Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

As per ANSI/ASHRAE standards 62.1.

2004

- Recommendation provide 3.7 lit/sec/m2 and exhaust is not required if two or more sides
comprise walls that are at least 50% to the outside.

- Provide indoor air quality for the system.

- For smoke management system the smoke zone shall be 2500 m2.

Therefore, for our project shall be the following:

- The selected area shall be ventilating according the ASHRAE standards 62.1.2004 by 3.7
lit/sec/m2.

For 12000 m2

cfm = 12000 x 3.7 x 2.1 = 93.240 cfm.

Shall be divided into 5 exhaust fan two speed fire protected each one as 20 000 cfm as
ventilation, 14.1 m3/sec.

As per smoke calculations the second shall be 30 000 cfm for smoke removal at 300 C for one
ECG Engineering Consultants Group

Project Name: Nozha City Center Date: 10/2007


Project No: 1127 Computed By: A .Salah

SMOKE MANAGEMENT DESIGN CALCULATION SHEET

Area Served: Car Park


Ventilation Type: Mechanical Ventilation Fans
Brief description: Exhaust through high temperature rated fans.
Fresh Air make-up through Ramps and slab openings.

Design Parameters:

Fire Size (A) = 4 x 4


Fire Area = 14 m2
Heat Rate ( Qr) = 278 kw/m2
Heat Production (Q) = 4000 kw
Perimeter ( P ) = 15.19 m
Smoke Layer Height (Y) = 2.5 m
Smoke Layer Depth (Db) = 1.5 m
Air Specific Heat ( Cp) = 1.01 kj/kg.k
Outside Air Temp. (To) = 40 Deg.c 313 k

Calculations

Min. Smoke Flow Rate (Mf) = 1.5


0.188 x P x Y
= 11.29 kg/s

Temperature Rise (Tr) = Q / (Mf x Cp)


= = 350.7 Deg.c

Max. Smoke Temp. (Tc) = To + Tr


0
= = 390.7 Deg. c 664 K

Air Volume Flow rate (Ma) = Mf x Tc / (1.2 x To)


= 3
19.95 m /s

= 42300 cfm
Note:
As per ANSI/ASHRAE standards 62.1.2004
Recommendation provide 3.7 lit/sec/m2
Parking Area= 12000 m2
93250 cfm
Shall be divided into 5 exhaust fans two speed fire protected each one is 20 000 cfm for ventilation.
As per NFPA part 92B
Car parking area divided into 5 fire zones 2500 m2 each , Total exhaust 50,000 cfm.

Direct drive two speed smoke exhaust fans of 14.1 m 3/s (30,000 cfm) rating shall be provided in each
parking zone , Fire rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.

Make up fresh air shall be supplied from Ramps and Slab opening.
ECG Engineering Consultants Group

Project Name: Nozha City Center Date: 10/2007


Project No: 1127 Computed By: A .Salah

SMOKE MANAGEMENT DESIGN CALCULATION SHEET

Area Served: Car Park


Ventilation Type: Mechanical Ventilation Fans
Brief description: Exhaust through high temperature rated fans.
Fresh Air make-up through Ramps and slab openings.
Design Parameters

Q = Heat Production
M = Total fuel mass consumed
Z = Height above the fuel

Q= 4000 kw
ρ= 1.2 kg /m3 @20 OC
z= 2.5
M = 0.071 Q1/3 X Z 5/3 + 0.0018 Q NFPA part 92B Chapter 7

= 0.071*((4000)^(1/3))*((2.5)^(5/3))+((0.0018*4000))

M= 12.4 kg/sec

V= 10.3 m3/sec
V= 21900 cfm

Note:
Nos. Smoke exhaust fans of cfm shall be inter locked with fire system
The Exhaust fans shall be Rated for 300 Deg.c for 1 hr.
ECG Engineering Consultants Group

Project Name: Nozha City Center Date: 10/2007


Project No: 1127 Computed By: A .Salah

SMOKE MANAGEMENT DESIGN CALCULATION SHEET

Area Served:Shopping Mall


Ventilation Type:Exhaust through high temperature rated fans.
Brief description:Fresh Air make-up through open doors

Design Parameters

Area of the Fire = 2 x 2


2
A= 4m
Perimeter of the Fire (P) P= 8m
Heat Rate (Qr ) Qr = 556 kw/m2
Heat energy of Fire Q= 2224 kw
Density of warm gases at height Z ρ= 1.2 kg/m5
Gravity Acceleration g= 9.81 m/s3
Width Of Shop W= 3 m
Air Specific Heat cp = 1.01 kj/kg.k
Outside Air Temp. T= 40 Deg.c 313 K
Height above void edge h= 16 m
Effective layer depth d= 13 m
Smoke layer height (above void edge) (Z) h-d= 3m
Height of shop compartment Δ= 3m
Empirical height (of vertical source below void edge)
0.3 x h = 0.9 m
(L)
2 1/3
0.58 x p x {(g x Qf x w ) / ( p x cp x Ta )} X (Z + L ) X {1
Mass flow of smoky gases (passing height Z) Mf =
+ 0.22 ( Z + 2L ) / W } 2/3

Mf = 32.15 kg/sec
Tempreture Rise Ө = Qf /Mf x cp )
Ө= 68.48 Deg.0c
Outside Air Temp. Tc = 341.48 K
Air Volume Flow rate V = ( Mf x Tc / 1.2 x Ta )
29.23 m3/s
V = 61950 cfm
Note:
4 Nos. Smoke exhaust fans of shall be provided on the Roof
The Exhaust fans shall be Rated for 300 Deg.c for 1 hr.
ECG Engineering Consultants Group

Project Name: Nozha City Center Date: 4-2008


Project No: 1127 Computed By: A .Salah

SMOKE CONTROL FOR THE BUILDING

Area Served: Shopping Mall


Ventilation Type: Exhaust through high temperature rated fans.
Brief description: Fresh Air make-up through open doors.

