Professional Documents
Culture Documents
Air Compressor System-Atlas Copco
Air Compressor System-Atlas Copco
Deo R. Ybarrita
Technical & Training Manager
Program Agenda
Air Requirements
Control techniques
3
Feed mill compressed air requirements
Instrumentation
Production pneumatic cylinders & valves
Conveyors
Blowers for Waste Water Treatment Plant
4
Understanding Air Compressor
Basic Parameters
Pressure
Atmospheric Pressure
Gauge Pressure
Absolute Pressure
Psi or Bar
Temperature
Ambient temperature
Room temperature
Discharge temperature
°C or °F
Flow rate
Volume per unit time
l/s or cfm
Power
Package power
Shaft input power
HP or KW
5
Understanding Air Compression
Basic Compression
Characteristics of compression
Displacement
Enclosing a volume of air and
then increasing the pressure by
reducing the area of the enclosed
volume
Reciprocating
Rotary
Dynamic
The flowing gas accelerates to a
high velocity by means of the
rotating blades, after which the
velocity of the gas is transformed
to pressure
6
Understanding Air Compression
Types of Compressor
Displacement
Reciprocating
Piston Compressor
Rotary
Screw Compressor
Other types
Dynamic
7
Distribution
End User
Pre-filter
8
Control
Pg = working % RH = 14 to 26%
pressure
T out = Cooling air
+ 10 °C
Power
cfm
10
Operational and Control of Air Compressor,
Auxiliaries & Accessories
11
Working Principle
Airflow
Oil Flow
Regulation
Operating Principle : Air Flow
Air Intake
Air Filter Minimum Pressure Valve
Compressor
Element Cooling Fan
Moisture Trap
Check Valve
Delivery Line
Float Valve
Oil/Air separator
tank
13
Air Flow Control
Tin < 40 °C Toutelement < Tin + 60 °C
Pin = 0 (g) Pout = WP (g)
14
Working Principle
- Airflow
- Oil Flow
- Regulation
Operating Principle: Oil Flow
Scavenging Line
Oil/Air separator
tank Oil
Filter
Oil Line
18
Oil Flow Control - Loading
T = Tin + 60 °C
P = (WP – 1 to 2 bar) (g)
22
Air Flow & Oil Flow During Loading
Tair = Tcooling air + 10 °C
P = WP (g)
Tair = Tin + 60 °C
P = WP (g)
100% in
inlet, cfm
cap
Tout = Tin + 60 °C Toil = (Tin + 60 °C) - 25
P = WP (g) P = WP (g)
23
Oil Flow Control - Unloading
10% air
inlet, cfm T = Depends on TBV (60 to 75 °C
capacity
P = (< 1 bar) (g)
24
Air flow and Oil Flow During Unloading
Tout = (Tin + 60 °C) -
25
P = (< 1 bar) (g)
10%
air
inlet,
cfm
cap
25
Regulating System – Load / Unload
Pressure Transducer
Feedbacks signal to elektronikon for
data processing
Electrical signal is 0 to 5 Vdc
0.5 to 4.5 Vdc for 0 bar and max
pressure (bar) respectively
Solenoid Valve
Supplies control air into the unloader
valve during loading
Vent the control air trap in the
unloader valve into the atmosphere
during unloading.
Supply voltage is controlled by
elektronikon.
26
Regulating System – Load / Unload
Elektronikon
Monitor
Compares feedback data
against setting
Provides or cuts off electrical
supply to solenoid valve
Unloading Assembly
Opens or close the air intake
Control air is coming through
solenoid valve
27
Regulating System - Unloaded
Y1 – Solenoid Valve
is de-energized
28
Regulating System - Loaded
Y1 – Solenoid Valve
is energized
29
Proper Operation
Before Starting:
Check vacuum indicator, clean or replace air
filter element if necessary
Check Oil level, top-up if necessary
Check belt condition if belt driven, retighten or
replace if necessary
Check external condition of coolers, schedule
servicing if necessary
Close the manual drain valve.
