Resistance CONFERENCE/

to fire A
CLEAR VIEW ON FIRE
SAFETY
Franck Gyppaz
CABLES
Group Leader – Fire Safety & Services
Nexans Research Center
Lyon

16th of September 2015


Utrech
Agenda

Fire Resistance in Netherlands


Fire Resistance and standardisation
 CPR and Fire Resistant cables
…and the technical challenges
Introduction
Fire fully developed

Temperature
Fire extinction
and escape
possible

Flash over
Start of fire &
Ignition propagation

Time
Role of Role of
fire reaction fire resistance
Fire Resistant Cables are LFH in buildings. They are active components maintaining
the electrical continuity of vital circuit (alarm, lights, exhaust systems…) in fire conditions

...To safe LIFES


Fire Resistance in Netherland
Test standards for fire resistance
 Intrinsic fire resistance of cables
 Fire resistance at lab scale
EN 50200 EN 50362
U≤ 0,6/1 kV, < 80 V and OF cables > 20 mm
≤ 20 mm et S ≤ 2,5 mm²
Fire performance up to 120 min.
Fire Resistance in Netherland
Test standards for fire resistance
 Intrinsic fire resistance of cables on cable managemnt system
 Fire resistance at large scale
4x1.5 and 4x50mm² for LV
2 pairs for JEH(St)
Installation on Fire Resistant CMS / system test
U = 400V max
Temperature-time curve ISO834 / EN1363
All tested specimens shall fulfill the performance
 E30 ; E60 ; E90
Fire Resistance and Standardisation
Construction Product Regulation / CPR
CLC/TC20 WG10 CLC/TC213 WG7-1 CEN TC127 WG2 TG5

Fire Resistance of Fire resistant cable Manufactured Built onsite protective


unprotected management protective systems systems
electrical cables systems - -
Standard cables Standard cables
CPR and Fire Resistant Cables

Standard EN 50200 : Standard EN 50577 :


• Cables U≤ 0,6/1 kV, < 80 V, data and OF • Cables U≤ 0,6/1 kV, data and optical fiber
• ≤ 20 mm et S ≤ 2,5 mm². • Valid whatever  and cross sections
• Fire integrity 120 min max • Fire integrity 90 min max
• Constant Temperature of 850°C • ISO834 Time/Temperature curve
30min of fire resistance following the ISO  90min = 1005°C

 PH 15, 30, 60,90, 120.  P 15, 30, 60,90 ..


CPR and Fire Resistant Cables

EN50200 : EN50577:
• Small scale or Lab test • Large scale test
• Do not consider the installation systems • Cables and systems together
• Only for small cables • Validation of the full cable familly
• Fire temperature relatively low • Representative temperature of real fire
• PH Classification • P Classification equivalent to the management
systems
CPR and Fire Resistant Cables
A different degree of severity…

• Fire exposure >0.5m Vs > 3m


• Load
• Deformation
•…
CPR and Fire Resistant Cables
…and the technical challenges
 Performance assessed at rated voltages Vs 400V
 Cable designs must be adapted(0,6/1kV)

• Insulation :
• Mica/XLPE
• Silicone
• INFIT™
• Bedding
• Sheath
CPR and Fire Resistant Cables
Innovative ceramifiable technology:

After 90 min
@ 900°C

New
New
Technology

Current
Technologie