Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

lindab | di splacement diff users

Perforated diffuser - rectangular CRA


Dimensions
1 D

50
2

H
5

6
Description
Comdif CRA is a rectangular perforated displacement dif-
7 fuser for installation against a wall or column. CRA has a
rectangular connection and therefore has a limited depth,
making it ideal for installation in premises where a discrete 16
8 appearance is required. Behind the perforated front plate, C
CRA is equipped with individually adjustable nozzles, mak- B
ing it possible to alter the geometry of the near zone. The
diffuser can be turned and has a rectangular duct connec-
9 tion, so the diffuser can be connected at the top or bottom.
The connection duct CRAZ with a circular connection is
available as an accessory. The diffuser is suitable for the
10 supply of large volumes of moderately cooled air. A

• The diffuser is suitable for the supply of large volumes


of air. A B C D H Weight
11 • The geometry of the near zone can be adjusted using Size mm mm mm mm mm kg
adjustable nozzles 3010 300 278 150 98 980 10,0
• Duct connections and plinths can be supplied as 5010 500 478 150 98 980 17,0
12 accessories 8010 800 778 150 98 980 27,0
8020 800 778 250 198 2020 32,0

Maintenance
13 The front plate can be removed from the diffuser, making it Accessories
possible to clean the nozzles. The visible parts of the dif- Can be supplied with duct connection and plinth.
fuser can be wiped with a damp cloth.
14

15
Order code
16 Materials and finish
Product CRA aaaa
Diffuser: Galvanised steel
Type
Nozzles: Black plastic
Size
Front plate: 1,5 mm galvanised steel
17 Standard finish: Powder-coated
Standard colour: RAL 9010 - white, gloss 30
Order - accessories
18 Connection duct: CRAZ - 1 - size The diffuser is available in other colours. Please contact
Plinth: CRAZ - 2 - size Lindab’s sales department for further information.

472 We reserve the right to make changes without prior notice


lindab | di splacement diff users

Perforated diffuser - rectangular CRA


Technical data Nearzone
1
∆pt [Pa] CRA 3010 5010 8010 8020
70

50
2
50

45
30
40
20
35 h
3
15
30
10
25 v
7
20 vmax 4
5 LWA dB(A)
4
qV [l/s]
50 70 100 150 200 300 400 500 700 1000

200 300 400 500 700 1000 2000 3000


qV [m /h]
3

Large diffusion Small diffusion


5
a0 . 2 [ m ]
1 2 3 (factory setting)
b0.2 [m]
3 4 5 7 10
6

Recommended maximum volume flow


7
The near zone is given at an under-temperature of -3 K to a
maximum terminal velocity of 0.20 m/s.
8
Conversion to other terminal velocities - see table 1, correc-
tion of the near zone for -3 K and -6 K respectively.

2 × a0,2
Sound effect level
9
b0,2

Sound effect level LW [dB] = LWA + Kok

10
Centre frequency Hz
Size 63 125 250 500 1K 2K 4K 8K
3010 9 -1 5 -1 -11 -17 -30 -41 a0,2 2 × a0,2
11
5010 7 1 4 0 -11 -19 -32 -42
8010 15 0 4 0 -12 -20 -31 -43
8020 10 4 6 -2 -11 -21 -33 -39
12
Table 1
Sound attenuation Correction of the near zone (a0.2, b0.2)
Sound attenuation ΔL [dB] including end reflection.
13
Under- Maximum Correction
Centre frequency Hz
temperature velocity Mean velocity factor
Size 63 125 250 500 1K 2K 4K 8K
3010 11 7 6 4 2 2 1 2
Ti-Tr m/s m/s 14
0.20 0.10 1.00
5010 10 6 6 4 2 2 1 2
0.25 0.12 0.80
8010 10 6 4 3 2 1 1 1
8020 7 4 3 2 1 1 1 1 -3K 0.30 0.15 0.70 15
0.35 0.17 0.60
0.40 0.20 0.50
0.20 0.10 1.20 16
0.25 0.12 1.00
-6K 0.30 0.15 0.80
0.35 0.17 0.70
17
0.40 0.20 0.60

18

We reserve the right to make changes without prior notice 473


lindab | di splacement diff users

Perforated diffuser - rectangular CRA


Accessories
1
Connection duct CRAZ-1
B
2

25
3
ØD1

4
L= To be specified

8 A

A B ØD1 Weight
9 Size mm mm mm kg/m
3010 280 100 200 5,0
5010 480 100 250 7,0
10 8010 780 100 315 9,0
8020 780 200 400 11,0

11

12

13

14
Order code
15 Connection duct CRAZ-1 aaaa bbbb c
Type
16 Size

Length According to
17 dimensions in mm
L=max. 2,000 mm

18 Connection Front 0
Back (Standard) 1

474 We reserve the right to make changes without prior notice