor
Outgoing feeder to
110 E_0330 90 90BCB01 3.3 kV Station switchgear Later NM 3200.00 3300 3 1.00 1.00 615.84 0.00 761 800 Later 1Cx630 x2 XLPE Al 0.065 0.090 840 0.88 0.70 0.62 517 25.13 0.762 0.0 0.000 T 0
FGD 3.3kV unit-A
111 M_0040 90 90BCB01 3.3 kV Station switchgear ACWP common Later MO 350.00 3300 3 0.90 0.85 88.05 528.29 380 400 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 9.77 0.296 37.8 1.145 T 0
3 of 6
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Power Cable Sizing Rev. P1
ELECTRICAL CONSUMER Length POWER CABLE SPECIFICATION CURRENT CARRYING CAPACITY VOLTAGE DROP
Laying
From Current Margin Impedance Derating Factors Running Starting
Unit No. Type of Rated Power Rated Derated (D: Duct bank SIZING OK ?
S.N. Load ID KKS Code To KKS Code Rated Power Phase Efficiency Actual (5% for MV, Size Type REMARKS
(10/20/90) (Switchgear Name) feeder Voltage Factor Ir Is Cable ID Resistance Reactance Current Current T: Tray, TR: Trench (YES/NO)
10% for LV)
G: Directly Buried)
(kW)/(kVA) (V) (A) (A) (m) (m) (sqmm) (line) (ohm/km) (ohm/km) (A) ft FdxFhxFc fT (A) (V) (%) (V) (%)
IA compressor motor-
112 M_0153 90 90BCB01 3.3 kV Station switchgear Later MO 550.00 3300 3 0.95 0.90 123.80 742.79 190 200 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.92 0.210 26.6 0.805 T 0
A
SA compressor
113 M_0156 90 90BCB01 3.3 kV Station switchgear Later MO 550.00 3300 3 0.95 0.90 123.80 742.79 190 200 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.92 0.210 26.6 0.805 T 0
motor-A
IA compressor motor-
114 M_0154 90 90BCB01 3.3 kV Station switchgear Later MO 550.00 3300 3 0.95 0.90 123.80 742.79 190 200 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.92 0.210 26.6 0.805 T 0
B
IA compressor motor-
115 M_0155 90 90BCB01 3.3 kV Station switchgear Later MO 550.00 3300 3 0.95 0.90 123.80 742.79 190 200 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.92 0.210 26.6 0.805 T 0
C
SA compressor
116 M_0157 90 90BCB01 3.3 kV Station switchgear Later MO 550.00 3300 3 0.95 0.90 123.80 742.79 190 200 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.92 0.210 26.6 0.805 T 0
motor-B
SA compressor
117 M_0158 90 90BCB01 3.3 kV Station switchgear Later MO 550.00 3300 3 0.95 0.90 123.80 742.79 190 200 Later 3Cx240 x1 XLPE Al 0.162 0.090 400 0.88 0.70 0.62 246 6.92 0.210 26.6 0.805 T 0
motor-C
Outgoing feeder to
118 E_0331 90 90BCB01 3.3 kV Station switchgear Later NM 3200.00 3300 3 1.00 1.00 615.84 0.00 761 800 Later 1Cx630 x2 XLPE Al 0.065 0.090 840 0.88 0.70 0.62 517 25.13 0.762 0.0 0.000 T 0
FGD 3.3kV unit-B
Outgoing feeder to
129 E_0773 10 10BGB01 Boiler PMCC-1 10BKB01 NM 811.00 415 3 1.00 1.00 1241.09 0.00 45 50 Later 1Cx630 x4 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.49 0.359 0.0 0.000 T 0
Boiler MCC
Outgoing feeder to
130 E_0774 10 10BGB01 Boiler PMCC-1 10BKR01 NM 647.00 415 3 1.00 1.00 990.12 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.59 0.382 0.0 0.000 T 0
Coal mill MCC
Outgoing feeder to
131 E_0775 10 10BGB01 Boiler PMCC-1 10BKR01 NM 647.00 415 3 1.00 1.00 990.12 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.59 0.382 0.0 0.000 T 0
Coal mill MCC
Outgoing feeder to
132 E_0776 10 10BGB01 Boiler PMCC-1 10BKB02 NM 59.00 415 3 1.00 1.00 90.29 0.00 54 60 Later 3.5Cx95 x1 XLPE Al 0.096 0.088 155 0.90 0.70 0.63 98 3.28 0.789 0.0 0.000 T 0
Soot blower MCC
Outgoing feeder to
133 E_0777 10 10BGB01 Boiler PMCC-1 10BKB02 NM 59.00 415 3 1.00 1.00 90.29 0.00 54 60 Later 3.5Cx95 x1 XLPE Al 0.096 0.088 155 0.90 0.70 0.63 98 3.28 0.789 0.0 0.000 T 0
