Head loss calculation PROJECT :

Head loss calculation using (2) HAZEN-WILLIAMS Formula

Local factors of fittings

ID Pipe Inner diameter


DN Nominal diameter

flexible connection
C Hazen constant

Double Reg. valve

Total local factors

V Mean Velocity
discharge outlet
no. part of pipe

elbow ( 45 leg.)

elbow ( 90 leg.)

GH Static heal
L Pipe length

Q Flow rate

check valve
gate valve

Strainer
reducer
tee
0.20
0.20
0.42
2.00

0.19

0.36
0.72
0.50
2.00
1.00
no. DN mm m mm GPM l/s 1/1 m m/s

P1 - Pump suction and discharge header 10" ST 254.46 15 140 1296.00 81.65 3 11 9 1.6055233419

P2 - Pump suction and discharge 8" ST 202.74 3 140 648.00 40.82 2 2 1 2 2 1 6.52 1.2645813997

P3- chiller suction headers 10" ST 254.46 10 140 1296.00 81.65 3 2.16 1.6055233419

P4 -chiller In 8" ST 202.74 7 140 648.00 40.82 1 1 1 1 1 1 1 3.87 1.2645813997

P5 -chiller Out 8" ST 202.74 7 140 648.00 40.82 1 1 1 1 1 1.45 1.2645813997

P6- chiller discharge headers 10" ST 254.46 21 140 1296.00 81.65 4 2.88 1.6055233419

P7 10" ST 254.46 12 140 1083.63 68.27 2 1.44 1.3424330702

P8 10" ST 254.46 74 140 871.00 54.87 2 6 5.04 1.0790207028

P9 5" ST 128.2 2 140 368.18 23.2 2 1 2 2 3.26 1.7969451095

P10 4" ST 102.26 20 140 180.48 11.37 2 2 2.44 1.3844209847

P11 3" ST 77.92 50 140 92.16 5.806 2 8 2 7.48 1.2175736658

P12 2 1/2" ST 62.68 26 140 64.80 4.082 12 2 9.64 1.3230239266

P13 2" ST 52.48 18 140 38.16 2.404 8 2 6.76 1.1114025308

P14 1 1/2" ST 40.94 9 140 20.40 1.285 4 2.88 0.9763042028

P15 1 1/4" ST 35.08 10 140 12.24 0.771 2 1.44 0.7978346917

P16 1" ST 26.64 10 140 7.44 0.469 2 2 2 3.16 0.8409209314


P17 1/2" ST 15.76 9 140 2.64 0.166 2 2 2 6 4 1 7.8 0.852593797

TOTAL 303 8 6 4 1 2 19 66 20 3 ### 0

Static head =
total friction loss =
total dynamic head =
AIR SEPARATOR
Chiller
Y-Strainer
Flow Meter
AHU
DOUBLE REGULATING VALVE
TOTAL PUMP HEAD
PUMP HEAD WITH 25 % SAFETY FACTOR
PUMP HEAD WITH 25 % SAFETY FACTOR
Total heal (DH+GH) / pipe

