Professional Documents
Culture Documents
PM4H A
PM4H A
PM4H-A
DIN48 SIZE
MULTI-RANGE ANALOG TIMER PM4H-S
PM4H-M
UL File No.: E122222 CSA File No.: LR39291
FEATURES
48
• Front panel of IP65 type is protected against water-splash and dust
1.890 • 100-240V AC free-voltage input, 48-125V DC type available
• Built-in Screw terminals
• Screw terminal type is used for easy wiring and reducing additional cost for
62.5 mm inch accessories.
48 2.461
1.890 • 8 different operation modes: (PM4H-A)
• Tube base with pin style terminals
Socket • Multiple time ranges — 1 s to 500 h (Max.)
mount Flush mount • Short body — 62.5mm 2.461 inch (screw terminal type)
PRODUCT TYPE
Contact Protective Rated
Type Operation mode Time range Terminal type Part No.
arrangement construction operating voltage
11 pin PM4HA-H-AC240VW
100 to 240V AC
Screw terminal PM4HA-H-AC240VSW
11 pin PM4HA-H-24VW
8 operation modes IP65 24V AC/DC
Screw terminal PM4HA-H-24VSW
• Pulse ON-delay
11 pin PM4HA-H-DC12VW
• Pulse Flicker 12V DC
• Pulse ON-flicker Relay Screw terminal PM4HA-H-DC12VSW
PM4H-A Timed-out
• Differential ON/OFF-delay (1) (2) 11 pin PM4HA-H-AC240V
• Signal OFF-delay 2 Form C 100 to 240V AC
Screw terminal PM4HA-H-AC240VS
• Pulse One-shot
11 pin PM4HA-H-24V
• Pulse One-cycle IP50 24V AC/DC
Screw terminal PM4HA-H-24VS
11 pin PM4HA-H-DC12V
12V DC
Screw terminal PM4HA-H-DC12VS
8 pin PM4HS-H-AC240VW
100 to 240V AC
Screw terminal PM4HS-H-AC240VSW
8 pin PM4HS-H-24VW
IP65 24V AC/DC
Screw terminal PM4HS-H-24VSW
8 pin PM4HS-H-DC12VW
Relay 16 selectable 12V DC
Screw terminal PM4HS-H-DC12VSW
PM4H-S Power ON-delay Timed-out ranges
2 Form C 8 pin PM4HS-H-AC240V
1s to 500h 100 to 240V AC
Screw terminal PM4HS-H-AC240VS
8 pin PM4HS-H-24V
IP50 24V AC/DC
Screw terminal PM4HS-H-24VS
8 pin PM4HS-H-DC12V
12V DC
Screw terminal PM4HS-H-DC12VS
8 pin PM4HM-H-AC240VW
100 to 240V AC
Screw terminal PM4HM-H-AC240VSW
8 pin PM4HM-H-24VW
IP65 24V AC/DC
5 operation modes Screw terminal PM4HM-H-24VSW
(With instantaneous contact) Relay 8 pin PM4HM-H-DC12VW
• Power ON-delay Timed-out 12V DC
Screw terminal PM4HM-H-DC12VSW
PM4H-M • Power Flicker 1 Form C
Instantaneous 8 pin PM4HM-H-AC240V
• Power ON-flicker 100 to 240V AC
• Power One-shot 1 Form C Screw terminal PM4HM-H-AC240VS
• Power One-cycle 8 pin PM4HM-H-24V
IP50 24V AC/DC
Screw terminal PM4HM-H-24VS
8 pin PM4HM-H-DC12V
12V DC
Screw terminal PM4HM-H-DC12VS
If you use this timer under harsh environment, please order above sealed type (IP65 type). IP65 type — Protection dust and water jet splay on the front face.
When ordering CE type, please order the Part No. with suffix CE. (e.g. PM4HA-H-AC240VWCE)
TIME RANGE
Time unit PM4H-A/PM4H-S/PM4H-M
sec min hrs 10h
Scale All types of PM4H timer have multi-time
1 0.1s to 1s 0.1 min to 1 min 0.1h to 1h 1.0h to 10h range.