Soot blower MCC
Outgoing feeder to
134 E_0778 10 10BGB01 Boiler PMCC-1 Boiler VLB and 10BKV01 NM 205.00 415 3 1.00 1.00 313.72 0.00 45 50 Later 3.5Cx240 x2 XLPE Al 0.061 0.086 280 0.90 0.70 0.63 176 1.86 0.449 0.0 0.000 T 0
Damper MCC
Outgoing feeder to
135 E_0781 10 10BGA01 Turbine PMCC-1 10BKW01 NM 487.00 415 3 1.00 1.00 745.27 0.00 31 35 Later 1Cx400 x3 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 1.32 0.317 0.0 0.000 T 0
Turbine valve ACDB
Outgoing feeder to
136 E_0779 10 10BGA01 Turbine PMCC-1 10BKA01 NM 145.00 415 3 1.00 1.00 221.90 0.00 50 55 Later 1Cx630 x1 XLPE Al 0.096 0.088 550 0.90 0.70 0.63 347 1.85 0.445 0.0 0.000 T 0
Turbine MCC
Outgoing feeder to
137 E_0780 10 10BGA01 Turbine PMCC-1 10BKA01 NM 145.00 415 3 1.00 1.00 221.90 0.00 50 55 Later 1Cx630 x1 XLPE Al 0.096 0.088 550 0.90 0.70 0.63 347 1.85 0.445 0.0 0.000 T 0
Turbine MCC
Outgoing feeder to
138 E_0782 10 10BGA01 Turbine PMCC-1 10BGC01 NM 608.00 415 3 1.00 1.00 930.44 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.49 0.359 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
139 E_0783 10 10BGA01 Turbine PMCC-1 10BGC01 NM 608.00 415 3 1.00 1.00 930.44 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.49 0.359 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
140 E_0797 10 10BKW01 Turbine valve ACDB-1 10BGC01 NM 145.00 415 3 1.00 1.00 221.90 0.00 45 50 Later 1Cx630 x1 XLPE Al 0.096 0.088 550 0.90 0.70 0.63 347 1.68 0.405 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
141 E_0784 20 20BGB01 Boiler PMCC-2 20BKB01 NM 777.00 415 3 1.00 1.00 1189.06 0.00 45 50 Later 1Cx630 x4 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.43 0.344 0.0 0.000 T 0
Boiler MCC
Outgoing feeder to
142 E_0785 20 20BGB01 Boiler PMCC-2 20BKB01 NM 777.00 415 3 1.00 1.00 1189.06 0.00 45 50 Later 1Cx630 x4 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.43 0.344 0.0 0.000 T 0
Boiler MCC
Outgoing feeder to
143 E_0786 20 20BGB01 Boiler PMCC-2 20BKR01 NM 635.00 415 3 1.00 1.00 971.76 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.56 0.375 0.0 0.000 T 0
Coal mill MCC
Outgoing feeder to
144 E_0787 20 20BGB01 Boiler PMCC-2 20BKR01 NM 635.00 415 3 1.00 1.00 971.76 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.56 0.375 0.0 0.000 T 0
Coal mill MCC
Outgoing feeder to
145 E_0788 20 20BGB01 Boiler PMCC-2 20BKB02 NM 59.00 415 3 1.00 1.00 90.29 0.00 54 60 Later 3.5Cx95 x1 XLPE Al 0.096 0.088 155 0.90 0.70 0.63 98 3.28 0.789 0.0 0.000 T 0
Soot blower MCC
Outgoing feeder to
146 E_0789 20 20BGB01 Boiler PMCC-2 20BKB02 NM 59.00 415 3 1.00 1.00 90.29 0.00 54 60 Later 3.5Cx95 x1 XLPE Al 0.096 0.088 155 0.90 0.70 0.63 98 3.28 0.789 0.0 0.000 T 0
Soot blower MCC
Outgoing feeder to
147 E_0790 20 20BGB01 Boiler PMCC-2 Boiler VLB and 20BKV01 NM 206.00 415 3 1.00 1.00 315.25 0.00 45 50 Later 3.5Cx240 x2 XLPE Al 0.061 0.086 280 0.90 0.70 0.63 176 1.87 0.452 0.0 0.000 T 0
Damper MCC
Outgoing feeder to
148 E_0793 20 20BGA01 Turbine PMCC-2 20BKW01 NM 145.00 415 3 1.00 1.00 221.90 0.00 31 35 Later 3.5Cx400 x1 XLPE Al 0.096 0.088 375 0.90 0.70 0.63 236 1.18 0.283 0.0 0.000 T 0
Turbine valve ACDB
4 of 6
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Power Cable Sizing Rev. P1
ELECTRICAL CONSUMER Length POWER CABLE SPECIFICATION CURRENT CARRYING CAPACITY VOLTAGE DROP
Laying
From Current Margin Impedance Derating Factors Running Starting
Unit No. Type of Rated Power Rated Derated (D: Duct bank SIZING OK ?
