Head Loss Calculation Head Loss Calculation Using: No. DN MM M MM L/s 1/1 M M/s
Head Loss Calculation Head Loss Calculation Using: No. DN MM M MM L/s 1/1 M M/s
flexible connection
C Hazen constant
V Mean Velocity
discharge outlet
no. part of pipe
elbow ( 45 leg.)
elbow ( 90 leg.)
GH Static heal
L Pipe length
Q Flow rate
check valve
gate valve
Strainer
reducer
tee
0.20
0.20
0.42
2.00
0.19
0.36
0.72
0.50
2.00
1.00
no. DN mm m mm GPM l/s 1/1 m m/s
P1 - Pump suction and discharge header 10" ST 254.46 15 140 1296.00 81.65 3 11 9 1.6055233419
P2 - Pump suction and discharge 8" ST 202.74 3 140 648.00 40.82 2 2 1 2 2 1 6.52 1.2645813997
P3- chiller suction headers 10" ST 254.46 10 140 1296.00 81.65 3 2.16 1.6055233419
P6- chiller discharge headers 10" ST 254.46 21 140 1296.00 81.65 4 2.88 1.6055233419
Static head =
total friction loss =
total dynamic head =
AIR SEPARATOR
Chiller
Y-Strainer
Flow Meter
AHU
DOUBLE REGULATING VALVE
TOTAL PUMP HEAD
PUMP HEAD WITH 25 % SAFETY FACTOR
PUMP HEAD WITH 25 % SAFETY FACTOR
Total heal (DH+GH) / pipe
Accumulative Pressure
RE Reynolds number
DH Total loss
1/1 1/1 m m m m m m
0.00 M
11.56 M
11.56 M
2M
8M
0M
1M
2M
1M
25.56 M
31.95 M
104.82 FT
DCPRO Calculation
Item Dated on February 6, 2017
DCPRO Calculation
Item Dated on February 6, 2017
Y-Strainer (m) 1
flow meter 0
DCPRO Calculation
Item Dated on February 6, 2017
Takyeef
Dated on February 12, 2017
13 -
7 -
42 -
Takyeef
Dated on February 12, 2017
Takyeef comments on DCPRO calculation
Head calculation
14 -
1 -
1 -
0 -
10 -
27 -
30 Safety factor must be 15 % at this stage of design
Takyeef
Dated on February 12, 2017
Takyeef comments on DCPRO calculation
Head calculation
50 -
1 -
1 -
5 -
57 -
62 Safety factor must be 15 % at this stage of design
mp head calculation
Please note that the total pumping head (static head + nozzle pressure drop)
required for the cooling tower in Hamon selection received from Takyeef on
2016-11-28 (attached for reference) for the same project is 6.5 m.
Since the technical selection for Kelvion was not provided, we made an
assumption by modeling the cooling tower with a pressure drop of 8.5 m which
is conservative considering the cooling tower height and flow rate required.
Larger cooling towers in previous projects even had total pressure drops less
than 8.5 m.
Takyeef are applying the 10% safety margin to the overall pump head.
It should only be applied to the pipes, fittings, and accessory loss, but not to
equipment such as chillers and cooling towers.
p head calculation
We are considering 2 m for the pressure drop inside the TES tank.
We consider 1 m pressure drop on the lower diffuser connection and another 1 m on
the upper diffuser connection.
mp head calculation
-
-
-
-
-
Takyeef
Dated on February 18, 2017
5 -
13 -
5 -
11.8
7 no safety factor.
41.8 -
Takyeef
Dated on February 18, 2017
Head calculation Notes
14 -
1 -
1 -
10 -
32 -
safety factor only applied on
33
Pipes , fitting loss Accessory loss
Takyeef
Dated on February 18, 2017
no modification
different (M)
difference (M)
flow meter 3
total
7.8
DCPRO Comment
Please note that the total pumping head (static head + nozzle pressure drop) required for the cooling tower in Ham
received from Takyeef on 2016-11-28 (attached for reference) for the same project is 6.5 m.
Since the technical selection for Kelvion was not provided, we made an assumption by modeling the cooling to
drop of 8.5 m which is conservative considering the cooling tower height and flow rate required. Larger cooling to
projects even had total pressure drops less than 8.5 m.
Suction diffuser selection was not provided by Takyeef. We assumed a conservative pressure drop of 1m based on
selection which shows the pressure drop 11500 GPM flow through a 24”x24” suction diffuser as 1.1 psi (approx.
The pressure drop calculated by Takyeef for the pipes, fittings and accessory losses seems exaggerated. We used a
software to model the condenser pump circuit where all the pipe diameters, lengths, and minor losses are matchin
drawings.
It should only be applied to the pipes, fittings, and accessory loss,
but not to equipment such as chillers and cooling towers.
DCPRO Comment
We are considering 2 m for the pressure drop inside the TES tank.
We consider 1 m pressure drop on the lower diffuser connection and another 1 m on the upper diffuser connection
-
The pressure drop calculated by Takyeef for the pipes,
fittings and accessory losses seems exaggerated.
Draft Reply
Draft Reply
Reference Head (m) Power (KW) per pump Total Power (KW) different
DCPRO 32 315 -
Submittal material 32 300 -45
TAKTEEF online selection 32 300 -45
TAKTEEF 43 375 180
TAKTEEF 50 450 405
Reference Head (m) Power (KW) per pump Total Power (KW) different
DCPRO 24 160 -
Submittal material 24 187.5 82.5
TAKTEEF online selection 24 187.5 82.5
TAKTEEF 30 187.5 82.5
TAKTEEF 33 187.5 82.5
- DCPRO