Design Parameters
Q= Total heat output of a fire (Kw)
D= Diameter of fire source.
zo = Virtual origin.
Qc = Convective portion of total heat release = Q / 1.5
Z1 = mean Flame height Z = Smoke clear height.
D= Flame diameter = Aeq ^ 0.5
M= Mass flow rate in the plume.
dT = Qc / MCp
Cp = Specific heat capacity of air ( 1KJ/Kg.K )
d= Depth of smoke layer.
 = 2 when extraction near wall & 2.8 when away from wall.
N= min number of extraction points from smoke layer.
0.5
M QC  gd 5T0 T 
V   M crit   2 
 0  0 T0 C P  ( T  T0 ) 

Z O  0.083 Q 2 / 5  1.02 D
Small diameter source Large diamter source
2/5 2/5
QC QC
 14  14
D D
2/3
0.035.QC
z1  0.2.QC
2/5
z1 
( D  0.074.QC ) 2 / 3
2/5

Flame height lower than smoke clear height

M  0.071.QC .(z  z0 )5 / 3 M  0.071.QC .z 5 / 3


1/ 3 1/ 3

Flame height greater than smoke clear height

0.0054.QC .z
M 
 z0
2/5
0.166.QC
Plume Temperature Number of extraction points
QC M
Tm   To N 
Mcrit
M .Cp
q= 500 KW/m²
Aeq = 4 m²
Q= 3000 KW
Qc = 2000 KW
D= 2.0 m
2/5
Qc = 21 14 D = 28 Large
2/5
Qc /D = 10.46 Large diameter source
z= 4.5 m zo = 0.0014
H= 6.0 m To = 40 °C
d= 1.5 m To = 313 K
Small diameter source Large diamter source

z1= 4.2 m z1= 2.4 m


Flame is not a smoke layer
Flame height lower than smoke clear height

M= 11.0 Kg/S M= 11.0 Kg/S.


dT = 182.4 °C dT = 182.3 °C
TM = 495.4 K TM = 495 K
V= 14.5 m³/S V= 14.5 m³/S
Mcr = 8.3 Kg/S Mcr = 8.3 Kg/S
V= 30650 cfm V= 30700 cfm
N= 2 N= 2
If Extraction away from wall  =2.8
Mcr = 11.7 Kg/S Mcr = 11.7 Kg/S
N= 1 N= 1

Flame height greater than smoke clear height

M= 14.0 Kg/S.
dt = 142.9 °C
Tplume = 455.9 K
V= 17.0 m³/S
Mcr = 8.0 Kg/S
V= 36000 cfm

DEEP SEATED COMBUSTION


M= 14.2 Kg/S.

Note:
**** Nos. Smoke exhaust fans of *** cfm shall be provided on the Roof

The Exhaust fans shall be Rated for 300 Deg.oc for 1 hr.
ECG Engineering Consultants Group

Project Name: Nozha City Center Date: 10/2007


Project No: 1127 Computed By: A .Salah

SMOKE MANAGEMENT DESIGN CALCULATION SHEET

Area Served: Offices


Ventilation Type: Mechanical Ventilation Fans
Brief description: Exhaust through high temperature rated fans.
Fresh Air make-up through automatic doors.
Design Parameters:

Fire Size (A) = 2 x 2


2
Fire Area = 4 m
Heat Rate ( Qr) = 93 kw/m2
Heat Production (Q) = 372 kw
Perimeter ( P ) = 8 m
Smoke Layer Height (Y) = 2.5 m
Smoke Layer Depth (Db) = 1.5 m
Air Specific Heat ( Cp) = 1.01 kj/kg.k
Outside Air Temp. (To) = 40 Deg.c 313 k

Calculations

1.5
Min. Smoke Flow Rate (Mf) = 0.188 x P x Y
= 5.9451 kg/s

Temperature Rise (Tr) = Q / (Mf x Cp)


= 61.953 Deg.c

Max. Smoke Temp. (Tc) = To + Tr


= 101.95 Deg.c 375 k

Air Volume Flow rate (Ma) = Mf x Tc / (1.2 x To)


= 5.93 m3/s
= 12600 cfm
Note:
As per ANSI/ASHRAE standards 62.1.2004
Recommendation provide 3.7 lit/sec/m2
Parking Area= 12000 m2
93300 cfm
Shall be divided into 5 exhaust fans two speed fire protected each one is 20 000 cfm for ventilation.

As per NFPA part 92B

Car parking area divided into 5 fire zones 2500 m2 each , Total exhaust 50,000 cfm.

Direct drive two speed smoke exhaust fans of 14.1 m3/s (30,000 cfm) rating shall be provided in each parking zone , Fire
rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.

Make up fresh air shall be supplied from Ramps and Slab opening.
ECGEngineering Consultants Group

PROJECT NAME: PRIME TOWER DATE: 4/2007


PROJECT NO.: 1147 COMPUTED BY: A. Salah

STAIR CASE PRESSURIZATION DESIGN CALCULATION SHEET

Input Data:
No. of levels (including ground floor) : 9
Average level height : 3 m
2
Floor Area : 2200 m
2
Exterior building wall area per floor : 105 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
2
Stairwell wall area per floor : 14 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
2
Elevator shaft walls : 14 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
2
The area gap around each stairwell door : 0.024 m
Outside design temperature : 46 deg C
Stairwell temperature : 28 deg C

Stairwell door width : 1 m


Stairwell door height : 2.1 m
Force to overcome door closer : 53 N
Distance from door knob to
edge of knob side of door : 75 mm

Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 20 Pa

Critical Velocity : 1.524 m/s

Height Limit Check:

Maximum allowable pressure difference


between the stairwell and the building = 70.48 Pa

Height limit below which satisfactory


pressurization is possible = 209.3 m
Calculations:
2
Abo Flow area between the building and outside per floor = 0.022 m
2
Asb Flow area between stairwell and the building per floor = 0.026 m
B Pressure difference per height due to stack effect = 0.6 Pa/m
Psb Pressure difference between stairwell top and the building = 27.5 Pa