Accumulative Pressure
RE Reynolds number

Loss m per 100 m

dh(2) Local loss


dh(1) Liner loss
Loss m per m

DH Total loss
1/1 1/1 m m m m m m

408541.46958 0.00857 0.857 0.129 1.182 1.311 1.311 1.311

256381.23298 0.00718 0.718 0.022 0.531 0.553 0.553 0.553

408541.46958 0.00857 0.857 0.086 0.284 0.369 0.369 0.3695

256381.23298 0.00718 0.718 0.05 0.315 0.366 0.366 0.3657

256381.23298 0.00718 0.718 0.05 0.118 0.168 0.168 0.1684

408541.46958 0.00857 0.857 0.18 0.378 0.558 0.558 0.5583

341595.51904 0.006152 0.615 0.074 0.132 0.206 0.206 0.2061

274567.60803 0.004105 0.411 0.304 0.299 0.603 0.603 0.6029

230368.36304 0.023498 2.35 0.047 0.537 0.584 0.584 0.5835

141570.8899 0.018873 1.887 0.377 0.238 0.616 0.616 0.6158

94873.34004 0.020433 2.043 1.022 0.565 1.587 1.587 1.5868

82927.139716 0.030721 3.072 0.799 0.86 1.659 1.659 1.6588

58326.404815 0.027369 2.737 0.493 0.426 0.918 0.918 0.9182

39969.894062 0.028766 2.877 0.259 0.14 0.399 0.399 0.3988

27988.040984 0.023703 2.37 0.237 0.047 0.284 0.284 0.2837

22402.133611 0.036024 3.602 0.36 0.114 0.474 0.474 0.4741


13436.878241 0.068191 6.819 0.614 0.289 0.903 0.903 0.9027

5.101 6.456 11.56 11.56

0.00 M
11.56 M
11.56 M
2M
8M
0M
1M
2M
1M
25.56 M
31.95 M
104.82 FT
DCPRO Calculation
Item Dated on February 6, 2017

Cooling tower - sprayer system head (m) 0.5

Chiller - Up Unit and down Unit (m) 13

Suction Diffuser (m) 1


Pipes , fitting loss Accessory loss (m) 8.71

Static head (m) 8

Pump head (m) 31.2

Pump head with 10 % (m) 32

DCPRO Calculation
Item Dated on February 6, 2017

Chiller Evaporator (m) 14

Air Separator (m) 3

Thermal Storage Tank (m) 1

Y-Strainer (m) 1

flow meter 0

Pipes , fitting loss Accessory loss (m) 5.2

Pump head (m) 24


Pump head with 10 % (m) 24

DCPRO Calculation
Item Dated on February 6, 2017

Expender network (m) 50


Y-Strainer (m) 1
Flow Meter (m) 0
Pipes , fitting loss Accessory loss (m) 4
Pump head (m) 55
Pump head with 10 % (m) 60
Condenser Water Pump head calculati

Takyeef
Dated on February 12, 2017

Takyeef comments on DCPRO calculation


Head calculation

5 Incorrect pressure drop 50 KPA is 5 M not 0.5

13 -

5 Check Suction Diffuser head and provide reference


11.8 DCPRO shall provide detail of pipe loss

7 -

42 -

50 Safety factor must be 15 % at this stage of design

Primary Water Pump head calculation

Takyeef
Dated on February 12, 2017
Takyeef comments on DCPRO calculation
Head calculation

14 -

1 DCPRO heat is summation of three air separators

1 -

1 -

0 -

10 -

27 -
30 Safety factor must be 15 % at this stage of design

Secondary Water Pump head calculati

Takyeef
Dated on February 12, 2017
Takyeef comments on DCPRO calculation
Head calculation
50 -
1 -
1 -
5 -
57 -
62 Safety factor must be 15 % at this stage of design
mp head calculation

DCPRO reply on February 13, 2017

The nozzle head is wrongly referenced in the report.


The attachment highlights the maximum sprayer pressure which is 49 kPa and
not the nozzle pressure drop. The reference to the nozzle pressure drop should be
omitted from the hydraulic report.

Suction diffuser selection was not provided by Takyeef. We assumed a


conservative pressure drop of 1m based on the attached selection which shows
the pressure drop 11500 GPM flow through a 24”x24” suction diffuser as 1.1 psi
(approx. 0.75m).
The pressure drop calculated by Takyeef for the pipes, fittings and accessory
losses seems exaggerated. We used a hydraulic analysis software to model the
condenser pump circuit where all the pipe diameters, lengths, and minor losses
are matching the design drawings.

Please note that the total pumping head (static head + nozzle pressure drop)
required for the cooling tower in Hamon selection received from Takyeef on
2016-11-28 (attached for reference) for the same project is 6.5 m.
Since the technical selection for Kelvion was not provided, we made an
assumption by modeling the cooling tower with a pressure drop of 8.5 m which
is conservative considering the cooling tower height and flow rate required.
Larger cooling towers in previous projects even had total pressure drops less
than 8.5 m.

Takyeef are applying the 10% safety margin to the overall pump head.
It should only be applied to the pipes, fittings, and accessory loss, but not to
equipment such as chillers and cooling towers.

p head calculation

DCPRO reply on February 13, 2017

Air separator selection was not provided by Takyeef.


We assumed a conservative pressure drop of 3m based on the attached selection
(highlighted with a red rectangle)

We are considering 2 m for the pressure drop inside the TES tank.
We consider 1 m pressure drop on the lower diffuser connection and another 1 m on
the upper diffuser connection.

The pressure drop calculated by Takyeef for the pipes,


fittings and accessory losses seems exaggerated.
Takyeef are applying the 10% safety margin to the overall pump head.
It should only be applied to the pipes, fittings, and accessory loss, but not to
equipment such as chillers and cooling towers.

mp head calculation

DCPRO reply on February 13, 2017

-
-
-
-
-
Takyeef
Dated on February 18, 2017

Head calculation Notes

5 -

13 -

5 -
11.8

7 no safety factor.

