Data Sheet Tq-04 RLL Eppetroecuador Epn Rev C
Data Sheet Tq-04 RLL Eppetroecuador Epn Rev C
Floatation Considerations? N Flot. Suppl. Spec.* N/A Applied Suppl. Load Spec. N/A
8. Seismic Design? Y Appendix E Y Alt. Seismic Criteria NEC SE DS Seismic Use Group III
MBE Site Class C Vertical Seismic Design? Y Vertical Ground Motion Accelerator Av: 0,583
Basis of Lat. Accel. (Select one):
N Mapped Seismic Parameters Ss 1,25 S1 0,63 So 0,5 I 1,5
Site-Specific Procedures MCE Design Required?
Y Other (Non-ASCE) Methods NORMA ECUATORIANA CONSTRUCCION EDICION 14
Freeboard Required for SUG 1 Design Roof Tie Rods at Outer Ring?* N
9. Wind Velocity for non-U.S. sites, 50-yr wind speed (3-sec Gust)* 120 kph
Top Windgirder Style* Top Angle Dimensions* L100 x 10 mm Use Top WG as a Walkway? N
Intermediate Wind Girders?* N Intermediate Windgirder Style* Dimensions*
Check Buckling in Corroded Cond.? N
10. Shell Design: 1-Ft Mthd?* Y Variable-Des-Pt Mthd?* Elastic Anal. Mthd?*
Plate Stacking Criteria* Centerline Stacked? N Flush-Stacked? Y Inside
Plate Widths (in.) (Shell course heights) and Thicknesses (in.)* Numbers Below Indicate Course Number
1. 2440 mm / 15,86 mm 2. 2440 mm / 14,27 mm 3. 2440 mm / 9,52 mm 4. 2440 mm / 8 mm
5. 2420 mm / 6,35 mm 6. x 7. x 8. x
9. x 10. x 11. x 12. x
13. x 14. x 15. x 16. x
Joint Efficiency* 0,85 % Shell-to-Bottom Weld Type* Fillets Shell-to-Bottom Weld Insp Mthd*
Approvals: Revisions (no./date) Title:
1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 1 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
2 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.
11. Open-Top and Fixed Roofs: (See Sheet 6 for Floating Roofs) Open Top?* N
Fixed Roof Type* Multi Bay Int Struct. Roof Support Columns* Structural Shape
Cone Slope* 1
: 16 Dome or Umbrella IS Radius* N/A in Weld Joints* Lap
Seal Weld Underside of Lap Joints? Y ; Seal Weld Underside of Windgirder Joints? Y
Gas Tight? Y Joint Efficiency* 85 % Roof Thickness* 6,35 mm
Minimum Roof Live Load 0 psf Balanced Snow Load 0 psf Unbalanced Snow Load 0 psf
App. Suppl. Load Spec.* 20 psf Column Lateral Load 1,4 psf
Normal Venting Devices*: Qty 2 Type
Emergency Venting Devices*: Qty 2 Type
For Non-Frangible Roofs: Seal Weld Roof Plates to Top Angle IS N ; Weld Rafters to Roof Plates N
Roof-to-Shell Detail* Top Angle Lapped Radial Projection of Horizontal Component* Outward
12. Bottom: Thickness* 9,53 mm Style* Cone Up to Center Slope* 1 : 120 Weld Joint* SW Lap
Provide Drip Ring? N Alternate Spec. N/A
SK/Ann. Ring? N Annular Ring: Minimum Radial Width* mm. Thickness* mm.
