Triconex uses their own protocol for SOE, the system polling SOE events has to be able to use

their SOE
config files that contain tag and description info.
There are OPC drivers for Triconex SOE that will work.
We have used the Matricon OPC server for Triconex.
Be warned that SOE events at 50 or 100 msec. scan time can create large volumes of events, especially
from a chattering limit switch.
You probably do not want to fill your DCS event log with that many events.
We gathered the BMS events into a separate SOE event log.
We limited our BMS alarms and events in the DCS to slower events such as analogue alarms, statuses,
analogue values and first out events for trips.