Test Report

TSG Technical Team visited 220kV G/S Ghazi Road Lahore for the testing of Bushings and
Bushing Current Transformers on dated results are as under.

Bushing Current Transformers TEST

Red Phase Yellow Phase Blue Phase


Sr.No
1a-1n
Vp(V) Vs(mV) Ratio Vp Vs Ration Vp(V) Vs (mV) Ratio
1. 10 8.352 1197.6 10 8.346 1198.5 10 8.345 1198.5
2. 20 16.76 1197.7 20 16.69 1198.4 20 16.68 1199.1
3. 40 33.41 1197.6 40 33.39 1198,2 40 33.37 1198.7
2a-2n
1. 10 8.348 1198.2 10 8.342 1199.1 10 8.34 1199.3
2. 20 16.70 1198.2 20 16.69 1199.0 20 16.63 1199.2
3. 40 33.40 1198.0 40 33.38 1198.6 40 33.37 1198.8
PRIMARY AND SECONDARY WINDING RESISTANCE TEST
Applied
Winding
Sr. No test Red Phase Yellow Phase Blue Phase
Resistance
current
Primary
1. 10 mA 8.189 kilo ohms 8.179 kilo ohms 8.072 kilo ohms
A-N
Secondary
2. 100 mA 49.02 milli ohms 50.48 milli ohms 47.92 milli ohms
1a-1n
Secondary
3. 100 mA 52.22 milli ohms 51.56 milli ohms 57.2 milli ohms
2a-2n

C&DF TEST OF PT
Red Phase Yellow Phase Blue Phase
Sr. Applied
Capacitance Capacitance DF (%) Capacitance DF (%)
No Voltage DF (%)
(nF) (nF) (nF)
1. 1 kV 1.038 0.020 1.034 0.028 1.034 0.028
2. 2 kV 1.037 0.028 1.034 0.029 1.034 0.029
3. 5 kV 1.037 0.036 1.034 0.034 1.034 0.040
On the basis of above results, Tested PT of bus bar is fit for service.

GSO, NTDC TSG, NTDC EHV-1, NTDC


(220kV G/S Ghazi Road,
Lahore)