5 0.5s to 5s 0.5 min to 5 min 0.5h to 5h 5h to 50h 16 time ranges are selectable.
Control
10 time range 1.0s to 10s 1.0 min to 10 min 1.0h to 10h 10h to 100h
1s to 500h (Max. range) is controlled.
50 5s to 50s 5 min to 50 min 5h to 50h 50h to 500h
Note: 0 setting is for instantaneous output operation.
12
02/2003
PM4H-A/S/M
CHARACTERISTICS
Item Type PM4H-A PM4H-S PM4H-M
Rated operating voltage 100 to 240V AC, 12V DC, 24V AC/DC, 48 to 125V DC
Rated frequency 50/60Hz common (AC operating type)
Approx. 10VA (100 to 240V AC)
Rated power consumption Approx. 2.5VA (24V AC)
Approx. 2W (12V DC, 24V DC, 48 to 125V DC)
Output rating 5A 250V AC (resistive load)
Rating Pulse ON-delay
Power ON-delay
Pulse Flicker
Power Flicker
Pulse ON-Flicker
Power ON-flicker
Operating mode Differential ON/OFF-delay (1) (2) Power ON-delay
Power One-shot
Signal OFF-delay
Power One-cycle
Pulse One-shot
(with instantaneous contact)
Pulse One-cycle
Time range 1s to 500h (Max.) 16 time ranges switchable
Operating time fluctuation ±0.3% (power off time change at the range of 0.1s to 1h)
Time Setting error ±5% (Full-scale value)
accuracy
Note:) Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of –10 to +50°C +14 to +122°F)
Timed-out 1 Form C
Contact arrangement Timed-out 2 Form C
Instantaneous 1 Form C
Contact
Contact resistance (Initial value) Max. 100mΩ (at 1A 6V DC)
Contact material Silver alloy Au flash on Silver alloy
Mechanical (contact) 2×107
Life
Electrical (contact) 105 (at rated control capacity)
Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.)
Between live and dead metal parts
Between input and output
Insulation resistance (Initial value) Min. 100MΩ (At 500V DC)
Between contacts of different poles
Between contacts of same pole
Electrical
2,000Vrms for 1 min Between live and dead metal parts
function
2,000Vrms for 1 min Between input and output
Breakdown voltage (Initial value)
2,000Vrms for 1 min Between contacts of different poles
1,000Vrms for 1 min Between contacts of same pole
Min. power off time 100ms
Max. temperature rise 55°C 131°F 65°C 149°F
Functional Min. 98m/s2 (4 times on 3 axes)
Shock resistance
Mechanical Destructive Min. 980m/s2 (5 times on 3 axes)
function Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Vibration resistance
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Ambient temperature –10 to +50°C +14 to +122°F
Operating Ambient humidity Max. 85%RH
condition Atmospheric pressure 860 to 1,060hPa
Ripple factor (DC type) 20%
Protective construction IP65 on front panel (using rubber gasket ATC18002) <only for IP65 type>
Others 100g 3.527 oz (Pin type)
Weight
110g 3.880 oz (Screw terminal type)
Note: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple
factor for DC), 20°C 68°F ambient temperature, and 1s power off time.
2) For the 1s range, the tolerance for each specification becomes ±10ms.
WIRING DIAGRAMS
PM4H-A PM4H-S
Pin type Screw terminal type Pin type Screw terminal type
• Timed-out 2 Form C • Timed-out contact 2 Form C • Timed-out 2 Form C • Timed-out 2 Form C
COM COM N.C. N.C. COM COM
N.O.
