- Recommendation provide 3.7 lit/sec/m2 and exhaust is not required if two or more sides
comprise walls that are at least 50% to the outside.
- For smoke management system the smoke zone shall be 2500 m2.
- The selected area shall be ventilating according the ASHRAE standards 62.1.2004 by 3.7
lit/sec/m2.
For 12000 m2
Shall be divided into 5 exhaust fan two speed fire protected each one as 20 000 cfm as
ventilation, 14.1 m3/sec.
As per smoke calculations the second shall be 30 000 cfm for smoke removal at 300 C for one
ECG Engineering Consultants Group
Design Parameters:
Calculations
= 42300 cfm
Note:
As per ANSI/ASHRAE standards 62.1.2004
Recommendation provide 3.7 lit/sec/m2
Parking Area= 12000 m2
93250 cfm
Shall be divided into 5 exhaust fans two speed fire protected each one is 20 000 cfm for ventilation.
As per NFPA part 92B
Car parking area divided into 5 fire zones 2500 m2 each , Total exhaust 50,000 cfm.
Direct drive two speed smoke exhaust fans of 14.1 m 3/s (30,000 cfm) rating shall be provided in each
parking zone , Fire rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.
Make up fresh air shall be supplied from Ramps and Slab opening.
ECG Engineering Consultants Group
Q = Heat Production
M = Total fuel mass consumed
Z = Height above the fuel
Q= 4000 kw
ρ= 1.2 kg /m3 @20 OC
z= 2.5
M = 0.071 Q1/3 X Z 5/3 + 0.0018 Q NFPA part 92B Chapter 7
= 0.071*((4000)^(1/3))*((2.5)^(5/3))+((0.0018*4000))
M= 12.4 kg/sec
V= 10.3 m3/sec
V= 21900 cfm
Note:
Nos. Smoke exhaust fans of cfm shall be inter locked with fire system
The Exhaust fans shall be Rated for 300 Deg.c for 1 hr.
ECG Engineering Consultants Group
Design Parameters
Mf = 32.15 kg/sec
Tempreture Rise Ө = Qf /Mf x cp )
Ө= 68.48 Deg.0c
Outside Air Temp. Tc = 341.48 K
Air Volume Flow rate V = ( Mf x Tc / 1.2 x Ta )
29.23 m3/s
V = 61950 cfm
Note:
4 Nos. Smoke exhaust fans of shall be provided on the Roof
The Exhaust fans shall be Rated for 300 Deg.c for 1 hr.
ECG Engineering Consultants Group
Design Parameters
Q= Total heat output of a fire (Kw)
D= Diameter of fire source.
zo = Virtual origin.
Qc = Convective portion of total heat release = Q / 1.5
Z1 = mean Flame height Z = Smoke clear height.
D= Flame diameter = Aeq ^ 0.5
M= Mass flow rate in the plume.
dT = Qc / MCp
Cp = Specific heat capacity of air ( 1KJ/Kg.K )
d= Depth of smoke layer.
= 2 when extraction near wall & 2.8 when away from wall.
N= min number of extraction points from smoke layer.
0.5
M QC gd 5T0 T
V M crit 2
0 0 T0 C P ( T T0 )
Z O 0.083 Q 2 / 5 1.02 D
Small diameter source Large diamter source
2/5 2/5
QC QC
14 14
D D
2/3
0.035.QC
z1 0.2.QC
2/5
z1
( D 0.074.QC ) 2 / 3
2/5
0.0054.QC .z
M
z0
2/5
0.166.QC
Plume Temperature Number of extraction points
QC M
Tm To N
Mcrit
M .Cp
q= 500 KW/m²
Aeq = 4 m²
Q= 3000 KW
Qc = 2000 KW
D= 2.0 m
2/5
Qc = 21 14 D = 28 Large
2/5
Qc /D = 10.46 Large diameter source
z= 4.5 m zo = 0.0014
H= 6.0 m To = 40 °C
d= 1.5 m To = 313 K
Small diameter source Large diamter source
M= 14.0 Kg/S.
dt = 142.9 °C
Tplume = 455.9 K
V= 17.0 m³/S
Mcr = 8.0 Kg/S
V= 36000 cfm
Note:
**** Nos. Smoke exhaust fans of *** cfm shall be provided on the Roof
The Exhaust fans shall be Rated for 300 Deg.oc for 1 hr.