Simple stairwell pressurization:


Q Flow rate of the pressurization air = 0.9 m3/s (=

Canadian stairwell pressurization:

In this system, an exterior stairwell door opens automatically upon system activation. In addition,
the lower two floors will be considered opened, while the others doors will be considered closed

I. Opened doors section:


Pressure difference at the bottom of the section = 20 Pa
Pressure difference at the top of the section = 21.66 Pa
Flow factor = 3.83 m/s
2
Open stairwell flow area = 0.85 m
Effective flow area = 0.02 m2
Flow rate from this section = 0.17 m3/s (=

II. Closed doors section:


Pressure difference at the bottom of the section = 50.72 Pa
Pressure difference at the top of the section = 64.34 Pa
Flow factor = 6.36 m/s
2
Effective flow area = 0.03 m
Flow rate from this section = 1.14 m3/s (=

III. Exterior stairwell door:


Pressure difference at the exterior door
(~ at 1.5m height) = 47.81 Pa
2
Open exterior stairwell door effective flow area = 0.85 m
Flow rate from this section = 4.95 m3/s (=

The total flow needed to pressurize the stairwell


at the above conditions is the sum of these three
separate flows = 0.17 + 1.136 +
3
= 6.25 m /s
(=

PROVIDE STAIRCASE PRESSURIZATION FAN ( 13,500 CFM ) FOR EACH STAIR


ON SHEET

Wall Tightness - Area ratio


Construction element Tight Av. Loose V. Loose
, 3=Loose, 4=Very Loose) 1 2 3 4
Exterior building walls 0.00007 0.00021 0.00042 0.0013
Stairwell walls 1.4E-05 0.00011 0.00035
Elevator shaft walls 0.00018 0.00084 0.0018
Floors 5.2E-05

Door Width (mm)


Door Closer Force (N)
800 900 1000 1100
26 112.5 100 92.5 85
35 102.5 92.5 85 77.5
44 92.5 85 75 70
53 85 75 67.5 62.5
62 75 67.5 60 55
2000 cfm)

on. In addition,
sidered closed

357 cfm)

2408 cfm)

10484 cfm)

5
13250 cfm)

FOR EACH STAIR


(mm)
1200
77.5
70
65
57.5
52.5
ECG Engineering Consultants Group
Project Name: Nozha City Center Date: 10/2007
Project No: 1127 Computed By: A .Salah

Calculation Tile: Stair Pressurisation

Area Served: Stair case pressurisation


Ventilation Type: Pressurisation
Brief description: Fans Provided on Roof of stair case pressurisation

Design Parameters

Total no of Floors = 20
Egres Velocity across open door (Qs) = 0.75 m/s
Area of open door = 2.1 x 1
= 2.1 m2
Number of open door (n) = 2
Egres Velocity (Ve) = 0.6 x Qs / A x n
Qs = Ve x A x n / 0.6
5.25 m3/s

Leakage through closed doors on all floors


Leakage area of single leaf door = 0.024 sq.m
Air leakage thru closed tair case = k x Ae x p^0.5
0.14 m3/s
Total no of closed doors= 18.00 nos
total Leakage thru closed doors= 2.53 m3/s

Adding 1 & 2 = 6.52 m3/s


= 13800 cfm

Note:-
Two no,supply roof top fan of 5.39 m3/sec (12000cfm) will be provided on the Roof of stair case.
ECG Engineering Consultants Group

Project Name: Nozha City Center Date: 10/2007


Project No: 1127 Computed By: A .Salah

SMOKE CONTROL FOR LIFT SHAFT

Area Served: Lift Shaft


Ventilation Type: Pressurisation
Brief description: Fans Provided on Roof

Design Parameters

Total no of Floors = 20
Egres Velocity (Ve) =
Area of door = 2.1 x 1
= 2.1 m2
Leakage through closed doors on all floors 0.06 sq.m
Leakage area of lift landing door ) =
Air leakage thru lift landing door (Q) = k x Ae x p^0.5
0.35 m3/s
Total no of closed doors= 18 nos
total Leakage thru closed doors= 6.33 m3/s
13450 cfm
ECG Engineering Consultants Group

Project Name: Date: 10/2007


Project No: Computed By: A .Salah
Transformer Heat Dissipation
Total
Power Iron Loss Copper Loss Air Cap Cfm
KVA Wall Watt
Loss
∆T = 18
∆T = 18 ∆T = 9 Air Cap cmh ∆T = 18 ∆T = 9
Watt
50 210 1250 1460 260 260 520 442 450 890
100 340 2150 2490 440 440 880 748 750 1500
160 480 3100 3580 630 630 1260 1071 1080 2150
200 570 3600 4170 740 740 1470 1258 1260 2500
300 720 5450 6170 1090 1090 2170 1853 1860 3690
500 1000 7800 8800 1550 1550 3090 2635 2640 5260
800 1450 11000 12450 2190 2190 4380 3723 3730 7450
1000 1750 13500 15250 2680 2680 5360 4556 4560 9120
1500 2550 19800 22350 3930 3930 7850 6681 6690 13350
2000 3900 22500 26400 4640 4640 9270 7888 7890 15760

Heat Dissipation Calc From Carrier Hand Book.