02/2003
PM4H-A/S/M
PARTS NAME
PM4H-S PM4H-A PM4H-M
Power indicator LED Operation indicator LED
Hand
Time indicator window
Set dial
DIMENSIONS mm inch
• PM4H-
Screw terminal type Pin type
(Flush mount) (Flush mount/Surface mount)
6.0 6.0
48 12.0 .236 62.5 48 12.0 .236 66.5
1.890 .472 2.461 1.890 .472 2.618 14.5
.571
∅1.614
∅1.614
44.5 44.5
∅41
48 48 ∅41
1.890 1.752 1.890 1.752
0 0
1.969
48 66 44.5 48 66
50
50
48 1 61.5 48 77
1.890 .039 2.421 1.890 3.031
14
02/2003
PM4H-A/S/M
OPERATION MODE The new settings
are valid after power OFF ON LED lighting LED flickering
PM4H-A T: Setting time t1, t2, ta, tb<T t1+t2=T
Operation mode Operation Time chart
Turn the operation selector to ON . Power supply
ON
OFF
Power is applied continuously. When a start signal is applied, the ON ON ON
time cycle begins. The output contacts change state after the time Operation signal – OFF OFF
OP. LED
POWER LED
When the time delay is completed, the output contacts change state ON
Reset – OFF
and next time cycle begins. When this time delay is completed, the
Pulse ON
output contacts return to their normal state. This cycle will repeat until – OFF
Flicker Stop
a reset signal is applied or power is removed. T T ta t1 t2 tb
FL (Note: When a stop signal is applied during timing operation, the time ON ON
cycle stops. When a stop signal is removed, the time cycle begins.) Time out (N.O. contact) OFF OFF
OP. LED
POWER LED
the time delay is completed, the output contacts change state and ON
Reset – OFF
next time cycle begins. When the time delay is completed, the output
Pulse ON
contacts return to the normal state. Stop – OFF
ON-flicker
This cycle will repeat until a reset signal is applied or power is T T ta t1 t2 T tb
FO removed. ON
OFF OFF
(Note: When a stop signal is applied during timing operation, the time Time out (N.O. contact)
cycle stops. When a stop signal is removed, the time cycle begins.) OP. LED
POWER LED
(Note: When a stop signals is applied during timing operation, the time OP. LED Restart
cycle stops. When a stop signal is removed, the time cycle begins.)
POWER LED
removed the time cycle begins. The output contacts will return to their ON
Reset – OFF
normal state when the time delay is completed.
Signal ON
Reset will occur when a reset signal is applied or power is removed. Stop – OFF
OFF-delay
(Note: When a stop signal is applied during timing operation, the time T ta tb
SF cycle stops. When a stop signal is removed, the time cycle begins.) ON
Time out (N.O. contact) OFF
OP. LED
POWER LED
02/2003
PM4H-A/S/M
Operation mode Operation Time chart
ON
Turn the operation selector to OS . Power supply OFF
Power is applied continuously. When a start signal is applied, the out- ON ON
put contacts change state immediately and time cycle begins. When Operation signal – OFF OFF
the time delay is completed, the output contacts return to their normal ON
Reset – OFF
state. The contacts will return to normal state when a reset signal is
Pulse ON
applied or power is removed. Stop – OFF
One-shot
(Note: When a stop signal is applied during timing operation, the time T T t1 t2 ta
OS cycle stops. When a stop signal is removed, the time cycle begins.) ON
Time out (N.O. contact) OFF
OP. LED
POWER LED
tacts remain in their normal state. The output contacts change state ON
Reset – OFF
after time delay is completed. When the start signal is removed the
Differential ON
time cycle begins. The output contacts return to their normal state Stop – OFF
ON/OFF-delay (2)
after time delay is completed. The start signal is applied or start sig- T t1 t2 ta tb
OF2 nal is removed while timing operation, the output contacts change ON ON
state and time cycle begins at this point. Time out (N.O. contact) OFF OFF
The contacts will return to their normal state when a reset signal is
OP. LED Restart
applied or power is removed.