S.N. Load ID KKS Code To KKS Code Rated Power Phase Efficiency Actual (5% for MV, Size Type REMARKS
(10/20/90) (Switchgear Name) feeder Voltage Factor Ir Is Cable ID Resistance Reactance Current Current T: Tray, TR: Trench (YES/NO)
10% for LV)
G: Directly Buried)
(kW)/(kVA) (V) (A) (A) (m) (m) (sqmm) (line) (ohm/km) (ohm/km) (A) ft FdxFhxFc fT (A) (V) (%) (V) (%)
Outgoing feeder to
149 E_0791 20 20BGA01 Turbine PMCC-2 20BKA01 NM 385.00 415 3 1.00 1.00 589.18 0.00 50 55 Later 3.5Cx300 x3 XLPE Al 0.061 0.086 315 0.90 0.70 0.63 198 2.07 0.500 0.0 0.000 T 0
Turbine MCC
Outgoing feeder to
150 E_0792 20 20BGA01 Turbine PMCC-2 20BKA01 NM 385.00 415 3 1.00 1.00 589.18 0.00 50 55 Later 3.5Cx300 x3 XLPE Al 0.061 0.086 315 0.90 0.70 0.63 198 2.07 0.500 0.0 0.000 T 0
Turbine MCC
Outgoing feeder to
151 E_0794 20 20BGA01 Turbine PMCC-2 20BGC01 NM 582.00 415 3 1.00 1.00 890.65 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.43 0.344 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
152 E_0795 20 20BGA01 Turbine PMCC-2 20BGC01 NM 582.00 415 3 1.00 1.00 890.65 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.43 0.344 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
153 E_0799 20 20BKW01 Turbine valve ACDB-2 20BGC01 NM 145.00 415 3 1.00 1.00 221.90 0.00 45 50 Later 1Cx630 x1 XLPE Al 0.096 0.088 550 0.90 0.70 0.63 347 1.68 0.405 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
Raw water treatment plant
154 E_0824 90 90BGQ01 Clarified water and 90BKS01 NM 538.00 415 3 1.00 1.00 823.32 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.32 0.318 0.0 0.000 T 0
PMCC
Fire water MCC
Outgoing feeder to
Raw water treatment plant
155 E_0825 90 90BGQ01 Clarified water and 90BKS01 NM 538.00 415 3 1.00 1.00 823.32 0.00 45 50 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 1.32 0.318 0.0 0.000 T 0
PMCC
Fire water MCC
Raw water treatment plant Outgoing feeder to
156 E_0826 90 90BGQ01 90BKS02 NM 262.00 415 3 1.00 1.00 400.95 0.00 327 360 Later 3.5Cx400 x3 XLPE Al 0.061 0.086 375 0.90 0.70 0.63 236 7.28 1.754 0.0 0.000 T 0
PMCC WWTP MCC
Outgoing feeder to
163 E_0801 90 90BGD01 Station PMCC-1 90BKA01 NM 223.00 415 3 1.00 1.00 341.26 0.00 36 40 Later 3.5Cx240 x2 XLPE Al 0.061 0.086 280 0.90 0.70 0.63 176 1.62 0.391 0.0 0.000 T 0
Station ACDB-1
Outgoing feeder to
164 E_0802 90 90BGD01 Station PMCC-1 90BKY01 NM 474.00 415 3 1.00 1.00 725.37 0.00 159 175 Later 1Cx400 x3 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 6.40 1.543 0.0 0.000 T 0
HVAC MCC
Outgoing feeder to
165 E_0803 90 90BGD01 Station PMCC-1 90BKY01 NM 474.00 415 3 1.00 1.00 725.37 0.00 159 175 Later 1Cx400 x3 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 6.40 1.543 0.0 0.000 T 0
HVAC MCC
Outgoing feeder to
166 E_0804 90 90BGU01 Demin water PMCC 90BKE01 NM 107.00 415 3 1.00 1.00 163.74 0.00 45 50 Later 3.5Cx240 x1 XLPE Al 0.096 0.088 280 0.90 0.70 0.63 176 1.95 0.469 0.0 0.000 T 0