Motor In, Motor In, Motor In,
CFM CFM CFM CFM CFM ∆T CFM
HP KW Machine out. Machine In. Machine
∆T = 9 ∆T = 18 ∆T = 9 ∆T = 18 =9 ∆T = 18
Btu/Hr (PUMP) Btu/Hr (AHU) Out. Btu/Hr
2 1.5 1,280 140 70 6,380 660 330 5,100 530 270
3 2.2 1,800 190 100 9,450 980 490 7,650 790 400
5 3 2,800 290 150 15,600 1,610 810 12,800 1,320 660
7.5 4 3,400 350 180 22,500 2,320 1,160 19,100 1,970 990
10 5.5 5,400 560 280 30,000 3,090 1,550 25,500 2,630 1,320
15 7.5 6,300 650 330 44,500 4,580 2,290 38,200 3,940 1,970
20 11 7,500 780 390 58,500 6,020 3,010 51,000 5,250 2,630
25 14.7 8,800 910 460 72,400 7,450 3,730 63,600 6,550 3,280
30 18.5 9,400 970 490 85,800 8,830 4,420 76,400 7,870 3,940
40 22 13,000 1,340 670 115,000 11,840 5,920 102,000 10,500 5,250
50 30 16,000 1,650 830 143,000 14,720 7,360 127,000 13,070 6,540
60 37 19,000 1,960 980 172,000 17,700 8,850 153,000 15,750 7,880
75 44 21,000 2,170 1,090 212,000 21,820 10,910 191,000 19,660 9,830
100 55 29,000 2,990 1,500 284,000 29,220 14,610 255,000 26,240 13,120
125 73.5 36,000 3,710 1,860 354,000 36,420 18,210 318,000 32,720 16,360
ECG Engineering Consultants Group
Project Name: Nozha City Center Date: 10/2007
Project No: 1127 Computed By: A .Salah
PUMPS ELECTRICAL POWER SUPPLY

ft m gpm l\s l/s gpm m ft


100.0 30.480 100.0 6.309 1.0 15.850 1.0 3.281
Put the GPM & Head in the cells, then see the HP, then get the standard HP from table and then put the equivalent kw.
GPM , ft , HP L\S , m , HP Standard HP Standard KW
GPM H ft HP L\S Hm HP 1 0.75

100 20 0.8 6.3 30.48 3.9 1.5 1.1

200 120 9.3 12.0 40 9.7 2 1.5

300 140 16.3 14.0 50 14.1 3 2.2

400 160 24.9 16.0 60 19.4 4 3

500 180 35.0 18.0 70 25.5 5.5 4

600 200 46.6 20.0 80 32.3 7.5 5.5

700 220 59.8 25.0 90 45.5 10 7.5

800 240 74.6 30.0 100 60.6 15 11

900 260 90.9 35.0 120 84.9 20 14.7

1000 280 108.8 40.0 140 113.1 25 18.5

1100 300 128.2 45.0 160 145.5 30 22

1200 320 149.2 50.0 180 181.8 40 30

1300 340 171.7 60.0 200 242.4 50 37

1400 360 195.8 70.0 250 353.6 60 44

1500 380 221.4 80.0 300 484.9 75 55

1600 400 248.6 90.0 400 727.3 100 73.5


ECG Engineering Consultants Group

Project Name: Nozha City Center


Project No: 1127 3- Phase Amper = 380 x I x 0.8 x (3^0.5)
FANS ELECTRICAL POWER SUPPLY 1- Phase Amper = 220 x I x 0.8
Put the CFM in the cell, the see the KW , then get the standard KW from table.
FAN SECTION, IN LINE AXIAL FANS
0.5" STATIC 1" STATIC 1.5" STATIC 0.1" STATIC
CFM KW CFM KW CFM KW CFM KW
100 0.01 200 0.04 300 0.09 200 0.01
200 0.02 400 0.08 600 0.18 400 0.02
300 0.03 600 0.12 900 0.27 600 0.02
400 0.04 800 0.16 1200 0.36 800 0.03
500 0.05 1000 0.20 1500 0.46 1000 0.04
600 0.06 1500 0.30 2000 0.61 1200 0.05
700 0.07 2000 0.40 3000 0.91 1400 0.06
800 0.08 2500 0.51 4000 1.21 1600 0.06
900 0.09 3000 1.42 5000 1.52 1800 0.07
1000 0.10 5000 1.01 6000 1.82 2000 0.08

FAN SECTION, IN LINE AXIAL FANS


2" STATIC 3" STATIC 4" STATIC 0.5" STATIC
CFM KW CFM KW CFM KW CFM KW
500 0.20 1000 0.61 2500 2.02 500 0.10
1500 0.61 3000 1.82 5000 4.05 1000 0.20
2500 1.01 5000 3.04 7500 6.07 1500 0.30
3500 1.42 7000 4.25 10000 8.10 2000 0.40
4500 1.82 9000 5.46 12500 10.12 2500 0.51
5500 2.23 11000 6.68 15000 12.14 3000 0.61
6500 2.63 13000 7.89 17500 14.17 5000 1.01
7500 3.04 15000 9.11 20000 16.19 8000 1.62
8500 3.44 17000 10.32 22500 18.21 10000 2.02
10000 4.05 20000 12.14 25000 20.24 15000 3.04
ECG Engineering Consultants Group
Project Name:

Package Units "Carrier" r-22

Hermatic - Scroll Compressor, Axial fan Condencer

Unit Size CFM Btu\hr TR Cooling Elec Heater P.Supply KW 3 KW Cooling Width Cond Height Cond Height+Evap Depth Cond Nominal Air Flow cfm
m \HR
55 2,000 54,000 4.5 6 7.25 3,400 15.98 890 1,069 1,605 753 3,000
90 3,000 84,000 7 15 11.2 5,100 25.12 1,338 1,165 1,828 766 5,900
110 3,500 108,000 9 15 14.5 5,950 31.97 1,338 1,165 1,828 766 5,900
145 6,000 144,000 12 18 19.4 10,200 42.20 1,593 1,405 2,201 824 7,650
180 6,000 168,000 14 18 21 10,200 50.12 1,593 1,405 2,197 824 7,650
240 7,000 229,200 19.1 22.5 34.9 11,900 67.41 2,088 1,405 2,059 1,060 10,500