POWER LED
(Note: When a stop signal is applied during timing operation, the time
cycle stops. When a stop signal is removed, the time cycle begins.) Note: LED lighting or No LED lighting
ON
Turn the operation selector to OC . Power supply OFF
OC cycle stops. When a stop signal is removed, the time cycle begins.) ON
OFF
ON
OFF
Time out (N.O. contact)
OP. LED
POWER LED
ON
T OFF
Time out (N.O. contact)
Power ON-delay
OP. LED
POWER LED
PM4H-M
Operation mode Operation Time chart
Power ON-delay Power ON-delay Power ON-delay
ON When power is applied continuously, the output contacts change ON
FO (As for other operation mode, refer to the operation mode of PM4H- Instantaneous contact (N.O. contact)
ON
OFF
02/2003
PM4H-SD/SDM
mm inch
66.5
48 2.618
1.890
CHARACTERISTICS
Item Type PM4H-SD/SDM
Rated operating voltage 100 to 240V AC, 24V AC
Rated frequency 50/60Hz common
Approx. 10VA (100 to 240V AC)
Rated power consumption
Approx. 2.5VA (24V AC)
Rating
Output rating 5A 250V AC (resistive load)
Operation mode - star-delta switching (Power ON-delay)
operation control time range 2s to 100s, 4 time ranges switchable
- switching time 0.04, 0.1, 0.3, 0.5, 0.7s (5 time range selectable)
Operation time fluctuation ±0.3% (power off time change at the range of 0.5s to 1h)
Time Setting error ±5% (Full-scale value)
accuracy
Note:) Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of –10 to +50°C +14 to +122°F)
Star ( ) side: Timed-out 1 Form A Delta () side: Timed-out 1 Form A
Contact arrangement
Instantaneous: 1 Form A (Instantaneous for SDM type only)
Contact
Contact resistance (Initial value) Max. 100mΩ (at 1A 6V DC)
Contact material Au flash on Silver alloy
Mechanical (contact) 2×107
Life
Electrical (contact) 105 (at rated control capacity)
Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.)
Between live and dead metal parts
Between input and output
Insulation resistance (Initial value) Min. 100MΩ (At 500V DC)
Between contacts of different poles *3
Between contacts of same pole
Electrical
2,000Vrms for 1 min Between live and dead metal parts
function
2,000Vrms for 1 min Between input and output
Breakdown voltage (Initial value)
2,000Vrms for 1 min Between contacts of different poles *3
1,000Vrms for 1 min Between contacts of same pole
Min. power off time 500ms
Max. temperature rise 65°C 131°F
Functional Min. 294m/s2 (4 times on 3 axes)
Shock resistance
Mechanical Destructive Min. 980m/s2 (5 times on 3 axes)
function Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Vibration resistance
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1h on 3 axes)
Ambient temperature –10 to +50°C +14 to +122°F
Operating Ambient humidity Max. 85%RH
condition
Atmospheric pressure 860 to 1,060hPa
Protective construction IP65 on front panel (using rubber gasket ATC18002) <only for IP65 type>
Others 100g 3.527 oz (Pin type)
Weight
110g 3.880 oz (Screw terminal type)
Notes: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage, 20°C 68°F ambient
temperature, and 1s power off time.
2) For the 2s range, the tolerance for each specification becomes ±10ms.
3) Between contacts of different poles for SDM type only.