CPU MCC
Outgoing feeder to
167 E_0805 90 90BGU01 Demin water PMCC 90BKE01 NM 107.00 415 3 1.00 1.00 163.74 0.00 45 50 Later 3.5Cx240 x1 XLPE Al 0.096 0.088 280 0.90 0.70 0.63 176 1.95 0.469 0.0 0.000 T 0
CPU MCC
Outgoing feeder to
168 E_0806 90 90BGS01 Admin building PMCC Hydrogen generation 90BKE02 NM 354.00 415 3 1.00 1.00 541.74 0.00 159 175 Later 3.5Cx300 x3 XLPE Al 0.096 0.088 315 0.90 0.70 0.63 198 6.07 1.463 0.0 0.000 T 0
MCC
Outgoing feeder to
169 E_0807 90 90BGS01 Admin building PMCC Hydrogen generation 90BKE02 NM 354.00 415 3 1.00 1.00 541.74 0.00 159 175 Later 3.5Cx300 x3 XLPE Al 0.096 0.088 315 0.90 0.70 0.63 198 6.07 1.463 0.0 0.000 T 0
MCC
Outgoing feeder to
170 E_0808 90 90BGD02 Station PMCC-2 90BKA02 NM 174.00 415 3 1.00 1.00 266.28 0.00 36 40 Later 1Cx630 x1 XLPE Al 0.096 0.088 550 0.90 0.70 0.63 347 1.61 0.388 0.0 0.000 T 0
Station ACDB-2
Outgoing feeder to
171 E_0809 90 90BGD02 Station PMCC-2 90BKA02 NM 174.00 415 3 1.00 1.00 266.28 0.00 36 40 Later 1Cx630 x1 XLPE Al 0.096 0.088 550 0.90 0.70 0.63 347 1.61 0.388 0.0 0.000 T 0
Station ACDB-2
Outgoing feeder to
172 E_0810 90 90BGD02 Station PMCC-2 90BKE05 NM 475.00 415 3 1.00 1.00 726.90 0.00 127 140 Later 1Cx400 x3 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 5.13 1.237 0.0 0.000 T 0
Air compressor MCC
Outgoing feeder to
173 E_0811 90 90BGD02 Station PMCC-2 90BKE05 NM 475.00 415 3 1.00 1.00 726.90 0.00 127 140 Later 1Cx400 x3 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 5.13 1.237 0.0 0.000 T 0
Air compressor MCC
Outgoing feeder to
179 E_0813 90 90BGD02 Station PMCC-2 90BLA01 NM 540.00 415 3 1.00 1.00 826.38 0.00 159 175 Later 1Cx630 x3 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 4.63 1.116 0.0 0.000 T 0
Auxiliary boiler MCC
Outgoing feeder to
180 E_0814 90 90BGS01 Admin building PMCC 90BGK901 NM 99.00 415 3 1.00 1.00 151.50 0.00 63 70 Later 3.5Cx240 x1 XLPE Al 0.096 0.088 280 0.90 0.70 0.63 176 2.52 0.608 0.0 0.000 T 0
Fire station MCC
Outgoing feeder to
183 E_0830 90 90BGW01 HVAC PCC 90BLW01 NM 461.00 415 3 1.00 1.00 705.48 0.00 27 30 Later 3.5Cx400 x3 XLPE Al 0.096 0.088 375 0.90 0.70 0.63 236 1.07 0.257 0.0 0.000 T 0
HVAC CCB MCC
Outgoing feeder to
184 E_0831 90 90BGW01 HVAC PCC 90BLW01 NM 461.00 415 3 1.00 1.00 705.48 0.00 27 30 Later 3.5Cx400 x3 XLPE Al 0.096 0.088 375 0.90 0.70 0.63 236 1.07 0.257 0.0 0.000 T 0
HVAC CCB MCC
Outgoing feeder to
185 E_0832 90 90BGW01 HVAC PCC 90BLW02 NM 816.00 415 3 1.00 1.00 1248.75 0.00 18 20 Later 1Cx630 x4 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 0.60 0.145 0.0 0.000 T 0
HVAC TG-1 MCC
5 of 6
OBRA “C” 2x660 MW THERMAL POWER EXTENSION PROJECT Power Cable Sizing Rev. P1
ELECTRICAL CONSUMER Length POWER CABLE SPECIFICATION CURRENT CARRYING CAPACITY VOLTAGE DROP
Laying
From Current Margin Impedance Derating Factors Running Starting
Unit No. Type of Rated Power Rated Derated (D: Duct bank SIZING OK ?
