1.dresser Rand Surge Control

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Surge Control

Control Systems
A surge controller typically measures a function of
Introduction pressure rise versus flow. The controller operates a
surge valve to maintain sufficient forward flow to
Dresser-Rand has been a leading designer and
prevent surge.
supplier of surge control systems for centrifugal and
axial compressors for over thirty five years. Surge Control Algorithm
Recent innovations in control technology have made Dresser-Rand's method of accurately defining the
it possible to supply surge control systems which are surge point over a wide range of changing conditions
capable of coping with rapid flow fluctuations and makes it possible to set the control line for optimum
process gas variations. Current surge control surge protection without unnecessary re-cycling.
systems from Dresser-Rand Control Systems This method automatically compensates for changes
provide protection against surge with more efficient in molecular weight, temperature, compressibility,
compressor operation, especially in process pressure and compressor rotor speed.
applications that involve variations in the gas mixture
and temperature. The system utilizes a characterization of
compression ratio (Pd/Ps) versus compensated
Several surge methods are in use today, each with compressor inlet flow function (hs / Ps)1/2 as control
its own approximations and consequent inac- parameters. This algorithm allows for use of the
curacies. Operating the compressor safely in spite of Dresser-Rand surge control system on most
these inaccuracies is usually accomplished by applications, resulting in minimized recycle or blow-
establishing the surge controller flow set point based off flow. This method reduces the initial cost and
on the expected worst case operating conditions. simplifies engineering, testing, operation, and
This worst-case flow set point may be excessive for maintenance associated with the system when
normal operating conditions but is necessary in order compared to alternative methods.
to provide for safe operation at all expected
operating conditions. The input signals required to facilitate use of the
surge control algorithm on centrifugal compressors
This worst-case setting approach can result in are the suction flow differential pressure, suction
inefficient compressor operation caused by excess pressure and discharge pressure as indicated in
recycle or blow-off flow and wasted energy. Figure 1.
A more practical surge control method, which uses a
Universal Performance Curve, has been developed
and patented by Dresser-Rand. The Universal
Performance Curve method offers several benefits
when compared to traditional surge control methods. TURBINE COMPRESSOR
It provides extremely accurate surge control by
defining the surge point over a wide range of process SUCTION DISCHARGE
gas conditions. This method makes it possible to FE

position the control line for optimum surge protection


which eliminates unnecessary recycling and FT PT PT

increases overall plant operating efficiency. FV

Compressor Surge and Measurement SC


I/P
Centrifugal and axial compressors will surge when FY

forward flow through the compressor can no longer


be maintained, due to an increase in pressure
across the compressor, and a momentary flow
Figure 1. Required Input Signals
reversal occurs. Once surge occurs, the reversal of
flow reduces the discharge pressure or increases the
suction pressure, thus allowing forward flow to
resume again until the pressure rise again reaches
the surge point.

This surge cycle will continue until some change is


made in the process or compressor conditions.
The output to the valve is forced to decrease in
discrete, timed steps, thus opening the surge valve
much quicker than possible with conventional PI
control. Valve opening steps are initiated until the
Surge Control Operation flow has moved to a safe level.
Figure 2 illustrates the use of the universal surge Compressor surge is avoided by this quick
control map. The compressor flow set point is incremental control of the surge valve thus
provided by the control line. The location of the minimizing the effects of process upsets.
control line in comparison to the surge line depends
on the slope of the speed lines of the map. The
control line is positioned to the right of the surge line Set Point Shift
which provides a safety margin for the surge If the flow decreases to the backup line a
controller PI (Proportional & Integral) algorithm. The predetermined number of times (adjustable) within a
PI control loop is used to compare the control set given time period (indicating a recurring problem) the
point to the operating point of the compressor and surge control set point is shifted a percentage of full
provides an output to the surge valve to prevent the scale flow (i.e. 2%) in the direction of higher flow.
flow from decreasing below the control line. When a This action establishes a larger margin of safety from
safe relationship between the control line and the the surge line. The flow set point continues to be
surge line is determined, this relationship is shifted as necessary until the backup line crossings
configured into the surge controller. cease, or to a maximum of ten percent greater than
Under normal operating conditions, PI control is used the control line value.
and surge control action is initiated at the control line The intent of the set point shift is to prevent surge
by opening the surge valve as required to maintain until the cause of the instability can be corrected.
forward flow through the compressor. This prevents The shifted set point remains in effect until reset by
a further shift of the operating point to the left the operator.
towards surge.
In the case of rapid reductions in flow, such as
process upsets, three additional controls are Floating Proportional Algorithm
implemented. Derivative action as applied in a conventional PID
First, a backup line, located between the control line controller, under normal compressor operating
and the surge line, is used. If the compressor conditions, would tend to make the system unstable
operating point moves to the left of the control line and therefore is not used. However, for some fast
and reaches the backup line, Dresser-Rand's Closed changing conditions, the normal PI control response
Loop Step Logic will quickly force the surge valve is not sufficient to prevent flow from decreasing to
open as required to increase forward flow through values less than the control line.
the compressor. In general, the controller needs to be slow for normal
Second, if the operating point of the compressor operating conditions, but fast when needed to protect
reaches the backup line a set number of times (i.e. the compressor from surge. During rapid decreases
3), within a specified period of time (i.e. 5 minutes), in flow near the surge control line, Dresser-Rand
the control set point will be shifted to the right via uses a Floating Proportional control algorithm to
Dresser-Rand's Set point Shift Logic. open the surge valve before the operating point
reaches the control line
Third, a variable proportional gain action has been
added to the control loop to assist in stabilizing the Normal PI control is resumed when the process
process when rapid decreases in compressor flow upset has been stabilized.
are encountered.

Step Logic
The backup line is positioned between the surge line
and the control line and provides a basis for
additional control action. If the operating point of the
compressor decreases to flow values less than those
defined by the backup line, traditional PI control is
enhanced by the Closed Loop Step Logic control
function to facilitate rapid opening of the surge valve.
Y AXIS
BACKUP LINE

CONTROL LINE

SURGE LINE SHIFTED SET POINT

SET POINT
COMPRESSOR
OPERATING
POINT

%N

RTZ
INCREASING FLOW

X AXIS

"X AXIS" - Percent Flow Function = K1 * Q/(RTZ)1/2 = K2 (hs/Ps)1/2


"Y AXIS" - Pressure Ratio Function (Pd/Ps) - 1

Figure 2. Compressor Surge Contol Map

Field Devices and Process Designs


Implementation Compressor surge is a phenomenon which can
There are two methods of implementing the Dresser- occur very rapidly during upsets in process
Rand surge control algorithm. conditions. Proper surge control requires not only an
appropriate control algorithm and a dedicated control
The first method uses the DI-TRONICS IV control strategy but, also specific attention to the field
system. This PLC (Programmable Logic Controller) devices and process design.
based control system incorporates surge control as
an integral part of the PLC program without the need Flow measuring devices should be located such that
for additional external hardware. Compressor inlet gas disturbances will be minimized (less noise), and
flow, suction pressure, and discharge pressure designed for the full operating range of the
measurements are input directly into the system compressor.
using standard PLC analog inputs. The tuning Transmitters should be located as close as possible
parameters are displayed and adjusted from an to the source of measurement to minimize reaction
Operator Interface (OI) screen. Compressor curves, time.
with the operating point, control line and back-up line
are displayed on the Operator Interface monitor. The Surge valves should provide a full stroke response
system parameters are trended and displayed on the preferably within 1 second, but no more than 2
Operator Interface monitor. seconds.

The second method utilizes a stand-alone controller The surge valve should be linear and should be
and is offered for installations which do not require a sized in accordance with the compressor maps and
PLC, or for those applications where the PLC used is expected operating conditions.
not capable of providing adequate surge control. Since the effects of opening the surge valve are a
Both systems utilize the Universal Performance decrease in compressor discharge pressure and/or
Curve concept. an increase in suction pressure, to increase flow
through the compressor, process and piping
designers should minimize, as much as practical, the
piping volume in the recycle path and the volume
between the compressor and the discharge check
valve.
Z Compressibility factor to correct for the
deviation from the ideal gas law.

Subscripts
Controller Specifications
d Discharge
PLC Based s Suction

Will be identical to the PLC hardware specifications Instrument Symbols


Stand-Alone
SC Surge Controller
FE Primary Flow Element
Analog Inputs (5) 1 - 5 Volt FT Flow Transmitter
Analog Outputs (3) 4 - 20 mA FV Flow Control Valve
Discrete Inputs (3) PT Pressure Transmitter
Discrete Outputs (4)

Operating Temperature 0 to 50o C


Storage Temperature - 40 to 85o C References
Humidity 5 to 95%
Gaston, J.R. "Turbocompressor Antisurge Control,
Electrical Classifications FM, CSA New Solution for an Old Problem", The American
Society of Mechanical Engineers 92-GT-428,
Class 1 Division 2 Groups A,B,C and D rated Presented at the International Gas Turbine And
Aeroengine Congress and Exposition, Cologne,
Optional Serial Interface Available Germany (June 1-4, 1992)

Rigoni, K.B. "Anti-Surge Control Algorithm",


Dresser-Rand Control Systems
Nomenclature (S.I. Units in parenthesis)
ACFM Actual Cubic Feet Per Minute (M3/Hr =
1.6999 ACFM)
h Differential pressure produced by flow
through the flow element
K Proportionality constant
MW Molecular Weight
N Compressor rotor speed, RPM
P Pressure, PSIA, (KPa)
Q Volumetric flow rate at flowing conditions,
ACFM (M3/Hr)
R0 Universal gas constant
R Gas constant R0/MW
T Temperature, oR (oK)

Control Systems
1202 W. Sam Houston Pkwy. North
Houston, TX 77043
Phone: (713) 973-5312
FAX: (713) 365-2660
control_systems@dresser-rand.com

SC0498

You might also like