11644 5743 01

Full detailed

Room Projects Building PLANTA CELCO


Appliance/Project Test Date 6. Jul 2016 Status
11644-01/048 Retest Date 7. Jun 2017 Pass
Appliance name/Device Comment GEOPARK COLOMBIA S.A.S.
ACDA - T. DISTRIBUCION 4000 AMP. Test Site PRODUCCION/PLANTA CELCO
Measurement Parameter 1 Parameter 2 Parameter 3 Parameter 4 Parameter 5 Limit Result 1 Status
Visual Test Pass
Continuity 10A 5s Manual 0.20 Ω 0.011 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.005 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.008 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.007 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.007 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.006 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.012 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.016 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.019 Ω Pass
Continuity 10A 5s Manual 0.20 Ω 0.014 Ω Pass
Insulation 500V 5s single 10.00 MΩ >199.9 MΩ Pass
Insulation 500V 5s single 10.00 MΩ >199.9 MΩ Pass
Insulation 500V 5s single 10.00 MΩ >199.9 MΩ Pass
Insulation 500V 5s single 10.00 MΩ >199.9 MΩ Pass
HV Test 1890V 30s single 100 mA 4.6 mA Pass
Discharge time t = 0.3 s Pass
U peak = 662Vp
Voltage Ul-n = 456 V
Ul-pe = 450 V
Un-pe = 450 V
Phase rotation = 1.2.3 Pass
Functional Test single P = ----- Pass