17
02/2003
PM4H-SD/SDM
PRODUCT TYPE
Operation Protective Rated operating Terminal
Type Contact arrangement Time range Part number
mode construction voltage type
8 pin PM4HSD-S-AC240VW
PM4H-SD Relay Timed-out 100 to 240V AC
screw PM4HSD-S-AC240VSW
Star ( )-Delta side: 1 Form A
() switching side: 1 Form A 8 pin PM4HSD-S-AC24VW
24V AC
screw PM4HSD-S-AC24VSW
IP65
PM4H-SDM Relay Timed-out 8 pin PM4HSDM-S-AC240VW
Star ( )-Delta 100 to 240V AC
side: 1 Form A screw PM4HSDM-S-AC240VSW
() switching
(Instantaneous side: 1 Form A 8 pin PM4HSDM-S-AC24VW
4 selectable ranges over 24V AC
contact) Star ( )- Instantaneous: 1 Form A screw PM4HSDM-S-AC24VSW
2s to 100s
Delta ()
( - switching time: 8 pin PM4HSD-S-AC240V
switching 100 to 240V AC
PM4H-SD Relay Timed-out 0.04, 0.1, 0.3, 0.5, 0.7s) screw PM4HSD-S-AC240VS
Star ( )-Delta side: 1 Form A
() switching side: 1 Form A 8 pin PM4HSD-S-AC24V
24V AC
screw PM4HSD-S-AC24VS
IP50
PM4H-SDM Relay Timed-out 8 pin PM4HSDM-S-AC240V
Star ( )-Delta 100 to 240V AC
side: 1 Form A screw PM4HSDM-S-AC240VS
() switching
(Instantaneous side: 1 Form A 8 pin PM4HSDM-S-AC24V
Instantaneous: 1 Form A 24V AC
contact) screw PM4HSDM-S-AC24VS
When ordering CE type, please order the Part No. with suffix CE. (e.g. PM4HSD-S-AC240VWCE)
∅1.614
44.5
∅41
48
side time-delay contact 1.890 1.752
Operating Operating side time-delay contact 0
voltage voltage Instantaneous contact
(SDM type)
side time-delay contact
Screw terminal type side time-delay contact
No instantaneous contact With instantaneous contact Instantaneous contact
(SDM type)
con- con- con- con-
OPERATION MODE
tact tact tact tact
Power
supply
Instantaneous
contact
Operating Operating
voltage voltage Contact
t1: operation time
( indicator LED lights)
Contact t 2: – switching time
t 3: operation time
t1 t2 t3 ( indicator LED lights)
TIME RANGE
Time range
unit Operating (s) - switching time (s)
Time range
2 0.2s to 2s 0.04
10 1s to 10s 0.1
0.3
20 2s to 20s 0.5
100 10s to 100s 0.7
18
02/2003
PM4H-F
48
1.890
mm inch
62.5
48 2.461
1.890
CHARACTERISTICS
Item Type PM4H-F8 PM4H-F8R PM4H-F11R
Rated operating voltage 100 to 120V AC, 200 to 240V AC, 24V AC, 24V DC, 12V DC
Rated frequency 50/60Hz common (AC operating type)
Approx. 5VA (AC type)
Rated power consumption
Rating Approx. 2W (DC type)
Output rating 3A 250V AC (resistive load)
Operation mode Power OFF-delay Power OFF-delay (with reset)
Time range 1s to 10s: 3 range switchable 1 min to 10 min: 3 range selectable
Operation time fluctuation ±0.3%
Time Setting error ±5% (Full-scale value)
accuracy *1 Voltage error ±0.5% (at the operating voltage changes between 85 to 110%)
Temperature error ±2% (at 20°C ambient temp. at the range of –10 to +50°C +14 to +122°F)
Contact arrangement Timed-out 2 Form C Timed-out 1 Form C Timed-out 2 Form C
Contact Contact resistance (Initial value) Max. 100mΩ (at 1A 6V DC)
Contact material Au flash on Silver alloy
Mechanical (contact) 107
Life
Electrical (contact) 105 (at rated control capacity)
Allowable operating voltage range 85 to 110% of rated operating voltage (at 20°C coil temp.), 90 to 110% (DC Type)
Between live and dead metal parts
Between input and output
Insulation resistance (Initial value) Min. 100MΩ (At 500V DC)
Between contacts of different poles *3
Between contacts of same pole
1,500Vrms for 1 min Between live and dead metal parts
Electrical 1,500Vrms for 1 min Between input and output
function Breakdown voltage (Initial value)
1,000Vrms for 1 min Between contacts of different poles *3
750Vrms for 1 min Between contacts of same pole
s range type: 100ms
Min. power supply width
min range type: 2s
Min. reset time 50ms
Max. temperature rise 55°C 131°F
Functional Min. 98m/s2 (4 times on 3 axes)
Shock resistance
Mechanical Destructive Min. 980m/s2 (5 times on 3 axes)
function Functional 10 to 55Hz: 1 cycle/min double amplitude of 0.5mm (10min on 3 axes)
Vibration resistance
Destructive 10 to 55Hz: 1 cycle/min double amplitude of 0.75mm (1hr on 3 axes)
Ambient temperature –10 to +50°C +14 to +122°F
Operating Ambient humidity Max. 85%RH
condition Atmospheric pressure 860 to 1,060hPa
Ripple factor (DC type) 20%
Protective construction IP65 on front panel (using rubber gasket ATC18002) <only for IP65 type>
Others 100g 3.527 oz (Pin type)
Weight
110g 3.880 oz (Screw terminal type)
*Notes: 1) Unless otherwise specified, the measurement conditions at the maximum scale time standard are specified to be the rated operating voltage (within 5% ripple
factor for DC), 20°C 68°F ambient temperature.