ECG Engineering Consultants Group
Calculations
1.5
Min. Smoke Flow Rate (Mf) = 0.188 x P x Y
= 5.9451 kg/s
Car parking area divided into 5 fire zones 2500 m2 each , Total exhaust 50,000 cfm.
Direct drive two speed smoke exhaust fans of 14.1 m3/s (30,000 cfm) rating shall be provided in each parking zone , Fire
rated for 300oC for 1 HR. Motor and Bearing shall be out of air stream.
Make up fresh air shall be supplied from Ramps and Slab opening.
ECGEngineering Consultants Group
Input Data:
No. of levels (including ground floor) : 9
Average level height : 3 m
2
Floor Area : 2200 m
2
Exterior building wall area per floor : 105 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose, 4=Very Loose)
2
Stairwell wall area per floor : 14 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
2
Elevator shaft walls : 14 m
Wall Tightness : 2 (1=Tight, 2=Average, 3=Loose)
2
The area gap around each stairwell door : 0.024 m
Outside design temperature : 46 deg C
Stairwell temperature : 28 deg C
Assumptions:
The pressure difference between stairwell
and building at stairwell bottom : 20 Pa
In this system, an exterior stairwell door opens automatically upon system activation. In addition,
the lower two floors will be considered opened, while the others doors will be considered closed
on. In addition,
sidered closed
357 cfm)
2408 cfm)
10484 cfm)
5
13250 cfm)
Design Parameters
Total no of Floors = 20
Egres Velocity across open door (Qs) = 0.75 m/s
Area of open door = 2.1 x 1
= 2.1 m2
Number of open door (n) = 2
Egres Velocity (Ve) = 0.6 x Qs / A x n
Qs = Ve x A x n / 0.6
5.25 m3/s
Note:-
Two no,supply roof top fan of 5.39 m3/sec (12000cfm) will be provided on the Roof of stair case.
ECG Engineering Consultants Group
Design Parameters
Total no of Floors = 20
Egres Velocity (Ve) =
Area of door = 2.1 x 1
= 2.1 m2
Leakage through closed doors on all floors 0.06 sq.m
Leakage area of lift landing door ) =
Air leakage thru lift landing door (Q) = k x Ae x p^0.5
0.35 m3/s
Total no of closed doors= 18 nos
total Leakage thru closed doors= 6.33 m3/s
13450 cfm
ECG Engineering Consultants Group
Unit Size CFM Btu\hr TR Cooling Elec Heater P.Supply KW 3 KW Cooling Width Cond Height Cond Height+Evap Depth Cond Nominal Air Flow cfm
m \HR
55 2,000 54,000 4.5 6 7.25 3,400 15.98 890 1,069 1,605 753 3,000
90 3,000 84,000 7 15 11.2 5,100 25.12 1,338 1,165 1,828 766 5,900
110 3,500 108,000 9 15 14.5 5,950 31.97 1,338 1,165 1,828 766 5,900
145 6,000 144,000 12 18 19.4 10,200 42.20 1,593 1,405 2,201 824 7,650
