Barras: Single Busba 0.9231997
Barras: Single Busba 0.9231997
LINEAS DE TRANSMISION
Name Grid Terminal i Terminal i Terminal j Terminal j u, Magnitude u, MagnitudeLoading Capacitive LoadiActive Power
StaCubic Busbar StaCubic Busbar Terminal i in p.u.Terminal j in p% Mvar Terminal i in
L1 Grid Double Busba B2(1) Double Busbar B3 0.9690663 0.9650706 10.59017 0.4799382 -4.128173
L2 Grid Double Busba B2(1) Double Busbar B3 0.9690663 0.9650706 10.59017 0.4799382 -4.128173
L3 Grid Double Busba B2(1) Single Busbar(2) B7 0.9690663 0.9231997 38.35112 1.225737 29.83092
L4 Grid Double Busba B2(1) Single Busbar(2) B7 0.9690663 0.9231997 36.90873 1.753485 27.55711
L5 Grid Double Busba B3(1) Single Busbar(2) B7 0.9650706 0.9231997 49.92174 0.9153365 41.56222
TRANSFORMADORES
Name Grid HV-Side HV-Side LV-Side LV-Side u, Magnitude u, MagnitudeLoading Active Power Active Power
StaCubic Busbar StaCubic Busbar HV-Side in p.u. LV-Side in p.u% HV-Side in MW LV-Side in MW
T1 Grid Single Busbar B1 Double Busbar(1) B2 1.02 0.9690663 77.08288 84.32461 -84.13169
T2 Grid Double Busba B3(1) Single Busbar B4 0.9650706 1 53.80676 -29.93005 30
T3 Grid Double Busba B3(1) Single Busbar(1) B6 0.9650706 1 53.80676 -29.93005 30
GENERADORES
Name Grid Terminal Terminal Bus T. Active PowerReactive Power Apparent PowPar.no. App.Pow. u, Magnitude
StaCubic Busbar MW Mvar MVA MVA p.u.
G1 Grid Single Busbar B4 PV 30 6.735035 30.74672 1 46.55 1
G2 Grid Single Busbar B6 PV 30 6.735035 30.74672 1 46.55 1
RED EXTERNA
Name Grid Terminal Terminal Bus T. Active PowerReactive Power Apparent Powu, MagnituPower Factor
StaCubic Busbar MW Mvar MVA p.u.
External GrGrid Single Busbar B1 SL 84.32461 82.45271 117.9368 1.02 0.7149983
CARGAS
Name Grid Terminal Terminal u, Magnitude Active PowerReactive Power Apparent PowPower Factor
StaCubic Busbar p.u. MW Mvar MVA
C1 Grid Double Busba B2(1) 0.9690663 35 18.891 39.77273 0.88 LA MADRE DE TODOS LOS PROBLEMAS, CUANDO EL F
C2 Grid Double Busba B3 0.9650706 10 4.843222 11.11111 0.9 YA QUE LAS EMPRESAS COBRAN POR ELLO
C3 Grid Single Busbar B7 0.9231997 50 30.98721 58.82353 0.85
C4 Grid Single Busbar B7 0.9231997 46.4 28.75613 54.58823 0.85
L VALOR MINIMO ESTABLECIDO EN LA NTCSE
Power FactorLoading
%
0.9757139 66.05096 LA CARGABILIDAD ES MAYOR AL 50% HAY BUENA CAPACIDAD DE TRANSPORTE
0.9757139 66.05096