ETAP

Project: Page: 1
12.6.0H
Location: Date: 17-10-2017
Contract: SN:
Engineer: Revision: Base
Study Case: LF
Filename: UNIT_2 Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR

ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 16.500 100.000 0.0 333.888 162.006 0 0 Bus4 333.888 162.006 12985.7 90.0

Bus 2 18.000 87.712 -22.0 0 0 0 0 Bus7 0.000 0.000 0.0 0.0

Bus 3 13.800 87.568 -25.1 0 0 0 0 Bus9 0.000 0.000 0.0 0.0

Bus4 230.000 91.764 -13.0 0 0 0 0 Bus6 149.308 29.305 416.2 98.1

Bus5 182.668 46.642 515.7 96.9

Bus1 -331.976 -75.947 931.6 97.5

Bus5 230.000 89.876 -16.3 0 0 100.973 40.382 Bus7 80.368 -0.478 224.5 100.0

Bus4 -181.342 -39.904 518.6 97.7

Bus6 230.000 85.488 -25.0 0 0 146.158 36.567 Bus9 -2.825 -24.098 71.2 11.6

Bus4 -143.332 -12.469 422.5 99.6

Bus7 230.000 87.712 -22.0 0 0 0 0 Bus5 -78.739 -6.327 226.1 99.7

Bus8 78.739 6.327 226.1 99.7

Bus 2 0.000 0.000 0.0 0.0

Bus8 230.000 86.822 -24.7 0 0 75.383 26.373 Bus7 -78.305 -9.703 228.1 99.2

Bus9 2.922 -16.671 48.9 -17.3

Bus9 230.000 87.568 -25.1 0 0 0 0 Bus6 2.915 7.911 24.2 34.6

Bus8 -2.915 -7.911 24.2 34.6

Bus 3 0.000 0.000 0.0 0.0


* Indicates a voltage regulated bus (voltage controlled or swing type machine connected to it)