180 6,000 168,000 14 18 21 10,200 50.12 1,593 1,405 2,197 824 7,650
240 7,000 229,200 19.1 22.5 34.9 11,900 67.41 2,088 1,405 2,059 1,060 10,500
Unit Size CFM MBtu\hr TR Cooling Elec Heater P.Supply KW 3 KW Cooling Width Height Length Weight Comp type
m \HR
190 4000-6500 192 16.0 18 20.1 6800-11050 56.29 1,976 1,333 2,271 705 Hermatic Receprocating
240 5400-8400 242 20.1 18 22.1 9520-14280 70.79 2,263 1,303 2,677 859 Hermatic Scroll
260 6000-9000 255 21.3 18 24.1 10200-15300 74.72 2,263 1,303 2,677 920 Hermatic Scroll
320 7000-11500 324 27.0 18 37.1 11900-19550 94.93 2,263 1,303 2,677 955 Hermatic Scroll
360 9500-14000 338 28.2 36 35.6 16150-23800 99.09 2,235 1,776 5,207 1,600
420 10500-15000 378 31.5 36 36.6 17850-25500 110.78 2,235 1,776 5,207 1,650
480 12500-17000 466 38.8 36 66.1 21250-28900 136.54 2,235 1,776 5,207 1,691
600 14000-19000 593 49.4 36 74.1 23800-32300 173.60 2,235 1,776 5,207 1,886
38-RM-15 60.4 206,000 17.2 2 8.96 19.4 R-22 2,035 1,635 1,260 600 291
38-RM-20 75.0 256,000 21.3 2 11.59 24.7 R-22 2,035 1,635 1,260 740 359
38-RM-25 89.1 304,000 25.3 2 13.63 28.7 R-22 2,035 1,635 1,260 820 398
38-RM-30 120.8 421,000 34.3 2 8.96 38.7 R-22 2,035 1,635 2,520 1,300 316
38-RM-35 135.4 462,000 38.5 2 11.59 44.0 R-22 2,035 1,635 2,535 1,400 338
38-RM-40 150.1 412,000 42.7 2 11.59 49.3 R-22 2,035 1,635 2,535 1,480 357
38-RM-45 164.1 560,000 46.7 2 13.63 53.4 R-22 2,035 1,635 2,535 1,560 376
38-RM-50 178.2 608,000 50.7 2 13.63 57.5 R-22 2,035 1,635 2,535 1,640 396
Unit Size CFM Btu\hr TR Cooling P.Supply KW V \ PH \ HZ in"wg Elec Heater m3\HR KW Cooling Width Height Depth
MCD-712 300 12,000 1.0 1.1 240/1/50 0.24 2 510 3.50 280 965 577
MCD-718 500 18,000 1.5 1.6 240/1/50 0.13 2 850 5.25 280 965 577
MCD-724 750 24,000 2.0 2.2 240/1/50 0.15 3 1,275 7.00 280 965 577
MCD-730 950 30,000 2.5 3.7 240/1/50 0.13 4 1,615 8.75 280 1,118 577
MCD-736 1,000 36,000 3.0 4.2 240/1/50 0.16 4 1,700 10.50 280 1,270 577
MCD-748 1,200 42,000 3.5 3.3 380/3/50 0.16 6 2,040 12.25 408 1,091 703
MCD-048 1,600 48,000 4.0 6.5 380/3/50 0.15 6 2,720 14.00 408 1,091 703
MCD-060 2,000 60,000 5.0 7.4 380/3/50 0.18 6 3,400 17.50 408 1,241 703
Unit Size CFM Btu\hr Heat Pump Btu\hr P.Supply KW V \ PH \ HZ in"wg TR Cooling KW Cooling Width Height Depth Comp Type
20 650 20,000 18,750 1.92 240/1/50 0.0 1.67 5.8 1,000 270 590
Rotary
28 675 25,800 25,000 2.52 240/1/50 0.0 2.15 7.5 1,000 270 590
32 720 30,000 29,200 3.06 240/1/50 0.0 2.50 8.8 1,210 270 590
Receprocating
39 1,025 39,500 33,200 4.02 240/1/50 0.0 3.29 11.5 1,420 270 590
