Ateliers Francois (40 Bar - PET) Compressor
Ateliers Francois (40 Bar - PET) Compressor
These compressors have the ability to increase the pressure of the fluid upto 40 bar but
they do this in different stages. Mostly, the compressors of this type work in three stages and are
L-shaped. The motor coupled with them is from 37 to 550Kw. The fluids have flowrates upto 4800
m^3/hr.
Areas Visited:
We have seen these compressors in:
Sunlight
NH3 Liquid Bar
NH3 Liquid Receiver
Conden Evaporat
ser or Cooled
Glycol
Compressor
Hot
High Temp. NH3 Vapor Glycol
High Press. NH3
Gas
Syrup In
Glycol Tank
Syrup Out
(cooled)
Glycol pump
Purpose of Visit:
To replace the PLC of one Compressors with the other PLC as previously it is replaced as
one of compressor is not working properly and one PLC is not working properly. Now we change
PLC of Compressors and attach with it their real ones as other compressor also works now after
maintenance.
Nestle:
In Nestle we visit the compressor room for water plant here ATLIERS FRANCOIS 40 bar
compressor of 200kW and 55kW with dryers are installed. I also visit water Plant in which There
is a blowing machine and Siedal water line. Blowing machine by using material makes the bottle.
For this first heat the material then passing it from oven and then stretch it. First air comes from
10 bar compressor which blow it little than from 40 bar air compressor air blow it fully. Then this
bottle goes in line where its filling, capping and labeling is performed.
Purpose of Visit(Problem):
To Check the Dryer as its Temperature is not coming at lower value.
Working:
Here After opening Dryer we set the gas Setting valve after checking several things so
then Temperature is coming low to 7 °C to 8 °C. Before setting the temperature is about 30 °C to
35 °C. After this we also make full report on working of compressors in which on marking sheet
note the temperature and pressure values which is demanded in the sheet.
Reason:
The reason for higher temperature we find out is Plant water for cooling is not properly
cooled it as its Temperature is more than its normal temperature which it has to be. So basically
there is a problem in a cooling tower due to which dryer temperature not coming at lower value.