30
Proper Operation
During Operation
Check vacuum indicator, schedule replacement if necessary
Check pressure of oil separator if supported by the elektronikon
Check if automatic drain is working, schedule immediate
servicing if malfunctioning.
Record the operating parameter data
31
Monitoring & Inspection
Important Parameters
Pg = working % RH = 14 to 26%
pressure
T out = Cooling air
+ 10 °C
45
Protection
Overheating protection
Element out temperature
sensor – PT 1000
Trips at 110 °C (or 120 °C)
46
Protection
Overload Protection
Located at load side, Phase
current
OL Setting, Phase = (FLA/1.73)
x Service Factor
Located at supply side, FLA
OL Setting = FLA x Service
Factor
47
Protection
48
Elektronikon
50
Elektronikon®
Reliability
– controls and monitors compressor
and integrated ancillaries
– protects compressor
and surroundings via automatic
shut-down
in case of a fault in a vital function
– gives warnings well before shut-
down, so proactive measurements
can be taken
51
Elektronikon®
Service friendliness
– generates service
‘WARNING’ messages
52
Atlas Copco Compressors
Proper Care
Proper Care
– Compressor Elements
Air Filter
Must be maintained/replaced regularly
Oil
Right Quality is of utmost importance
Non Foaming Property
Correct Viscosity Grade
Oil affects the lifetime of the bearings
Operating temperature
54
Proper Care
- Main Drive Motor
Greasing
Frequency
Every 4,000 running hours or
Every 2,000 running hours
Quality
As specified in the manual and reflected in motor
data plate
Do not mix different type of grease
Quantity
As specified in manual or data plate if re-greasing
is done every 4,000 running hrs
½ of specified quantity if re-greasing is done
every 2,000 running hours
55
Proper Care
- Main Drive Motor
Re-bearing
Every after 24,000 hours < 100 hp
56
Proper Care
- Operational Integrity
Compressor Room
Ambient should not exceed 40°C
57
Atlas Copco
Reactive/Breakdown Maintenance
Preventive Maintenance
Predictive Maintenance
59
Compressor filtration system
Oil Separator
Air Filter
Oil Filter
Air
Compressor Oil
60
PMS: Preventive Maintenance Schedule
Every 2,000 hrs
Change Oil
Change oil filter
Change air filter
For GX units: Replace oil separator
Change drive belt/s for GX units & GA5-
GA10 units
Grease motor bearing (if not greased for
life)
Servicing of moisture trap
63
Troubleshooting
78
Troubleshooting
Overheating:
» Causes, Prevention & Solution
79
Troubleshooting
Compressor overheating
High ambient/room temperature
Very low oil level
Clog air filter
Clog oil separator element
Clog cooling fins of oil cooler
Oil cooler clog internally
Clog oil filter – insufficient cooling during unloading
Oil stop valve stuck up at close position
Thermostatic by pass valve stuck up at by passed
position
Malfunctioning cooling fan motor & damaged cooling fan
80
Overheating Problem
>40 °C Oil cooler, internally
OF
81
Overheating Problem Oil separator AF Motor & fan
TBV
82
Troubleshooting Scavenging Line
83
Clog OS
Troubleshooting P < MWP
Inlet or discharge
Compressor overloading
Clog oil separator
element, OS
High operating pressure
(should be less than the
CV
MWP)
Bearing problem for the
compressor element –
Inlet or discharge side
Bearing problem for the Drive end or N Drive end
motor – Drive End or N
Drive End
Leaking check valve CV
– trip during starting
84
Troubleshooting P
Loose
con. KO4 P set
to SV
Compressor not sensor
loading