2) For the 1s range, the tolerance for each specification becomes ±10ms. When the power goes on, in rush current (0.3A) flows. Cautions should be taken. The
minimum power supplying time after forced reset input is 2s or more.
3) Between contacts of different pools for F8, F11R types only.
19
02/2003
PM4H-F
PRODUCT TYPE
Operation Protective Rated operating Terminal
Type Contact arrangement Time range Part Number
mode construction voltage type
100 to 120V AC 8 pin PM4HF8-S-AC120VW
200 to 240V AC 8 pin PM4HF8-S-AC240VW
3 selectable ranges over 24V AC 8 pin PM4HF8-S-AC24VW
1s to 10s
12V DC 8 pin PM4HF8-S-DC12VW
24V DC 8 pin PM4HF8-S-DC24VW
IP65
100 to 120V AC 8 pin PM4HF8-M-AC120VW
200 to 240V AC 8 pin PM4HF8-M-AC240VW
3 selectable ranges over 24V AC 8 pin PM4HF8-M-AC24VW
1 min to 10 min
12V DC 8 pin PM4HF8-M-DC12VW
Power 24V DC 8 pin PM4HF8-M-DC24VW
Relay Timed-out
PM4H-F8 OFF-delay
2 Form C 100 to 120V AC 8 pin PM4HF8-S-AC120V
(without reset)
200 to 240V AC 8 pin PM4HF8-S-AC240V
3 selectable time ranges 24V AC 8 pin PM4HF8-S-AC24V
over 1s to 10s
12V DC 8 pin PM4HF8-S-DC12V
24V DC 8 pin PM4HF8-S-DC24V
IP50
100 to 120V AC 8 pin PM4HF8-M-AC120V
200 to 240V AC 8 pin PM4HF8-M-AC240V
3 selectable time ranges 24V AC 8 pin PM4HF8-M-AC24V
over 1 min to 10 min
12V DC 8 pin PM4HF8-M-DC12V
24V DC 8 pin PM4HF8-M-DC24V
100 to 120V AC 8 pin PM4HF8R-S-AC120VW
200 to 240V AC 8 pin PM4HF8R-S-AC240VW
3 selectable time ranges 24V AC 8 pin PM4HF8R-S-AC24VW
over 1s to 10s
12V DC 8 pin PM4HF8R-S-DC12VW
24V DC 8 pin PM4HF8R-S-DC24VW
IP65
100 to 120V AC 8 pin PM4HF8R-M-AC120VW
200 to 240V AC 8 pin PM4HF8R-M-AC240VW
3 selectable time ranges 24V AC 8 pin PM4HF8R-M-AC24VW
over 1 min to 10 min
Power 12V DC 8 pin PM4HF8R-M-DC12VW
OFF-delay 24V DC 8 pin PM4HF8R-M-DC24VW
Relay Timed-out
PM4H-F8R (with
1 Form C 100 to 120V AC 8 pin PM4HF8R-S-AC120V
instantaneous
reset) 200 to 240V AC 8 pin PM4HF8R-S-AC240V
3 selectable time ranges 24V AC 8 pin PM4HF8R-S-AC24V
over 1s to 10s
12V DC 8 pin PM4HF8R-S-DC12V
24V DC 8 pin PM4HF8R-S-DC24V
IP50
100 to 120V AC 8 pin PM4HF8R-M-AC120V
200 to 240V AC 8 pin PM4HF8R-M-AC240V
3 selectable time ranges 24V AC 8 pin PM4HF8R-M-AC24V
over 1 min to 10 min
12V DC 8 pin PM4HF8R-M-DC12V
24V DC 8 pin PM4HF8R-M-DC24V
When ordering CE type, please order the Part No. with suffix CE. (e.g. PM4HF8-S-AC120VWCE)