Roof Top Package Units "Trane" R-22-105 oF

Unit Size CFM MBtu\hr TR Cooling Elec Heater P.Supply KW 3 KW Cooling Width Height Length Weight Comp type
m \HR
190 4000-6500 192 16.0 18 20.1 6800-11050 56.29 1,976 1,333 2,271 705 Hermatic Receprocating
240 5400-8400 242 20.1 18 22.1 9520-14280 70.79 2,263 1,303 2,677 859 Hermatic Scroll
260 6000-9000 255 21.3 18 24.1 10200-15300 74.72 2,263 1,303 2,677 920 Hermatic Scroll
320 7000-11500 324 27.0 18 37.1 11900-19550 94.93 2,263 1,303 2,677 955 Hermatic Scroll
360 9500-14000 338 28.2 36 35.6 16150-23800 99.09 2,235 1,776 5,207 1,600
420 10500-15000 378 31.5 36 36.6 17850-25500 110.78 2,235 1,776 5,207 1,650
480 12500-17000 466 38.8 36 66.1 21250-28900 136.54 2,235 1,776 5,207 1,691
600 14000-19000 593 49.4 36 74.1 23800-32300 173.60 2,235 1,776 5,207 1,886

Air cooled condencer (Carrier) R-22

Hermatic - Scroll Compressor, Axial fan Condencer

Unit Size KW Cooling Btu\hr TR Cooling No of Comp P.S KW/


Total
compP.S KW + (0.736*2)
Refregerant
Cond Width Height+10 cm Base Depth weight kg KG\m 2

38-RM-15 60.4 206,000 17.2 2 8.96 19.4 R-22 2,035 1,635 1,260 600 291
38-RM-20 75.0 256,000 21.3 2 11.59 24.7 R-22 2,035 1,635 1,260 740 359
38-RM-25 89.1 304,000 25.3 2 13.63 28.7 R-22 2,035 1,635 1,260 820 398
38-RM-30 120.8 421,000 34.3 2 8.96 38.7 R-22 2,035 1,635 2,520 1,300 316
38-RM-35 135.4 462,000 38.5 2 11.59 44.0 R-22 2,035 1,635 2,535 1,400 338
38-RM-40 150.1 412,000 42.7 2 11.59 49.3 R-22 2,035 1,635 2,535 1,480 357
38-RM-45 164.1 560,000 46.7 2 13.63 53.4 R-22 2,035 1,635 2,535 1,560 376
38-RM-50 178.2 608,000 50.7 2 13.63 57.5 R-22 2,035 1,635 2,535 1,640 396

Split Units "Trane" R-22

Unit Size CFM Btu\hr TR Cooling P.Supply KW V \ PH \ HZ in"wg Elec Heater m3\HR KW Cooling Width Height Depth
MCD-712 300 12,000 1.0 1.1 240/1/50 0.24 2 510 3.50 280 965 577
MCD-718 500 18,000 1.5 1.6 240/1/50 0.13 2 850 5.25 280 965 577
MCD-724 750 24,000 2.0 2.2 240/1/50 0.15 3 1,275 7.00 280 965 577
MCD-730 950 30,000 2.5 3.7 240/1/50 0.13 4 1,615 8.75 280 1,118 577
MCD-736 1,000 36,000 3.0 4.2 240/1/50 0.16 4 1,700 10.50 280 1,270 577
MCD-748 1,200 42,000 3.5 3.3 380/3/50 0.16 6 2,040 12.25 408 1,091 703
MCD-048 1,600 48,000 4.0 6.5 380/3/50 0.15 6 2,720 14.00 408 1,091 703
MCD-060 2,000 60,000 5.0 7.4 380/3/50 0.18 6 3,400 17.50 408 1,241 703

Split Units "Carrier CCD" R-22

Unit Size CFM Btu\hr Heat Pump Btu\hr P.Supply KW V \ PH \ HZ in"wg TR Cooling KW Cooling Width Height Depth Comp Type

20 650 20,000 18,750 1.92 240/1/50 0.0 1.67 5.8 1,000 270 590
Rotary
28 675 25,800 25,000 2.52 240/1/50 0.0 2.15 7.5 1,000 270 590
32 720 30,000 29,200 3.06 240/1/50 0.0 2.50 8.8 1,210 270 590
Receprocating
39 1,025 39,500 33,200 4.02 240/1/50 0.0 3.29 11.5 1,420 270 590
48 1,200 48,000 42,000 3.96 380/3/50 0.0 4.00 14.0 1,420 370 590
scroll
60 1,340 54,000 52,000 5.10 380/3/50 0.0 4.50 15.8 1,630 370 590

Chilled Water Units"Trane"

Unit Size CFM Btu\hr TR Cooling P.Supply W V \ PH \ HZ in"wg Elec Heater m3\HR KW Cooling Width Height Depth
HFCE 04 373 11,650 1.0 40 220/1/50 0.1 2 634 3.4 993 305 590
HFCE 06 560 17,170 1.4 50 220/1/50 0.1 2 952 5.0 993 305 590
HFCE 08 747 22,500 1.9 187 220/1/50 0.1 3 1,270 6.6 993 305 590
HFCE 10 926 27,880 2.3 250 220/1/50 0.1 3 1,574 8.2 1,163 305 590
HFCE 12 1,015 33,260 2.8 250 220/1/50 0.1 4 1,726 9.7 1,358 305 590
HFCE 16 1,412 44,920 3.7 375 220/1/50 0.1 6 2,400 13.2 1,240 403 738
HFCE 20 1,765 56,500 5 450 220/1/50 0.1 6 3,001 16.6 1,405 403 738