41.8 -

safety factor only applied on


43
Pipes , fitting loss Accessory loss

Takyeef
Dated on February 18, 2017
Head calculation Notes

14 -

3 Modified to DCPRO selection

1 -

1 -

3 add to pump head

10 -

32 -
safety factor only applied on
33
Pipes , fitting loss Accessory loss

Takyeef
Dated on February 18, 2017

no modification
different (M)

cooling tower 3.5

Suction Diffuser (m) 4

Pipes , fitting loss Accessory loss (m) 3.41


Total 10.91

difference (M)

Air Separator (m) -

Thermal Storage Tank (m) -

flow meter 3

Pipes , fitting loss Accessory loss (m)


4.8

total
7.8
DCPRO Comment

Please note that the total pumping head (static head + nozzle pressure drop) required for the cooling tower in Ham
received from Takyeef on 2016-11-28 (attached for reference) for the same project is 6.5 m.
Since the technical selection for Kelvion was not provided, we made an assumption by modeling the cooling to
drop of 8.5 m which is conservative considering the cooling tower height and flow rate required. Larger cooling to
projects even had total pressure drops less than 8.5 m.

The nozzle head is wrongly referenced in the report.


The attachment highlights the maximum sprayer pressure which is 49 kPa and not the nozzle pressure drop. The r
nozzle pressure drop should be omitted from the hydraulic report.

Suction diffuser selection was not provided by Takyeef. We assumed a conservative pressure drop of 1m based on
selection which shows the pressure drop 11500 GPM flow through a 24”x24” suction diffuser as 1.1 psi (approx.

The pressure drop calculated by Takyeef for the pipes, fittings and accessory losses seems exaggerated. We used a
software to model the condenser pump circuit where all the pipe diameters, lengths, and minor losses are matchin
drawings.
It should only be applied to the pipes, fittings, and accessory loss,
but not to equipment such as chillers and cooling towers.

DCPRO Comment

Air separator selection was not provided by Takyeef.


We assumed a conservative pressure drop of 3m based on the attached selection (highlighted with a red rectangle)

We are considering 2 m for the pressure drop inside the TES tank.
We consider 1 m pressure drop on the lower diffuser connection and another 1 m on the upper diffuser connection

-
The pressure drop calculated by Takyeef for the pipes,
fittings and accessory losses seems exaggerated.
Draft Reply

technical selection for Kelvion was provided to DCPRO


since DCPRO attached to calculation report

referring cooling tower selection , 49 KPA is required sprayer pressure ,


therefore 5m head must add to total head .

DCPRO pressure drop selection based on clear basket .

1- pipes, fittings and accessory losses based on DD design .


2- no detail data from software provide by DCPRO .
3-last report received from DC from dated on February 13, 2017 don’t show
fitting details
- equipment submittal material is not approval material

Draft Reply

add to pump head

referring to report SC-C08-EGC-ALB-CAL-PR-00005 (page 27) , Pressure


Drop Calculations (Hydraulic) ,
1 m head considered for TSE tank
find attached file showing flow meter head
1- pipes, fittings and accessory losses based on DD design .
2- no detail data from software provide by DCPRO .
3-last report received from DC from dated on February 13, 2017 don’t show
fitting details
Condenser Water Pump power - 714 L/S

Reference Head (m) Power (KW) per pump Total Power (KW) different

DCPRO 32 315 -
Submittal material 32 300 -45
TAKTEEF online selection 32 300 -45
TAKTEEF 43 375 180
TAKTEEF 50 450 405

Primary Water Pump power - 513 L/S

Reference Head (m) Power (KW) per pump Total Power (KW) different
DCPRO 24 160 -
Submittal material 24 187.5 82.5
TAKTEEF online selection 24 187.5 82.5
TAKTEEF 30 187.5 82.5
TAKTEEF 33 187.5 82.5

Secondary Water Pump power - 513 L/S


Reference Head (m) Power (KW) per pump Total Power (KW) different
DCPRO 60 375 -
Submittal material 60 450 225

scenario I (Worst ) - additional total (KW) 712.5

scenario II - additional total (KW) 487.5

- DCPRO

Overall Plant Power Consumption (kWElectrical) 435,649

Overall Plant Efficiency (kWElectrical/Ton) 0.7292

SEER (BTU/ kWElectrical.Hr) 16.46