48 1,200 48,000 42,000 3.96 380/3/50 0.0 4.00 14.0 1,420 370 590
scroll
60 1,340 54,000 52,000 5.10 380/3/50 0.0 4.50 15.8 1,630 370 590
Unit Size CFM Btu\hr TR Cooling P.Supply W V \ PH \ HZ in"wg Elec Heater m3\HR KW Cooling Width Height Depth
HFCE 04 373 11,650 1.0 40 220/1/50 0.1 2 634 3.4 993 305 590
HFCE 06 560 17,170 1.4 50 220/1/50 0.1 2 952 5.0 993 305 590
HFCE 08 747 22,500 1.9 187 220/1/50 0.1 3 1,270 6.6 993 305 590
HFCE 10 926 27,880 2.3 250 220/1/50 0.1 3 1,574 8.2 1,163 305 590
HFCE 12 1,015 33,260 2.8 250 220/1/50 0.1 4 1,726 9.7 1,358 305 590
HFCE 16 1,412 44,920 3.7 375 220/1/50 0.1 6 2,400 13.2 1,240 403 738
HFCE 20 1,765 56,500 5 450 220/1/50 0.1 6 3,001 16.6 1,405 403 738
I.P.UNITS
MOTOR STAND SIZES
SUPPLY FAN DATA COOLING COIL DATA HEATING DATA R. FAN DATA HP KW
No CFM F.A. TOT ST M. HP TR T edb % e-air T Ldb % L-air GPM KW GPM R AIR cfm ST.P M.HP 1 0.75
1 22,565 1,677 1000 24.84 52.33 77.2 48 55 93 104.66 39 8.32 20,888 500 11.50 1.5 1.1
2 28,195 2,512 1000 31.04 67.98 77.6 47 55 92 135.96 34 7.25 25,683 500 14.14 2 1.5
3 28,195 2,512 1000 31.04 67.98 77.6 47 55 92 135.96 34 7.25 25,683 500 14.14 3 2.2
4 33,450 2,512 1000 36.83 77.73 77.2 48 55 93 155.46 48 10.24 30,938 500 17.03 4 3
5 5,000 1,000 250 1.38 0 0.00 4,000 0.00 5.5 4
6 6,741 1,500 1000 7.42 22.97 81.9 45 55.2 89 45.94 17 3.63 5,241 500 2.89 7.5 5.5
7 22,388 4,925 1000 24.65 70.06 81.7 45 55.2 92 140.12 0 0.00 17,463 500 9.61 10 7.5
8 11,365 1,250 1000 12.51 28.5 78.5 48 55.2 93 57 0.00 10,115 500 5.57 15 11
9 0.00 0 0.00 0 0.00 20 14.7
10 0.00 0 0.00 0 0.00 25 18.5
11 0.00 0 0.00 0 0.00 30 22
12 0.00 0 0.00 0 0.00 40 30
387.55 50 37
121.53 60 44
SU-1 SU-2
BAEMENT 2
GROUND 2
FIRST 2
SECOND 2
THIRD 2
ROOF
2 8
VAV-1 VAV-2 VAV-3 VAV-4
BAEMENT
GROUND
FIRST
SECOND
THIRD
ROOF
2 3
0.0924 0.116
HEATING 0.1848 0.348 0.5328
9 TOILET-PRAY AREA 132 5.6 435 20 8696 6957 TWIN DUCTED IN LINE
4410
TOTALAREA HEIGHT KITHEN AREA EXTRA HEAVY DUTY NORMAL DUTY TOTAL EXHAUST TOTAL SUPPLY MAKE UP EXH.FAN SUPPLY FAN
SERIAL FLOOR NAME ZONE NAME ONE A/C BALANCE
M2 M 0.8 AREA 0.3 KITCHEN AREA 0.7 KITCHEN AREA (112 X EXTRA) + (75 X NORMAL) 0.8 CFM 1.10%
2 FC-02 65.5 5.6 216 52 16 37 4512 3609 EXH-FAN 15300 CFM SF-11000 11131 902
5 FC-05 34 5.6 112 27 8 19 2342 1874 EXH-FAN 7800 CFM SF-5700 5621 468
10 FC-10 69 5.6 227 55 17 39 4753 3802 EXH-FAN 13000 CFM SF-9400 9395 951
13 FC-13 34.5 5.6 114 28 8 19 2376 1901 EXH-FAN 7800 CFM SF-5700 5703 475
16 FC-16 65.5 5.6 216 52 16 37 4512 3609 EXH-FAN 15300 CFM SF-11000 10993 902
1125