S.N. Load ID KKS Code To KKS Code Rated Power Phase Efficiency Actual (5% for MV, Size Type REMARKS
(10/20/90) (Switchgear Name) feeder Voltage Factor Ir Is Cable ID Resistance Reactance Current Current T: Tray, TR: Trench (YES/NO)
10% for LV)
G: Directly Buried)
(kW)/(kVA) (V) (A) (A) (m) (m) (sqmm) (line) (ohm/km) (ohm/km) (A) ft FdxFhxFc fT (A) (V) (%) (V) (%)
Outgoing feeder to
186 E_0833 90 90BGW01 HVAC PCC 90BLW02 NM 816.00 415 3 1.00 1.00 1248.75 0.00 18 20 Later 1Cx630 x4 XLPE Al 0.061 0.086 550 0.90 0.70 0.63 347 0.60 0.145 0.0 0.000 T 0
HVAC TG-1 MCC
Outgoing feeder to
187 E_0834 90 90BGW01 HVAC PCC 90BLW03 NM 700.00 415 3 1.00 1.00 1071.23 0.00 31 35 Later 1Cx400 x4 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 1.42 0.342 0.0 0.000 T 0
HVAC TG-2 MCC
Outgoing feeder to
188 E_0835 90 90BGW01 HVAC PCC 90BLW03 NM 700.00 415 3 1.00 1.00 1071.23 0.00 31 35 Later 1Cx400 x4 XLPE Al 0.096 0.088 435 0.90 0.70 0.63 274 1.42 0.342 0.0 0.000 T 0
HVAC TG-2 MCC
Outgoing feeder to
189 E_0818 90 90BGU01 Demin water PMCC 90BKU01 NM 111.00 415 3 1.00 1.00 169.87 0.00 472 520 Later 3.5Cx400 x2 XLPE Al 0.096 0.088 375 0.90 0.70 0.63 236 6.68 1.610 0.0 0.000 T 0
PT MCC
Outgoing feeder to
190 E_0819 90 90BGU01 Demin water PMCC 90BKU01 NM 111.00 415 3 1.00 1.00 169.87 0.00 472 520 Later 3.5Cx400 x2 XLPE Al 0.096 0.088 375 0.90 0.70 0.63 236 6.68 1.610 0.0 0.000 T 0
PT MCC
Outgoing feeder to
191 E_0346 90 10BGC01 Emergency PMCC-1 90BGX01 NM 340.00 415 3 1.00 1.00 520.31 0.00 454 500 Later 1Cx630 x4 XLPE Al 0.061 0.086 550 0.90 0.55 0.495 272 6.25 1.505 0.0 0.000 G 0
Switchyard PMCC
Outgoing feeder to
192 E_0347 91 10BGC02 Emergency PMCC-2 90BGX02 NM 205.00 415 3 1.00 1.00 313.72 0.00 72 80 Later 3.5Cx240 x2 XLPE Al 0.061 0.086 280 0.90 0.70 0.63 176 2.98 0.719 0.0 0.000 T 0
Essential PMCC
Outgoing feeder to
193 E_0348 92 10BGC03 Emergency PMCC-3 90BGX03 NM 206.00 415 3 1.00 1.00 315.25 0.00 72 80 Later 3.5Cx240 x2 XLPE Al 0.061 0.086 280 0.90 0.70 0.63 176 3.00 0.722 0.0 0.000 T 0
Essential PMCC
Supply to charger-1
194 E_0341 10 10BGC01 Emergency PMCC-1 24V DC system for Later NM 44.00 415 3 1.00 1.00 67.33 0.00 72 80 Later 3.5Cx70 x1 XLPE Al 0.769 0.110 130 0.90 0.70 0.63 82 4.51 1.087 0.0 0.000 T 0
