Protection For HV Line Bay
Protection For HV Line Bay
Requirements
a. PUTT
b. POTT
c. EARTH FAULT SETTINGS IN TERMS OF THE POSITIVE SEQUENCE
IMPEDANCE.
d. Tripping signal given before 30ms of fault occurrence
e. Distance time step characteristics
3 forward distance-time step characteristic
1 reverse time step characteristic
f. Lowest setting shall permit under reaching of the protected line and
highest setting shall enable the longest adjacent circuit in the forward
direction to b fully covered when there is a maximum fault current in
feed at the remote end bus bar.
g. Characteristic for measuring elements for earth faults shall be
quadrilateral
h. Characteristic of the measuring elements for inter-phase faults may be
quadrilateral- lenticular or circular
i. ZONE 2 and 3 continuous time delay setting range of 0-1 seconds and 0-
3 seconds respectively
j. Power swing blocking elements
k. Line check feature
l. Trip on reclose
m. Stub protection
n. Protection from high resistance earth faults. Directional earth fault
feature
o. Broken conductor protection
p. Auto reclosing
Single phase fast reclosing
3 phase delayed auto reclosing
Check synchronizing relay
The syncchrocheck relay shall only release a closing command to the
related CB if the voltages at two sides of the open CBs r
synchronous.
This must occur for adjustable time period before close command is
executed
q. Breaker failure relay
r. Disturbance recorder
s. Alarms
t. Distance to fault will be displayed
u. LCD 16*2 for display
v. Main protection tripping connected to the trip coil 1 of the CB.
w. 2 serial interfaces/ 4 profiles
Each IDMT element has separate trip and alarm contacts and separate trip indicators