Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018
Test Report For Motor Protection Relay-Sel 710: DATE: 21.06.2018
Serial No : 3140060036
1. Phase Over Current TOC – [ 51P] Non Directional Current (I) – 4XFLA A : TD- 0s ,FLA:0.815
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 3.26 3.26 0 0.038
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 10 10 0 0.019
Y-N 10 10 0 0.012
B-N 10 10 0 0.029
JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 1.63 1.63 5 4.92
Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 0.733 0.733 5 5.60
Phase Sett Voltage (v) Inj. Voltage(v) Actual Tripping Trip Time(s)
Time (s)
R-N 45 45 2 2.01
Y-N 45 45 2 2.02
B-N 45 45 2 2.05
JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018
Check List:
JAYAMKONDAN V MR.JEYAKUMAR