20
02/2003
PM4H-F
Operation Protective Rated operating Terminal
Type Contact arrangement Time range Part Number
mode construction voltage type
11 pin PM4HF11R-S-AC120VW
100 to 120V AC
screw PM4HF11R-S-AC120VSW
11 pin PM4HF11R-S-AC240VW
200 to 240V AC
screw PM4HF11R-S-AC240VSW
11 pin PM4HF11R-S-AC24VW
IP65 24V AC
screw PM4HF11R-S-AC24VSW
11 pin PM4HF11R-S-DC12VW
12V DC
screw PM4HF11R-S-DC12VSW
11 pin PM4HF11R-S-DC24VW
24V DC
3 selectable time ranges screw PM4HF11R-S-DC24VSW
over 1s to 10s 11 pin PM4HF11R-S-AC120V
100 to 120V AC
screw PM4HF11R-S-AC120VS
11 pin PM4HF11R-S-AC240V
200 to 240V AC
screw PM4HF11R-S-AC240VS
11 pin PM4HF11R-S-AC24V
IP50 24V AC
screw PM4HF11R-S-AC24VS
11 pin PM4HF11R-S-DC12V
12V DC
screw PM4HF11R-S-DC12VS
Power 11 pin PM4HF11R-S-DC24V
OFF-delay 24V DC
Relay Timed-out screw PM4HF11R-S-DC24VS
PM4H-F11R (with
2 Form C 11 pin PM4HF11R-M-AC120VW
instantaneous 100 to 120V AC
reset) screw PM4HF11R-M-AC120VSW
11 pin PM4HF11R-M-AC240VW
200 to 240V AC
screw PM4HF11R-M-AC240VSW
11 pin PM4HF11R-M-AC24VW
IP65 24V AC
screw PM4HF11R-M-AC24VSW
11 pin PM4HF11R-M-DC12VW
12V DC
screw PM4HF11R-M-DC12VSW
11 pin PM4HF11R-M-DC24VW
24V DC
3 selectable time ranges screw PM4HF11R-M-DC24VSW
over 1 min to 10 min 11 pin PM4HF11R-M-AC120V
100 to 120V AC
screw PM4HF11R-M-AC120VS
11 pin PM4HF11R-M-AC240V
200 to 240V AC
screw PM4HF11R-M-AC240VS
11 pin PM4HF11R-M-AC24V
IP50 24V AC
screw PM4HF11R-M-AC24VS
11 pin PM4HF11R-M-DC12V
12V DC
screw PM4HF11R-M-DC12VS
11 pin PM4HF11R-M-DC24V
24V DC
screw PM4HF11R-M-DC24VS
When ordering CE type, please order the Part No. with suffix CE. (e.g. PM4HF11R-S-AC120VWCE)
DIMENSIONS OPERATION
• Screw terminal type (embedded mounting) • PM4H-F8 (no reset input) • PM4H-F8R/F11R (with reset input)
44.5
∅41
48
1.890 1.752 Time-delay Reset
0 contact input
N.O. T t
Time-delay Time-delay
contact contact
• Pin type (embedded mounting/surface mount) N.C. N.O.
12.0 Time-delay
48 .472 62.5 contact
1.890 2.461 N.C.
Note: t<T: Time setting
Tr: Minimum power supply application time
∅1.614
44.5
∅41
6.0 14.5
.236 .571
21
02/2003
PM4H-F
WIRING DIAGRAMS
• PM4H-F8 (no reset input) • PM4H-F8R (with reset input) • PM4H-F11R (with reset input)
Pin type Pin type Pin type
Time-delay 2C Time-delay 1C, with reset input Time-delay 2C, with reset input
N.O.
