I 1.30A I 2.17A: Circuit No. 1: Lighting Outlet Circuit No. 4: Lighting Outlet
I 1.30A I 2.17A: Circuit No. 1: Lighting Outlet Circuit No. 4: Lighting Outlet
MCCB
CIRCUIT NO. 1: LIGHTING OUTLET
CIRCUIT NO. 4: LIGHTING OUTLET
(3)(100)
I= = 1.30A (5)(100)
230
I= = 2.17A
2 230
USE: 2-3-5mm THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB USE: 2-3-5mm2 THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB
CIRCUIT NO. 2: LIGHTING OUTLET
CIRCUIT NO. 5: LIGHTING OUTLET
(11)(100)
I= = 4.78A (6)(100)
230
I= = 2.60A
2 230
USE: 2-3-5mm THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB USE: 2-3-5mm2 THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB
CIRCUIT NO. 3: LIGHTING OUTLET
(4)(100)
I= = 1.73A
230
CIRCUIT NO. 6: LIGHTING OUTLET USE: 2-3-5mm2 THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB
(3)(100)
I= = 1.30A (6)(100)
230
I= = 2.60A
2 230
USE: 2-3-5mm THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB USE: 2-3-5mm2 THHN CU wire in a 15 mmØ PVC, 15AT,1P
MCCB
CIRCUIT NO. 8: CONVENIENCE OUTLET
(2)(100)
I= = 0.86A
230
CIRCUIT NO. 11: CONVENIENCE OUTLET CIRCUIT NO. 14: ACU (1hp)
From Table: I = 8A
USE: 2-3-5mm2 THHN CU wire in a 15 mmØ PVC, 15AT,1P I SERVICE = 96.7A + .25(8)
MCCB
I SERVICE = 98.7A
CIRCUIT NO. 19: ACU (1hp)
USE: 2-80mm2 THHN CU wire, 1-15mm2 in a 32 mm Ø
From Table: I = 8A RMC, 175AT,2P MCCB
From Table: I = 8A
CIRCUIT LOAD DESCRIPTION NO. OF VOLTS AMPERE POWER AT SIZE OF WIRE AND CONDUIT
NO. OUTLETS
1 LIGHTING OUTLET 3 230 1.30 300 15 2-3-5mm2 THHN CU wire in a
15 mmØ PVC, 15AT,1P MCCB
22 SPARE 230 20
23 SPARE 230 20