33KV Line Feeder Relay settings

Feeder No : 10 Location: EN 11

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035745

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 10
5. Full load Current :160
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.48xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 1.6xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 9 Location: EN 12

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035754

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 10
5. Full load Current :160
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.48xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 1.6xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.10xIn Time :0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 8 Location: EN 7 & EN 8

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035752

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 7
5. Full load Current :112
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.34xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 1.12xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.10xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 7 Location: EN6

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035748

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 12
5. Full load Current :192
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.58xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 1.92xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 6 Location: EN 5

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035749

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 16
5. Full load Current :256
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.768xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 2.56xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 5 Location: EN 3,4 & 6

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035753

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 16
5. Full load Current :256
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.768xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 2.56xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 4 Location: EN 6,12 & 13

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035750

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 12
5. Full load Current :192
6. Protection Enabled : I>,I>>,Io>,Io>>
cd
Pickup stage : 0.58xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 1.92xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 3 Location: Future

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035744

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected :
5. Full load Current :
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (0.9xIn)
Pickup stage : 0.9xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 3.6xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 2 Location: Future

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035755

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected :
5. Full load Current :
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (0.9xIn)
Pickup stage : 0.9xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 3.6xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV Line Feeder Relay settings
Feeder No : 1 Location: EN 1

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035747

1. Core Adopted : 400/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : 16
5. Full load Current : 256
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.2xIn)
Pickup stage : 0.768xIn Time : 0.5s
8. Over current stage I>>(4xIn)
Pickup stage : 2.56xIn Time : 0.04s
9. Earth fault stage Io> (40A)
Pickup stage : 0.1xIn Time : 0.5s
10. Earth fault stage Io>>(160A)
Pickup stage : 0.4xIn Time : 0.04s

EID Dept Servies Dept


33KV LV Feeder 2 Relay settings
Feeder No : LV 2 Location: -

Relay Type:VAMP 255 Make:Schneider Elec

Sr. No: 035746

1. Core Adopted : 2000/1-1A


2. VT Primary : 33KV
3. VT Secondry : 110V
4. Number of WEC Connected : -
5. Full load Current : 1749.59
6. Protection Enabled : I>,I>>,Io>,Io>>
7. Over current stage I> (1.1xIn)
Pickup stage : 0.87 x In Time : 1s
8. Over current stage I>>(4xIn)
Pickup stage : 3.48 x In Time : 0.04s
9. Earth fault stage Io> (80A)
Pickup stage : 0.04xIn Time : 1s
10. Earth fault stage Io>>(320A)
Pickup stage : 0.16 xIn Time : 0.1s

EID Dept Servies Dept


Transf 2 HV side O/C & E/F Relay settings
Feeder No : Tr 2 HV side Location: -

Relay Type:Micom P141 Make:Areva

Sr. No: 31729953/04/11

1. Core Adopted : 300/1-1A


2. VT Primary : 220KV
3. VT Secondry : 110V
4. Number of WEC Connected : -
5. Full load Current : 262A
6. Protection Enabled : I>1 , I>4 , IN1>1 , IN1>4
7. Over current stage I> (IEC S Inverse,Directional Forward)
Pickup stage : 880mA I>1 TMS : 200ms
8. Over current stage I>4 (DT)
Pickup stage : 4 x In Time Delay : 0.00s
9. Earth fault stage IN1>1 (IEC S Inverse,Directional Forward)
Pickup stage : 330mA I>1 TMS : 1.25s
10. Earth fault stage IN1>4
Pickup stage : 4 xIn Time Delay : 0.00s

EID Dept Servies Dept


Transf 2 HV REF Relay settings
Feeder No : Tr 2 HV side Location: -

Relay Type:Micom P141 Make:Areva

Sr. No: 31729954/04/11

1. Core Adopted : 300/1-1A


2. VT Primary : -----
3. VT Secondry : -----
4. Number of WEC Connected : ------
5. Full load Current : -----
6. Protection Enabled : Earth Fault 1, SEF/REF Protn
7. Earth Fault 1(IN1>1)
IN1>1 Function : DT Direction Type :Non Directional
Pickup stage : 200mA IN1>1 Time delay : 1.00s
8 SEF/REF Protn(Group 1)
SEF/REF Option : Hi Z REF
Restricted E/F
IREF > Is : 200mA

EID Dept Servies Dept


Transf 2 LV REF Relay settings
Feeder No : Tr 2 LV side Location: -

Relay Type:Micom P141 Make:Areva

Sr. No: 31729949/04/11

1. Core Adopted : 2000/1-1A


2. VT Primary : ----
3. VT Secondry : -----
4. Number of WEC Connected : -----
5. Full load Current : ------
6. Protection Enabled : Earth Fault 1, SEF/REF Protn
7. Earth Fault 1(IN1>1)
IN1>1 Function : DT Direction Type :Non Directional
Pickup stage : 200mA IN1>1 Time delay : 1.00s
8 SEF/REF Protn(Group 1)
SEF/REF Option : Hi Z REF
Restricted E/F
IREF > Is : 200mA

EID Dept Servies Dept


Transf 2 Diff Relay settings
Feeder No : Tranf 2 Location: -

Relay Type:Micom P633 Make:Areva

Sr. No: 36004157

1. Core Adopted Primary : 300/1A


2. Core Adopted in sec Side : 2000/1A
3. VT Primary : 220KV
4. VT Secondry : 110V
5. Protection Enabled : Diff,DTOC1,DTOC2,IDMT1,V/F
6. Diff Protn
Enabled :Yes
Vec Gr ends a-b PS1 : 0
Vec Gr ends a-b PS1 : 0
Idiff> 0.3 Iref
Idiff> > 6 Iref
Idiff>>> 10 Iref
Idiff (CTS) 0.2 Iref(M1=0.3, M2= 0.7)
IR, m2 : 4Iref.
Rush I (2fo)/ I(fo) PS1 = 20%
0 seq Filt a Enabled : Yes
0 seq Filt b Enabled : Yes
0 seq Filt c Enabled : Yes
Over flux balance enabled : Yes
Over I (5fo)/ I(fo) PS1 = 20%
Hyst effective PS1 : Yes
7. DTOC 1
Enabled : Yes
I> : Blocked
I>> : 4 x Inom
I>>> : Blocked
tI> : Blocked
tI>> : o sec
tI>>> : Blocked
8. DTOC 2
Enabled : Yes
I> : Blocked
I>> : 4 x Inom
I>>> : Blocked
tI> : Blocked
tI>> : o sec
tI>>> : Blocked
9. V/f (Over Flux Setting)
V/f Enabled : Yes
V/f Alarm : 1.1 x (Vnom/Fnom)
V/f (Trip)> : 1.2 x (Vnom/Fnom)
V/f (Trip)>> : 1.4 x (Vnom/Fnom)
Time : 2 Sec

EID Dept Servies Dept