AST Caja Cofre Y6!04!14 IT Security Rooms Specs and Examples

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

IT Security Room:

Products specs review


&
Installation Examples
Smart Shelter
Family
Smart Shelter Family
‰ FD Shelter
‰ Smart Shelter

‰ Smart Shelter Plus


FD Shelter: 60’ and 90’ Fire Resistance
Fast Deployment (FD) Shelter

‰ Kit-Type Shelter (“IKEA” Model)


‰ Installation by any qualified Installation Staff
‰ No supervision from AST Manager Required
‰ Technical Qualities:
9 According NEMA 12 (IP x5 as per EN60529)
9 60 min and 90 min Fire Resistance
9 Steel Walls providing protection and burglar
resistance
9 High Electro Magnetic Shielding Protection 20dB
‰ Installation: flatpack or by AST/Country
partner.
IP x5 Certification acc. EN60529

according
NEMA 12
Panels Certification
‰ Certification
according NFPA
(UNE 23802)
9 60 min
9 90 min

‰ Certification
DIN 4102
(under special
conditions)
SMART SHELTER: SS and SS Plus
Installation with AST Project Management
‰ SS
9 According UL 72 (TÜV Certification with temperatures acc.
EN-1047-2)
9 Fire Resistance Panels 120 minutes (according to UNE
23802 (official lab))
9 According to NEMA 12 (SGS IP x5 certified according
EN60529
9 New Special Door Design (shortly WK3 acc. EN1627)

‰ SS Plus
9 According UL 72 (SGS Certification with temperatures acc.
EN-1047-2)
9 According UL 72 (SGS Certification with humidity acc. EN-
1047-2)
9 According Nema 12 (SGS IP x5 certified acc. EN60529)
9 New Special Door Design (shortly WK3 acc. EN1627)
Improvements SS+
‰ New Panels
with
additional
thermal
insulation

‰ Corner
Panels
Improvements SS+

‰ Joint
between
panels

‰ Floor System
Improvements SS+
‰ Joint
between
ceiling and
walls panels
Test Perfomed October 2005
‰ Dimensions:
3 4 5

2 9 6

9 W: 78.74”
D: 78.74”
1 8 7
9

100
12 13 0 14
10
100
20

H: 98.43”
19 24
9 11 15

100
21 18

10 22 17 16

H/2
0
10
100 23
100 100

25

Cable Duct

100
T0660A

Interior Room Interior Room Door


Heating Curve acc. EN 1047
(vs UL 72)
EN 1047-2 OVEN CURVE (as UL 72)

2000,0

1800,0

1600,0

1400,0

1200,0
Tem p (ºF)

1000,0

800,0

600,0

400,0

200,0

0,0
0

12

15

18

21

24

27

30

33

36

39

42

45

48

51

54

57

60
Time (min.)
Internal Temperature

INTERNAL CELL TEMP. (Blue Line)

acc. EN1047-2: 176ºF


200,0 for I.T. equipment
180,0
acc. UL 72: 150ºF for
160,0
Tapes
140,0
acc. UL 72: 125ºF for
Temperature (ºF)

120,0 Diskettes
100,0

80,0 Internal SS+


temperature
60,0

40,0

20,0

0,0
12

15

18

21

24

27

30

33

36

39

42

45

48

51

54

57

60
0

Tim e (m in.)
Internal Humidity Result
INTERNAL CELL HUMIDITY (%)

90,0 acc. EN1047-2: 85 %


acc. UL 72: 85 % for
85,0
Tapes

80,0
acc. UL 72: 80 % for
Tapes

75,0
Humidity(%)

70,0

Internal SS+ humidity


65,0

60,0

55,0

50,0
0

8
10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

42

44

46

48

50

52

54

56

58

60
Time (min.)
SS Installation Example
SS Installation Example while
the Data Center is running

You might also like