13. Foundation: Furnished By* Type* Ringwall
Soil Allow. Bearing Press.* N/A psi Per Spec. N/A Anchor: Size 2 inch Dia Qty 34
Design Loads: Base Shear: Wind* N/A Seis.* N/A Moment: Wind* N/A Seis.* N/A
Ring Forces: Shell+Roof Weight New* N/A Corroded* N/A Roof LL* 20 psf Internal Pressure* atm
Partial Vacuum* N/A Wind* Siesmic*
Btm Forces: Flr Wt. New* N/A Corr.* N/A Prod. Wt.* Water Wt.* Int. Press.* atm
Partial Vacuum* N/A Other Found. Loads* N/A Min. Proj. of Found. Above Grade: TBD
14. Responsibility for Heating Water, if Required? Purchaser
Hydro-test Fill Height* 11,24 m Settlement Measure Req'd? Y Extended Duration of Hydro-test: API 650
Predicted Settlement Profile is Attached
Responsibility for Setting Water Quality Purchaser Suppl. Test Water Quality Spec. N/A
Test Water Source & Disposal Tie-in Locations Purchaser Hydro-test Appendix J Tank N
Post-Press.-Test Activities Req'd of Mfr: Broom Clean Potable Water Rinse Y Dry Interior Other
List Other
15. Inspection by: Shop Purchaser Field Purchaser
Supplemental NDE Responsibility Manufacturer Supplemental NDE Spec. Purchaser
Positve Material Identification? N PMI Requirements: N/A
Max. Plate Thickness for Shearing TBD
Must Welds not exceeding .25" be Multi-Pass? N Must Welds greater than .25" be Multi-Pass? Y
Leak Test Method: Roof* Hermeticity Test Shell* Hydrostatic Testing Shell Noz./MW Rein. PL* Pneumatic Testing
Bottom* Vaccum Box Floating Roof Components* N/A
Modify or Waive API Dimensional Tolerances (see 7.5) N Specify: N/A
Specify additional Tolerances, if any, and Circumferential and Vertical Measurement Locations:
Allowable Plumbness: N/A Measure and Record at a Min. of N/A Locations or Every N/A ft around the
Tank , at the Following Heights: Specify Other: N/A
Allowable Roundness:** Measure Radius and Record at a Min. of Locations or Every ft
around the Tank, at the Following Shell Heights: Specify Other:
** See Data Sheet Instructions for the Maximaum Allowable Additional Tolerance
Approvals: Revisions (no./date) Title:
1 2 3 4 5 6 By Ckd Date
Draw. No.: Sheet 2 of 10
Data Sheet Status:
API Std 650 Storage Tank
Data Sheet Page
3 of 10
*If box is blank, Mfr. shall determine and submit as per Appendix L.
16. Coatings:
Internal Linings by: ATC HEMPADUR 300 MICRONS`S Per Spec.* NORMA DE PETROECUADOR 02
External Coating by: ATC HEMPADUR 300 MICRONS`S Per Spec.* NORMA DE PETROECUADOR 02
Under-Bottom Coating by: ATC Per Spec.* NORMA DE PETROECUADOR 02
17. Cathodic Protection System? Y Per Spec.* API RP 651
18. Leak Detection System? Y Per Spec.* API RP 650
19. Release Detection Barrier? N Per Spec.* N/A
20. Tank Measurement System: Required? Y Remote Capability Required? N
By:* MANUFACTURER Per Spec.* TDD
21. Weight of Tank:
Full of Water* 9398487 kgs Empty* 230063 kgs Shipping* lbs Brace/Lift Spec.
22. References*:
23. Remarks*:
Annular Ring -
Remarks:
Hor Azimuth
Mark Service Diameter (in) Depth (in) Thk (in) Rad(in) "x" Dim "y" Dim (deg) Notes
Shell
Nom. Wall Flange Flg Cl. Offset Elev. Azimuth Proj. Trim
Mark Service Dia. Thk Type or Thk Hillside (mm) (mm.) (deg) (mm) Flush Notes
N1 LEVEL INDICATOR 2 XS RFWN 150 1600 23 153
N2 LEVEL INDICATOR 2 XS RFWN 150 2800 23 153
N3 TERMOWELL 1 CPLG 680 25
N4 CLEANOUT 35" X 47" API 650 API 332 34 206
N5 FILLING 6 XS RFWN 150 306 286 200
N6 BOTTOM DRAIN 4 XS RFWN 150 259 179 175
N7 BOTTOM DRAIN 4 XS RFWN 150 259 359 175
N8 TRANS. PRESSURE 2 XS RFWN 150 293 164 150
N9 SUCCTION 12 XS RFWN 150 449 290 225
N10 FREE PUMP 6 XS RFWN 150 306 295 200
M1 MANHOLE 30 8MM API 900 75 150
CS1 FOAM CHAMBER 8 XS RFWN 150 10842 108 200
CS2 FOAM CHAMBER 8 XS RFWN 150 10842 288 200
M2 MANHOLE 30 " 8MM API 900 255 150
Notes:
Notes:
Remarks:
Remarks:
Notes: