Professional Documents
Culture Documents
HeatGain Example
HeatGain Example
For Assignment 8: Heat Gain – Cooling Load Estimate, please download the assignment from the ET1 website –
“http://web.dcp.ufl.edu/mgold/ET1/ET1homepg.htm”. It must be done in a spreadsheet format. An example of
Excel spreadsheet is also available on the website.
PROCEDURE
The following steps outline the procedure for estimating the cooling load (in Btu/hr) for the example problem –
classroom space defined above.
d. Summary
Floor Area (SF) Total CFM Air Requirement (CFM) Total Space Cooling Load, QS (Btu/hr)
750 1,125 27,945
e. Summary
Total CFM Ventilation Sensible Heat Gain Latent Heat Gain Total Ventilation Load
(CFM) Qsensible (Btu/hr) Qlatent (Btu/hr) QV = Qsensible + Qlatent (Btu/hr)
300 12,960 29,040 42,000
Total Space Cooling Load CFM Total Ventilation Load CFM Total Cooling Load CFM
1,125 300 1,425
Based on the total required CFM for each space, we can size the VAV or the mixing box for each space, and
using a group of zones, we can size the Air Handling Unit (AHU).
Total Space Cooling Load Total Ventilation Load Total Cooling Load
QS (Btu/hr) QV (Btu/hr) QTotal (Btu/hr)
27,945 42,000 69,945
Tons of cooling are used to choose and size refrigeration equipments such as chillers and cooling towers.
Note: The HVAC system design – selection of air delivery system types, and sizing and layout of the required
equipments – will be done in Homework Assignment 9 based on 3. Total CFM Air Requirement and 4. Total
Cooling Required above.