Computer Room Units "DENCO" R-407


Unit Size CFM Steam Humidifier kg\HR V \ PH \ HZ
Btu\hr@21o Elec Reheat KW P.Supply KW TR Cooling KW Cooling Length Height Depth Weight
24 4,659 92,806 12 8.8 380/3/50 18.8 7.74 27.2 1275 1940 800 345
34 5,506 108,502 12 8.8 380/3/50 19.5 9.04 31.8 1275 1940 800 345
44 7,200 152,175 12 14 380/3/50 26.3 12.68 44.6 1865 1940 800 485
54 9,106 189,707 12 14 380/3/50 31.7 15.81 55.6 1865 1940 800 485
64 11,859 204,038 18 14 380/3/50 34.1 17.01 59.8 2450 1940 800 735
74 13,129 232,357 18 14 380/3/50 38.8 19.37 68.1 2450 1940 800 735
84 14,188 272,960 18 14 380/3/50 41.3 22.75 80 3040 1940 800 795
94 15,882 292,750 18 14 380/3/50 42.1 24.40 85.8 3040 1940 800 795
104 16,306 302,986 24 14 380/3/50 44.5 25.26 88.8 3675 1940 800 970
114 19,059 376,002 24 14 380/3/50 55.3 31.34 110.2 3675 1940 800 970

Capacity and correction Factors for Various Line lenghts


Length of Ref Lines (M) 7.5 12.5 14 21 26 37 45 54
Total Cooling Capacity Factor 1.00 0.99 0.97 0.97 0.94 0.94 0.9 0.9
Total Unit Consuption factor 1.00 1.01 1.01 1.02 1.03 1.04 1.06 1.08
ECG Engineering Consultants Group

Project Name: Smart Village Date: 10/2007


Project No: 1127 Computed By: A .Youssef
AHU SCHEDULE CONVERTER (SMART VILLAGE) ONLY:

I.P.UNITS
MOTOR STAND SIZES
SUPPLY FAN DATA COOLING COIL DATA HEATING DATA R. FAN DATA HP KW

No CFM F.A. TOT ST M. HP TR T edb % e-air T Ldb % L-air GPM KW GPM R AIR cfm ST.P M.HP 1 0.75
1 22,565 1,677 1000 24.84 52.33 77.2 48 55 93 104.66 39 8.32 20,888 500 11.50 1.5 1.1
2 28,195 2,512 1000 31.04 67.98 77.6 47 55 92 135.96 34 7.25 25,683 500 14.14 2 1.5
3 28,195 2,512 1000 31.04 67.98 77.6 47 55 92 135.96 34 7.25 25,683 500 14.14 3 2.2
4 33,450 2,512 1000 36.83 77.73 77.2 48 55 93 155.46 48 10.24 30,938 500 17.03 4 3
5 5,000 1,000 250 1.38 0 0.00 4,000 0.00 5.5 4
6 6,741 1,500 1000 7.42 22.97 81.9 45 55.2 89 45.94 17 3.63 5,241 500 2.89 7.5 5.5
7 22,388 4,925 1000 24.65 70.06 81.7 45 55.2 92 140.12 0 0.00 17,463 500 9.61 10 7.5
8 11,365 1,250 1000 12.51 28.5 78.5 48 55.2 93 57 0.00 10,115 500 5.57 15 11
9 0.00 0 0.00 0 0.00 20 14.7
10 0.00 0 0.00 0 0.00 25 18.5
11 0.00 0 0.00 0 0.00 30 22
12 0.00 0 0.00 0 0.00 40 30
387.55 50 37
121.53 60 44

S.I. UNITS 509.08 75 55


100 73.5
SUPPLY FAN DATA COOLING COIL DATA HEATING DATA R. FAN DATA
No m3/hr. F.A. TOT ST M.KW KW T edb % e-air T Ldb % L-air L/S KW L/S R AIR ST.P M.KW
1 38,361 2,851 1000 18.27 184.045 25.1 48 12.8 93 6.6032 39 0.52 35,510 500 8.45
2 47,932 4,270 1000 22.82 239.086 25.3 47 12.8 92 8.5779 34 0.46 43,661 500 10.40
3 47,932 4,270 1000 22.82 239.086 25.3 47 12.8 92 8.5779 34 0.46 43,661 500 10.40
4 56,865 4,270 1000 27.08 273.376 25.1 48 12.8 93 9.8082 48 0.65 52,595 500 12.52
5 8,500 1,700 250 1.01 0 -17.8 0 -17.8 0 0 0 0.00 6,800 0 0.00
6 11,460 2,550 1000 5.46 80.7855 27.7 45 12.9 89 2.8984 17 0.23 8,910 500 2.12
7 38,060 8,373 1000 18.12 246.401 27.6 45 12.9 92 8.8404 0 0.00 29,687 500 7.07
8 19,320 2,125 1000 9.20 100.235 25.8 48 12.9 93 3.5962 0 0.00 17,195 500 4.09
9 0 0 0 0.00 0 -17.8 0 -17.8 0 0 0 0.00 0 0 0.00
10 0 0 0 0.00 0 -17.8 0 -17.8 0 0 0 0.00 0 0 0.00
11 0 0 0 0.00 0 -17.8 0 -17.8 0 0 0 0.00 0 0 0.00
12 0 0 0 0.00 0 -17.8 0 -17.8 0 0 0 0.00 0 0 0.00
ECG Engineering Consultants Group

Project Name: Nozha City Center


Project No: 1127 in" mm gpm l\s l\s gpm
Pipe size 1.0 25.0 1.0 0.06309 1.0 15.85

Pipe size in (GPM , D") Pipe size in (L\sec , Dmm)