COM COM COM
(–) Operating (+) COM
(–) Operating (+)
voltage voltage COM
(–) Operating (+)
voltage
COM COM
Reset input
(+) Operating (–)
voltage
TIME RANGE
Time range
unit s range type min range type
Time range
1 0.04s to 1s 0.04 min to 1 min
5 0.2s to 5s 0.2 min to 5 min
10 0.4s to 10s 0.4 min to 10 min
22
02/2003
Notes for PM4H series
MODES & TIME SETTING
1) Operation mode setting [PM4H-A] 2) Time setting [common] 3) Time setting [common]
8 operation modes are selectable with 16 time ranges are selectable between To set the time, turn the set dial to a
operation mode selector. 1s to 500h. desired time within the range.
Turn the operation mode selector with Turn the time range selector with the Instantaneous output will be on when the
screw driver. screw driver. dial is set to “0”.
Operation mode is shown up through the Clockwise turning increases the time When the instantaneous output is used,
window above the mode selector. The range, and Counter-clockwise turning the dial should be set under “0” range.
marks are ON , FL , FO , OF1 , SF , OS , OF2 , OC . decrease the time range. (Instantaneous output area)
Turn the mode selector to the mark until Confirm the range selector position if it is When power supply is on, the time
you can check by clicking sound. correct. range, setting time and operation mode
Confirm the mode selector position if it is cannot be changed.
correct. Turn off the power supply or a reset sig-
If the position is not stable, the timer nal is applied to set the new operation
might mis-operate. mode.
20 30
Stop ring
0 0
SEC SEC
DATA • Load life curve (PM4H-A, PM4H-S, PM4H-W) • Load life curve (PM4H-M)
Load control life 1,000
Operations (×104)
Operations (×104)
100
0 1 2 3 4 5 6 0 1 2 3 4 5 6 7
Switching capacity (A) Switching capacity (A)
25
02/2003
Notes for PM4H series
CAUTIONS 2. Input connections No good
1) If the circuits is connected as in Fig. A,
1. Terminal connections Contact input
the internal circuits must be broken. Be (or non-contact input)
1) Refer to wiring diagram before termi-
sure to connect the circuit as in Fig. B.
nal connections.
Especially, for customer who has been
2) Use the screw terminal type for flush
used PM48A (Conventional type), be
mounting.
sure to check if the new circuit for PM4H
For using 8 pin type, use the timer with Fig. C
timer is corrected as in Fig. B.
screw terminal socket (AT8-RR) or 8 pin
cap (AD8-RC).
For using 11 pin type, use the timer with Input terminals Input terminals
T,Y,U T,Y,U
11 pin cap (AT8-DP11). Rated
PM4H-A PM4H-A
Do not solder directly the pin of the timer operating voltage
Stop input
26
02/2003
Notes for PM4H series
2) Connections of non-contact input 5. Cautions [Common] 4. For connecting and disconnecting
(open-collector) 1. Prevent using the timer in such places operating voltage to the timer, a circuit
where flammable or corrosive gas is should be used to prevent the flow of
generated, a lot of dust exists, oil is leakage current. For example, a circuit
Signal input
Reset input
Stop input
splashed or considerable shock and for contact protection as shown in Fig. A
vibration occur. will permit leakage current to flow
2. Since the main body cover is made of through R and C, causing erroneous
polycarbonate resin, prevent contact with operation of the timer. Instead, the circuit
Apply the open-collector connection. The
organic solvents such as methyl alcohol, shown in Fig. B should be used.
characteristics of the transistor used
benzine and thinner, or strong alkali
must be VCEO=10V or more, IC=10mA or
materials such as ammonia and caustic No good Good
more, and ICBO=6µA or less. Additionally,
soda.
the input impedance must be 1kΩ or Leak current
3. External surge protection may be R
less, and the residual voltage must be Power T Power T
required if the following values are supply
R C
supply
0.6V or less. C
exceeded. Otherwise, the internal circuit
3) Voltage input will be damaged. (Fig. A) (Fig. B)
27
02/2003