HEAT TREATMENT

T.C.L. Co. - Test & Control Laboratories


HEAD OFFICE: 116 AGIAS ELEOYSIS Str., 15125, AMAROYSION, ATHENS, GREECE
BRANCH OFFICES: 1. PATIMA, RATHIRI, ASPROPYRGOS 19300, ATTICA, P.O. Box 13101, GREECE
PHONE: +302105579375, FAX: +302105579376, MOBILE: +306944880908
2. AGROTEMACHIO 579, DIMOS ECHEDOROU, 57008, P.O. Box 1089
IONIA,THESSALONIKI, GREECE
PHONE: +302310722926, FAX: +302310722698, MOBILE: +306977637287
www.ad-ndt.gr e-mail: info@ad-ndt.gr
QUALITY CONTROL

RADIOGRAPHIC TEST REPORT


DATE: 30/07/2018 REPORT No: RT/T/18/167 PAGE NO: 1/1 DRAWING No:
CLIENT: ΠΟΣΕΙΔΩΝ ΑΤΕΒΕ CONTRACTOR: ΑΚΤΩΡ ΑΤΕ
CLIENT CODE : 115-001-RT-THES SUBCONTRACTOR:
MTH-2A – ΥΔΡΟΗΛΕΚΤΡΙΚΟ ΕΡΓΟ
PROJECT: ΜΕΤΣΟΒΙΤΙΚΟΥ PLACE:Metsovo ‘B’ SYMBOL: YES
MATERIAL: CS (as stated by client) SAMPLE RECEIVED DATE: - HEAT TREAT.: No
TEST ACCORDING TO: EN ISO 17636-1 ACC.STANDARD ACCORDING TO: EN ISO 10675-1
RAD.SOURCE: IR-192 EXP.TIME: 22min ACTIVITY: 20Ci SOURCE SIZE: 2*2 mm
FILM: D5 DENSITY: 2-4 SCREENS: 0.02mm IQI: 10-16 FILM SIDE/SOURCE SIDE
o
DISTANCE: PROC.TECHNIQUE: TEMP.: 23 C SWSI/DWSI/DWDI
X-RAY: KV: mA: WELDING METHOD: REMARKS:
CONCLUSION
DENSITY

I.Q I. V

ITEM JOINT NO ZONE FAULTS A.D. T.P. REMARKS


A. N.A. A. N.A.

Φ1200 WR10 0-40 2,9 W14 8.00 FF *


40-80 *
80-125 *
125-170 Aa *
170-210 *
210-255 *
255-300 *
300-340 *
340-0 *
Φ1200 WR11 0-40 2,9 W14 8.00 *
40-80 Aa * Aa(38-41)/Aa(52-55)
80-125 *
125-170 *
170-210 Aa *
210-255 Aa *
255-300 Aa *
300-340 *
340-0 *

I.Q.I.V:IMAGE QUALITY
Aa: GAS PORES D : INCOMPLETE PENETRATION Ru :ROOT CONCAVITY
INDICATION VALUE
Ab: WORM HOLES Ea : LONGITUDINAL CRACKS Tr: EXES. PENETRATION
I.Q.I.: IMAGE QUALITY
Ba: SLAG INCLUSIONS Eb :TRANSVERSE CRACKS Ti: TUNGSTEN INCL.
INDICATION
Bb: SLAG LINES F :UNDERCUT FF : FILM DEFECT
A :ACCEPTED
C : INCOMPLETE FUSION KV :LINEAR MISALIGNMENT
N.A. : NON ACCEPTED
REPORT APPROVED APPROVED FOR TEST RESULTS BY: TEST MADE BY:
BY T.P.: OWNER BY: REPORT APPROVED BY: AVDAMALINOS M.
AVRAMIDIS EL.
LEVEL II RT/PT/MT/UT
TEST DATE:
30/07/2018
DIPSAKIS D.
LEVEL II RT/PT/UT/VT
The report shall not be reproduced except in full without the written approval of the testing laboratory.
The test results relate only to the items tested.
The laboratory keeps the tested items for two months after the test date.

Ε331RT/8 ΑΒΡΑΜΙΔΗΣ ΕΛ. ΔΙΨΑΚΗΣ ΑΝΤ. Ο.Ε ΔΙΑΧΕΙΡΙΣΗ ΠΟΙΟΤΗΤΑΣ Βλ. Δ 330

Δοκιμές
Αρ. Πιστ. 159-4
3
(600)

WR-10
Ø1220x10

01.1 01.5 ΛΕΠΤΟΜΕΡΕΙΑ Β


03.5
20xM24 / Tk Ø620
Ø1220x10

Ø1020x10

WR-11
1220

200
(1408)

2050 518

DN100/PN10
4xØ18 /Tk Ø170

400 600 2566

ΛΕΠΤΟΜΕΡΕΙΑ Γ 04
06