Loading pressure
setting is below
operating pressure
(with other units)
Malfunctioning
pressure sensor
Upper solenoid Upper
valve plunger plunger
leaking
No supply voltage
for solenoid valve
SV
KO4 always open
Loose
connection
loading circuit KO4
Open solenoid Open Supply inside
coil voltage module
valve coil
85
KO4
Troubleshooting inside
module
Seal ring
Compressor not & o ring
loading
Open contact from
KO4 relay
(Elektronikon
module)
Leaking switching
valve & broken
spring for
unloading valve
assembly
Inlet valve stuck
up at closed
position
Leaking loading
piston seal ring Inlet valve
and o-ring
Leaking pilot air
Switching Pilot air
line
valve &
Spring
86
Troubleshooting Plant Pressur P
deman e sensor settin
d g
Compressor not
unloading/partial loading
High unloading
pressure setting
(with other units)
High plant demand
Air leak Leaking
plunger
Malfunctioning
pressure sensor
Leaking lower
solenoid valve
plunger
Inlet valve stuck up
at open position
Clog pressure sensor
- air side Inlet
IV valve
Broken inlet valve Spring
spring
87
Compressed Air Audit
Air Leakages
Moisture content & Relative humidity
Room Lay out & Ventilation
Restrictions on air filters, oil separator & line filters
92
Control
Pg = working % RH = 14 to 26%
pressure
T out = Cooling air
+ 10 °C
94
Air leakage and corresponding Power Consumption
95
Water in Compressed Air System
96
Compressed Air Quality Dry Air,
After AR Design
– Wet Air %RH = 15
Delivery
– Wet Air to 26
Air
Receiver
, AR –
Wet Air
Air Inlet –
Depends on
% RH at site
97
Water entering the system = 39.286 g/m³ x 0.85 x
Water in the system 200 liters/s x 60 s/min x 60 min/hr x m³/1000 liters x
24 hrs/day = 577,032.768 g/day x liters/1000 g =
577.032768 liters/day ≈ 577 liters/day
Compressor with a working
pressure of 7 bar (e),
compressed the air to 1/8 of the
7 bar (e)
volume.
How much water enter the
system in liters/day?
Answer: 577 liters/day
577 l/day
of water
Inlet: 35 °C, 85
% RH, 200 l/s
98
Water in the system
How much water separated at the air cooler °C
Answer = 437 l/day of water or condensates
85 % RH, 200
577 l/day 140 l/day
l/s of water of water
How much water is separated = 39.286 g/m³ x 0.85 x 8 (P.R.) – Outlet: 45 °C, 100 %
64.8 g/m³ = 202.3448 g/m³ x 90 m³/hr x 24 hrs/day = RH, 200 l/s, 7 bar (e)
437,064.768 g/day x liter/1000 g = 437 liters/day
Or = 577 – 140 = 437 liters/day (at 35 °C, 85% RH, FAD of 200 437 l/day
l/s) of water
99
Water into the FD dryer = 50.672 g/m³ x 200 l/s x
Water in the system 3600 s/hour x 1/8 x m³/1000 l x l/1000 g x 24
hours/day = 109.45 l/day
100
Water in the system
7 bar Water into
From the set up: Comp > Air 40 °C air net =
(e)
Receiver > FD dryer 12.86
l/day
How much water separated at
the moisture trap of FD dryer 32
Answer: 96.59 l/day
°C
How much water enter the air net
(leaving the dryer) with a PDP or
LAT of 3 °C?
Answer: 12.86 l/day
%
RH =
PDP = 3
°C
18
102
Room Lay Out & Ventilation
103
Compressor Room Layout
Wall
A A
Wall
Compressor Wall
104
Compressor Room Layout
Wall
Comp 1
>A
>A
A
Comp 2
105
Compressor Room Ventilation
dp max across ducting < 30 Pa
Limit temperature rise to 5 °C
Maximum pressure drop of 30 Pa for
ducting
Maximum length of 6 meters
Maximum bends of 2 dT < 5 ˚C
Cross sectional area of ducting should be >
the area of the base.
106
Compressor Room Ventilation
107
Material Specification
108
Committed to
sustainable productivity.
113
114