GPM D" P/100 FT L\sec D mm P/100 FT
1-4 0.75 0.4 4.5 0.06 - 0.25 20 0.4 4.5
5-8 1 2.1 4.9 0.32 - 0.50 25 2.1 4.9
9 -15 1.25 1.6 4 0.57 - 0.95 32 1.6 4
16 - 23 1.5 2.1 4.1 1.01 - 1.45 40 2.1 4.1
24 - 45 2 1.3 4 1.51 - 2.84 50 1.3 4.1
46 - 72 2.5 1.8 4 2.90 - 4.54 65 1.8 4.0
73 - 128 3 1.4 4 4.61 - 8.08 75 1.4 4.0
129 - 265 4 1.1 4 8.14 - 16.72 100 1.1 4.0
265 - 484 5 1.3 4 17 - 31 125 1.3 4.0
485 - 720 6 1.6 3.4 31 - 45 150 1.6 3.4
721 - 1240 8 0.9 2.4 45 - 78 200 0.9 2.4
1241 - 1960 10 0.8 1.8 78 - 124 250 0.8 1.8
1961 - 2790 12 0.8 1.5 124 - 176 300 0.8 1.5
2791 - 3370 14 0.9 1.3 176 - 213 350 0.9 1.3
3371 - 4400 16 0.7 1.1 213 - 278 400 0.7 1.1
4401 - 5570 18 0.6 1 278 - 351 450 0.6 1
5571 - 6930 20 0.6 0.9 351 - 437 500 0.6 0.9
6931 - 10000 24 0.3 0.7 437 - 631 600 0.3 0.7

FAN COIL UNIT DRAIN


1 3/4" 20
2-6 1" 25
7-12 1 1/4" 32
13-18 1 1/2" 40
19-24 2" 50
25-30 2 1/2" 65
31-42 3" 75
EGAT Diffuser Selection
C.F.M C.M.H. in" mm
50 85 4x4 100 x 100
100 170 6x6 150 x 150
150 255 8x8 200 x 200
200 340 10 x 10 250 x 250
250 425 10 x 10 250 x 250
300 510 12 x 12 300 x 300
350 595 12 x 12 300 x 300
400 680 14 x 14 350 x 350
450 765 14 x 14 350 x 350
500 850 14 x 14 350 x 350
550 935 16 x 16 400 x 400
600 1020 16 x 16 400 x 400
650 1105 16 x 16 400 x 400
700 1190 18 x 18 450 x 450
750 1275 18 x 18 450 x 450
800 1360 18 x 18 450 x 450
850 1445 20 x 20 500 x 500
900 1530 20 x 20 500 x 500
950 1615 20 x 20 500 x 500
1000 1700 20 x 20 500 x 500
ECG Engineering Consultants Group
PROJECT: ARAB BANK (B-135)
SUBJECT : Out let total quintity for the building DATE : SEP 2007

BASEMENT GROUND FIRST SECOND THIRD ROOF


S.R (600X250) 0
E.R (600X250) 0
E.R (150X150) 0
E.R (200X200) 0
E.R (300X200) 0
E.R (250X250) 0
E.R (650X150) 0
E.R (1200X150) 0
E.R (1500X150) 0
SW.C.D (300x300) 0
SW.C.D (350x350) 0
SW.C.D(250X250) 0
S.C.D (250X250) 0
S.C.D (300X300) 0
S.C.D (350X350) 0
S.C.D (450X450) 0
R.C.D (595x595) 0
D.V 150 mm 0
S.L.G (750X250) 0
R.L.G(750X250) 0
S.L.G (1000X100) 0
R.L.G (1000X100) 0
S.L.G (500X200) 0
R.L.G (500X200) 0
R.L.G (30 mX100mm) 0
R.L.G (10 mX100mm) 0
R.L.G (24 mX100mm) 0
R.L.G (15 mX100mm) 0
R.L.G (4 mX100mm) 0
R.L.G (10 mX250mm) 0
S.S.D (14.1m-2 slot) 0
S.S.D (29.5m-2 slot) 0
S.S.D (23.5m-2 slot) 0
S.S.D (18.1m-2 slot) 0
D.L (250X250) 0
D.L (400X400) 0
D.L (300X300) 0
D.L (200X200) 0
D.L (600X400) 0
ECG Engineering Consultants Group
PROJECT: ARAB BANK (B-135)
SUBJECT : ESTIMATE GPM for the building DATE : SEP 2007

L/S L/S L/S L/S L/S L/S L/S


HEATING 0.01 0.014 0.0225 0.03 0.037
COOLING 0.063 0.094 0.015 0.02 0.245 0.305 0.43
FCU-1 FCU-2 FCU-3 FCU-4 FCU-5 FCU-6 FCU-7
BAEMENT 8 5 2 2 2
GROUND 4 2 7 3 2 2
FIRST 1 11 4 5 3 2
SECOND 5 3 5 10 2
THIRD 1 4 6 6 9 2
ROOF
2 32 20 25 27 8 4
COOLING 0.126 3.008 0.3 0.5 6.615 2.44 1.72 14.709
HEATING 0.02 0.448 0.45 0.75 0.999 0 0 2.667

SU-1 SU-2
BAEMENT 2
GROUND 2
FIRST 2
SECOND 2
THIRD 2
ROOF
2 8
VAV-1 VAV-2 VAV-3 VAV-4
BAEMENT
GROUND
FIRST
SECOND
THIRD
ROOF
2 3
0.0924 0.116
HEATING 0.1848 0.348 0.5328

COOLING L\S HEATING L\S


AHU-01 1.665 0.353
AHU-02 4.807 1.024
AHU-03 8.84
AHU-04 3.598
AHU-05 2.898
CR-AHU 2.226
24.034 1.377

TOTAL COOLING L\S 38.743 l\s 614.1 GPM


TOTAL HEATING L\S 4.5768 l\s 72.5 GPM
Split case chilled water pump with 0.9 div
= 34.9 l\s 552.7 GPM
In line hot water pump with 0.9 div = 4.1 l\s 65.3 GPM
ECG Engineering Consultants Group
Project Name: Nozha City Center Date: 10/2007
Project No: 1127 Computed By: A .Salah
Ventilation Calculations