Unit-1
Supply to charger-2
195 E_0343 10 10BGC01 Emergency PMCC-1 24V DC system for Later NM 44.00 415 3 1.00 1.00 67.33 0.00 72 80 Later 3.5Cx70 x1 XLPE Al 0.769 0.110 130 0.90 0.70 0.63 82 4.51 1.087 0.0 0.000 T 0
Unit-1
Supply to charger-1
196 E_0723 20 20BGC01 Emergency PMCC-2 24V DC system for Later NM 44.00 415 3 1.00 1.00 67.33 0.00 72 80 Later 3.5Cx70 x1 XLPE Al 0.769 0.110 130 0.90 0.70 0.63 82 4.51 1.087 0.0 0.000 T 0
Unit-2
Supply to charger-2
197 E_0725 20 20BGC01 Emergency PMCC-2 24V DC system for Later NM 44.00 415 3 1.00 1.00 67.33 0.00 72 80 Later 3.5Cx70 x1 XLPE Al 0.769 0.110 130 0.90 0.70 0.63 82 4.51 1.087 0.0 0.000 T 0
Unit-2
Outgoing to
198 B_0589 10 10BGC01 Emergency PMCC-1 415V/240V Later NM 22.22 415 3 1.00 1.00 34.00 0.00 45 50 Later 3.5Cx16 x1 XLPE Al 2.290 0.128 64 0.90 0.70 0.63 40 6.13 1.477 0.0 0.000 T 0
emergency local
normal LDB#1
Outgoing to
199 B_0590 10 10BGC01 Emergency PMCC-1 415V/240V Later NM 22.22 415 3 1.00 1.00 34.00 0.00 45 50 Later 3.5Cx16 x1 XLPE Al 2.290 0.128 64 0.90 0.70 0.63 40 6.13 1.477 0.0 0.000 T 0
emergency local
normal LDB#2
Outgoing to
200 B_1269 20 20BGC01 Emergency PMCC-2 415V/240V Later NM 22.22 415 3 1.00 1.00 34.00 0.00 45 50 Later 3.5Cx16 x1 XLPE Al 2.290 0.128 64 0.90 0.70 0.63 40 6.13 1.477 0.0 0.000 T 0
emergency local
normal LDB#1
Outgoing to
201 B_1270 20 20BGC01 Emergency PMCC-2 415V/240V Later NM 22.22 415 3 1.00 1.00 34.00 0.00 45 50 Later 3.5Cx16 x1 XLPE Al 2.290 0.128 64 0.90 0.70 0.63 40 6.13 1.477 0.0 0.000 T 0
emergency local
normal LDB#2
EMLDB Unit-1 (Bus-
202 E_0260 10 10BGC01 Emergency PMCC-1 Later NM 100.00 415 3 1.00 1.00 153.03 0.00 45 50 Later 3.5Cx240 x1 XLPE Al 0.247 0.094 280 0.90 0.70 0.63 176 1.82 0.438 0.0 0.000 T 0
1)
212 P_0122 10 10BGC01 Emergency PMCC-1 Emergency lighting Later NM 21.43 415 3 1.00 1.00 32.79 0.00 45 50 Later 3.5Cx16 x1 XLPE Al 2.290 0.128 64 0.90 0.70 0.63 40 5.91 1.425 0.0 0.000 T 0
Outgoing feeder to
213 E_0771 10 10BGC01 Emergency PMCC-1 Later NM 460.57 415 3 1.00 1.00 704.82 0.00 72 80 Later 3.5Cx400 x3 XLPE Al 0.122 0.088 375 0.90 0.70 0.63 236 2.84 0.685 0.0 0.000 T 0
CCB MCC