Maintenance Schedule 3AXD10000613694

Issued by Date Language Revision Page

ABB Oy, Drives Service 22.3.2018 en C 1 (2)


Creator name Approver name Distribution
Oliver-shilei Lu Anttijussi Salminen Public

ACS800 Wind Turbine Drives


Legend:
Replacement of component (At rated load and ambient conditions) R
Inspection (visual inspection, correction and replacement if needed) I
Performance of on-site work (commissioning, tests, measurements, etc.) P

Air cooled wind turbine drive: A Years from start-up


Liquid-cooled wind turbine drive: L
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

Start-up A L P

Cooling
Ø Air Cooled Unit:
R R R
Ø Cooling fans A I I I I I 1) I I I I I 1) I I I I I 1) I I I
Ø ABB Liquid-Cooled Unit:
R R R R R R R
Ø Cooling fans L I I 1) I I 1) I I 1) I I 1) I I 1) I I 1) I I 1)

Ø Add coolant inhibitor L I P I P I P I P I P I P I P I P I P I P I


Ø Water-glycol coolant L I I R I I R I I R I
Ø Expansion tank air pressure L I I I I I I I I I I
Ø Cooling water pump L I I I I I R I I I I I R I I I I I R I I I
Ø Cooling water pipe
L I I I I I I I I I I I I I I I I I I I I I
connections
Heating
Ø Heating fan A I I I I I I I I R I I I I I I I I R I I I
Aging
Ø Electrolytic capacitors
L R R
(DC circuit)
Ø Film capacitors(DC circuit) A I/R I/R
Ø Memory backup battery
A L I I I I I R I I I I I R I I I I I R I I I
replacement in APBU unit
Ø ALCL filter capacitor 2) A I/R I I/R I I/R I

Connections & Surroundings


Ø AINT, AITF, APOW, AFCB,
A L R R
AFPS and cables
Ø Tightness of terminals A L I I I
Ø Cabinet air filters A R R R R R R R R R R R R R R R R R R R R R
Ø Module air filters A R R R R R R R R R R R R R R R R R R R R R
Ø Condition of contactors A L I I I I I I I I I I I I I I I I I I I I I
Ø Main contactors A L
(maintenance according to I I I I I I I I I P I I I I I I I I I P I
manufacturer instructions)
Ø Air circuit breaker A L
(maintenance according to I I I I I I I I I I I I I I I I I I I I I
manufacturer instructions)
Ø Fiber optic cables A L
I I I I I I I
(connections)
Ø Dustiness, corrosion and A L
I I I I I I I I I I I I I I I I I I I I I
temperature

Improvements

Ø Based on product notes A L I I I I I I I I I I I I I I I I I I I I I

Measurements
Ø Basic measurements with
A L P P P P P P P P P P P P P P P P P P P P P
supply voltage
Ø Quality of supply voltage A L I I I I I I I I I I I I I I I I I I I I I
Ó Copyright 2006 ABB Oy. All rights reserved. Specifications subject to change without notice.
Maintenance Schedule 3AXD10000613694

Issued by Date Language Revision Page

ABB Oy, Drives Service 22.3.2018 en C 2 (2)


Creator name Approver name Distribution
Oliver-shilei Lu Anttijussi Salminen Public

Spare Parts

Ø Spare Parts A L I I I I I I I I I I I I I I I I I I I I I
Ø DC-circuit electrolytic
L P P P P P P P P P P P P P P P P P P P P P
capacitors reforming

1)
Depends on actual load and ambient conditions, up to 9 years can be reached with long-life inverter module fans.
2)
If filter is not replaced, the filter shall be inspected after 3 years from the last inspection.

Note! Recommended service intervals and component replacements are based on the operational environment specified by ABB.
ABB recommends an annual drive inspection to be carried out in order to secure best reliability and optimum
performance. Please refer to service instructions and product manuals for more information or go to www.abb.com/drivesservices.

Ó Copyright 2006 ABB Oy. All rights reserved. Specifications subject to change without notice.