AREA HEIGHT TOTAL EXHAUST TOTAL SUPPLY


SERIAL FLOOR NAME ZONE NAME ONE A/C no OF A/C NOTES
M2 M CFM 0.8 CFM

1 STORE 634 6 2238 4 DUCTED IN LINE


GROUND

2 WAREHOUSE 1054 6 3720 4 DUCTED IN LINE

3 TOILET 120 6 424 15 6353 5082 TWIN DUCTED IN LINE

4 TOILET 62 3.5 128 15 1915 1532 TWIN DUCTED IN LINE


MEZZ

5 TOILET 29 3.5 60 15 896 716 TWIN DUCTED IN LINE

6 PLANT ROOM 113 3.5 233 6 1396 1117 DUCTED IN LINE

7 TOILET-W 110 5.6 362 15 5435 4348 TWIN DUCTED IN LINE


FIRST

8 TOILET-E 39 5.6 128 15 1927 1542 TWIN DUCTED IN LINE

9 TOILET-PRAY AREA 132 5.6 435 20 8696 6957 TWIN DUCTED IN LINE

10 SHOE RACK 4 5.6 13 15 198 - ROOF TOP FAN


ROOF SECOND

11 TOILET 35 4 82 15 1235 988 TWIN DUCTED IN LINE

12 LIFT ROOM 35 4 82 15 1235 ROOF TOP FAN

29286 23429 5857

KITCHEN VENTILATION FOR RESTAURANTS

TOTALAREA HEIGHT KITHEN AREA TOTAL EXHAUST TOTAL SUPPLY MAKE UP


SERIAL FLOOR NAME ZONE NAME ONE A/C BALANCE
M2 M 0.3 AREA 75 X CFM OR 35 L/S 0.8 CFM

1 RO-01 372 5.6 1225 112 8370 6696 1674


GROUND
2 RO-02 458 5.6 1509 137 10305 8244 2061

3 R1-01 137 5.6 451 41 3083 2466 617

4 R1-02 147 5.6 484 44 3308 2646 662


FIRST

5 R1-03 349 5.6 1150 105 7853 6282 1571

6 R1-04 126 5.6 415 38 2835 2268 567

7 R1 115 5.6 379 35 2588 2070 518

8 R1 106 5.6 349 32 2385 1908 477

4410

KITCHEN VENTILATION FOR FOOD COURT

TOTALAREA HEIGHT KITHEN AREA EXTRA HEAVY DUTY NORMAL DUTY TOTAL EXHAUST TOTAL SUPPLY MAKE UP EXH.FAN SUPPLY FAN
SERIAL FLOOR NAME ZONE NAME ONE A/C BALANCE
M2 M 0.8 AREA 0.3 KITCHEN AREA 0.7 KITCHEN AREA (112 X EXTRA) + (75 X NORMAL) 0.8 CFM 1.10%

1 FC-01 65.5 5.6 216 52 16 37 4512 3609 13914 902

2 FC-02 65.5 5.6 216 52 16 37 4512 3609 EXH-FAN 15300 CFM SF-11000 11131 902

3 FC-03 71 5.6 234 57 17 40 4890 3912 15305 978

4 FC-04 34 5.6 112 27 8 19 2342 1874 7026 468

5 FC-05 34 5.6 112 27 8 19 2342 1874 EXH-FAN 7800 CFM SF-5700 5621 468

6 FC-06 34 5.6 112 27 8 19 2342 1874 7728 468

7 FC-07 34.5 5.6 114 28 8 19 2376 1901 9609 475


EXH-FAN 10500 CFM SF-7700
8 FC-08 105 5.6 346 84 25 59 7232 5786 7687 1446
FIRST

9 FC-09 67 5.6 221 54 16 38 4615 3692 11744 923

10 FC-10 69 5.6 227 55 17 39 4753 3802 EXH-FAN 13000 CFM SF-9400 9395 951

11 FC-11 34.5 5.6 114 28 8 19 2376 1901 12918 475

12 FC-12 34.5 5.6 114 28 8 19 2376 1901 7129 475

13 FC-13 34.5 5.6 114 28 8 19 2376 1901 EXH-FAN 7800 CFM SF-5700 5703 475

14 FC-14 34.5 5.6 114 28 8 19 2376 1901 7842 475

15 FC-15 68.5 5.6 226 55 16 38 4718 3775 13742 944

16 FC-16 65.5 5.6 216 52 16 37 4512 3609 EXH-FAN 15300 CFM SF-11000 10993 902

17 FC-17 65.5 5.6 216 52 16 37 4512 3609 15116 902

63163 50530 12633 12632.592

COFFEE SHOPS VENTILATION

AREA HEIGHT SMOKING AREA TOTAL EXHAUST


SERIAL FLOOR NAME ZONE NAME ONE A/C NOTES
M2 M 0.5 X AREA 20 CFM / M2
FIRST

1 CS-002 56.25 5.6 185 28 563 ROOF TOP FAN

2 CS-003 56.25 5.6 185 28 563 ROOF TOP FAN

1125

TOTAL EXTRACT FROM GROUND FLOOR 10088

TOTAL EXTRACT FROM FIRST FLOOR 33299


Single phase 3-phase Standard HP Standard KW
KW Circuit Breaker Std KW Circuit Breaker Std 1 0.75
1 - 2.8 16A 1 - 8.4 16A 1.5 1.1
2.9 - 4.3 25A 8.5 - 13 25A 2 1.5
4.4 - 5.6 32A 13 - 16.8 32A 3 2.2
5.7 - 7 40A 17 - 21 40A 4 3
7 - 11 63A 21 - 33 63A 5.5 4
11 - 14 80A 33 - 42 80A 7.5 5.5
14 - 17.6 100A 42 - 52 100A 10 7.5
52 - 66 125A 15 11
KW A 66 - 79 160.0 20 14.7
3- Phase 8.5 16.1 79 - 105 200A 25 18.5
1- Phase 1 5.7 105 - 132 250A 30 22
132 - 168 320A 40 30
168 - 210 400A 50 37
A KW Air Circuit breaker 60 44
3- Phase 9.5 5.0 210 - 263 500A 75 55
1- Phase 10 1.8 264 - 315 630A 100 73.5
315 - 420 800A
420 - 520 1000A
520 - 650 1250A